Plan Review Details - Permit 04060622
Plan Review Stops For Permit 04060622
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-23 Cont ID  
Sent By jwitmer Date 2005-02-23 Time 08:04 Rev Time 0.33
Received By jwitmer Date 2005-02-23 Time 08:04 Sent To  
Notes
2005-02-23 00:00:00TRASH COMPACTOR CONCRETE MIX DESIGN 3500
 PSI

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-15 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 16:12 Rev Time 0.50
Received By mjacobs Date 2004-07-15 Time 08:51 Sent To PC
Notes
2004-07-15 00:00:00BLDG PRIVISO FBC SEC. 11-4.8.4(3)
 IF RAMPS CHANGE DIRECTION AT LANDING
 THE MINIUM LANDING SIZE SHALL BE 5'X5'

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-17 Cont ID  
Sent By mjacobs Date 2004-06-17 Time 15:55 Rev Time 1.00
Received By mjacobs Date 2004-06-17 Time 15:57 Sent To PC
Notes
2004-06-17 00:00:00BLDG PROVISO
 1)11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)805-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-07-28 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 16:12 Rev Time 0.33
Received By dpalmer Date 2004-07-28 Time 16:12 Sent To B
Notes
2004-07-28 00:00:00*** REDLINED ***
  
 1)NOTE: PLANS STILL SHOW 100A OCP FOR
 10HP MOTOR.
 PLEASE SEE TABLE IN NEC 430 AND PLEASE
 SEE OCP 125% OF MOTOR LOAD WHICH IS
 SHOWN AS 50A'S IN NEC TABLE.
 THIS WILL NEED TO BE CORRECTED IN FIELD.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-07 Cont ID  
Sent By csiegber Date 2004-07-22 Time 14:19 Rev Time 0.33
Received By dpalmer Date 2004-07-07 Time 16:14 Sent To  
Notes
2004-07-07 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE A COMPLETELY NEW
 ELECTRICAL RISER IS NOW SUBMITTED.??
 PLEASE SEE PLANS FOR COMPACTOR HAVE NOT
 BEEN REVISED TO SHOW CORRETC RISER.
  
 2)NOTE: PLEASE SEE RISER INDICATES 100A
 OCP FOR 10HP TRSH COMPACTOR MOTOR?
 PLEASE VERIFY THIS AND ALSO SEE 430.148
 FOR SIZING OF OCP.
  
  
 PLEASE CORRECT TRSH CMP PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-16 Cont ID  
Sent By dpalmer Date 2004-06-16 Time 16:20 Rev Time 0.33
Received By dpalmer Date 2004-06-16 Time 16:20 Sent To  
Notes
2004-06-16 00:00:00************* UNSAT **********
  
 1)NOTE: PLEASE CORRELATE CONDUCTORS ON
 RISER DIAGRAM.
 SERVICE IS SHOWN AS 3/PHASE.
 PLEASE SEE 250.6,250.24
 SEC'S WOULD CONTAIN NEUTRAL TO FIRST
 MEANS OF DISCONNECT.
 215.5
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 12:46 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 12:46 Sent To B
Notes
2005-02-14 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 12:37 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 12:37 Sent To B
Notes
2005-02-14 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 13:00 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 13:00 Sent To B
Notes
2005-02-11 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 12:59 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 12:59 Sent To B
Notes
2005-02-11 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 16:00 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 16:00 Sent To B
Notes
2005-02-09 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 15:59 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 15:59 Sent To B
Notes
2005-02-09 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 15:57 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 15:57 Sent To B
Notes
2005-02-09 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 15:56 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 15:56 Sent To B
Notes
2005-02-09 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 14:18 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 14:18 Sent To E
Notes
2004-07-22 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 13:07 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 13:07 Sent To  
Notes
2004-07-02 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-17 Cont ID  
Sent By mjacobs Date 2004-06-17 Time 16:09 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 15:10 Sent To PC
Notes
2004-06-15 00:00:00TO COMM BD #1