Plan Review Details - Permit 04060620
Plan Review Stops For Permit 04060620
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By jwitmer Date 2005-02-23 Time 08:42 Rev Time 0.22
Received By jwitmer Date 2005-02-23 Time 08:42 Sent To  
Notes
2005-02-23 00:00:00GATES: CONCRETE DESIGN MIX

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-06 Cont ID  
Sent By shill Date 2004-10-06 Time 10:44 Rev Time 1.00
Received By shill Date 2004-10-06 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-07-13 Cont ID  
Sent By shill Date 2004-07-13 Time 14:11 Rev Time 1.00
Received By shill Date 2004-07-13 Time 14:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-11-29 Cont ID  
Sent By dpalmer Date 2004-11-29 Time 16:02 Rev Time 1.00
Received By dpalmer Date 2004-11-29 Time 14:58 Sent To B
Notes
2004-11-29 00:00:00SENT TO BLDG TO ADJUST VALUE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-11-03 Cont ID  
Sent By dpalmer Date 2004-11-03 Time 14:30 Rev Time 0.50
Received By dpalmer Date 2004-11-03 Time 14:30 Sent To FIRE
Notes
2004-11-03 00:00:00********** UNSAT3RD REVIEW *******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SUBMIT SPECS ETC FOR GATE
 CONTROLS/MOTORS ETC.
 SEE FIRE REVIEW NOTES INCASE OF POWER
 FAILURE.
 MUST SHOWS LISTING BY A NRTL.
  
 2)NOTE: PLEASE SEE ONLY TWO SETS WERE
 BROUGHT BACK IN, THREE SETS ARE REQUIRED
 FOR A THRESHOLD JOB.
  
 3)NOTE: PLEASE REMOVE ELECTRICAL FROM
 BLDG SHEETS NOW NEW ELECTRICAL IS SHOWN
 ON "E-SHEETS".
  
 *** PLEASE BE SURE CONTRACTOR PICKS UP
 PLANS WHEN REVIEWS ARE COMPLETED.*****
 PLANS ARE TO BE RE-SUBMITTED AS A
 COMPLETE PACKAGE WITH APPLICATION AND
 ALL PAPERWORK.
 PLANS CAME IN AS REVISIONS. REVISIONS
 ARE ONLY SUBMITTED AFTER PERMIT HAS BEEN
 ISSUED. THESE ARE RE-SUBS.
  
 PLEASE REMOVE ALL/OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
  
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESTITATE TO CALL. THIS
 WILL HELP IN AVOIDING DELAYS IN
 PROCESSING FOR PERMIT.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-10-27 Time 15:17 Rev Time 0.25
Received By dpalmer Date 2004-09-21 Time 06:44 Sent To  
Notes
2004-09-21 00:00:00***** UNSAT ****
  
 1)NOTE: PLEASE SEE A PANEL SCHEDULE IS
 NOW SUBMITTED SHOWING GATES TO BE
 ELECTRICAL, HOWEVER NO INFORMATION ON
 THESE GATES/MOTORS/ DISCONNECTING MEANS
 IS SHOWN ON NEW SHEETS.?
 SPECS FOR THE ABOVE MUST BE SUBMITTED
 SHOWING ALL LISTING(S). PLEASE ALSO SEE
 FIRE REVIEW COMMENTS FOR POSSIBLE
 COMMENTS FOR GATE OPERATORS.
  
 2)NOTE: PLEASE SEE "EXISTING" PANEL DP
 INDICATES SIGN CIRCUIT WHICH PLANS SHOW
 GOING TO TWO SCONCES. IS THIS CORRECT?
 IS THE "SIGN" MALIBU BAY NOT GOING TO BE
 LIT?
  
 3)NOTE: PLEASE SEE ONLY TWO SETS OF PLAN
 -S WERE SUBMITTED. PLEASE SUBMIT THE
 REQUIRED THREE DUE TO THIS JOB BEING A
 THRESHOLD JOB.
  
 4)NOTE: PLEASE CLARIFY WHERE LIGHTING
 ON GATE COLUMNS ARE GOING TO FED?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-16 Cont ID  
Sent By jleahy Date 2004-06-16 Time 14:31 Rev Time 0.30
Received By jleahy Date 2004-06-16 Time 14:29 Sent To  
Notes
2004-06-16 00:00:00NO CIRCUITS SHOWN FOR ANY ELECTRIC
  
 IS SIGN ELECTRIC?
  
 IS GATE ELECTRIC?
  
 WHERE DOES CALL BOX COME FROM?
  
 QUESTIONS CALL JAKE LEAHY 805-6740

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-11-09 Cont ID  
Sent By nmccray Date 2004-11-09 Time 10:58 Rev Time 0.00
Received By nmccray Date 2004-11-09 Time 10:36 Sent To  
Notes
2004-11-09 00:00:00COMMENTS AND NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1) FIRE DEPARTMENT REQUIRES 20 FEET WIDE
 MINIMUM OPENING FOR ACCESS.
  
 2) IS THERE A KNOX-KEY OPERATED CONTROL
 GATE.
  
 3) THIS GATE OPERATION HAVE TO BE FAIL
 SAFE POWERED.
  
 4) CUT SHEETS AND SPEC'S ON THE GATES
 CONTROLS AND EQUIPMENT.
  
 5) SEPARATE PLANS AND PERMIT APPLICATION
 MAYBE REQUIRED FOR THE GATE AND
 CONTROLS.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-09-21 Cont ID  
Sent By nmccray Date 2004-09-21 Time 14:58 Rev Time 0.00
Received By nmccray Date 2004-09-21 Time 14:58 Sent To  
Notes
2004-09-21 00:00:00***********DENIED***********************
  
 COMMENTS AND NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED. INFORMED
 DONNA VIA PHONE ON 9-21-04
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-07-13 Cont ID  
Sent By nmccray Date 2004-07-13 Time 14:44 Rev Time 0.00
Received By nmccray Date 2004-07-13 Time 14:44 Sent To  
Notes
2004-07-13 00:00:00*********DENIED*************************
 1) ENTRY GATE SHOWS 14 FEET WIDE SWING
 OPENING. FIRE DEPARTMENT REQUIRES 20
 FEET WIDE MINIMUM OPENING FOR ACCESS.
 OR DOES BOTH GATES OPEN MAKING IT 28
 FEET OPENING.
  
 2) HOW WILL FIRE DEPT GAIN ACCESS THRU
 THE SECURITY GATES, IS THERE KNOX-BOX
 KEY OPERATED CONTROL.
  
 3) WILL THESE GATES BE FAIL SAFE POWERED
  
 4) SEPARATE PLANS AND PERMIT APPLICATION
 MAYBE REQUIRED WITH CUT SHEETS ON THE
 GATES CONTROLS AND EQUIPMENT.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 12:47 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 12:47 Sent To B
Notes
2005-02-14 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 12:37 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 12:37 Sent To B
Notes
2005-02-14 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 12:48 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 12:48 Sent To B
Notes
2005-02-11 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 16:52 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 16:52 Sent To B
Notes
2005-02-09 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 16:50 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 16:50 Sent To B
Notes
2005-02-09 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 16:48 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 16:48 Sent To B
Notes
2005-02-09 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 16:47 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 16:47 Sent To B
Notes
2005-02-09 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-19 Cont ID  
Sent By mjacobs Date 2004-11-19 Time 10:46 Rev Time 0.00
Received By mjacobs Date 2004-11-19 Time 10:46 Sent To E
Notes
2004-11-19 00:00:00SENT TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-27 Time 15:17 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 15:17 Sent To E
Notes
2004-10-27 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-09-16 Time 08:31 Rev Time 0.00
Received By csiegber Date 2004-09-16 Time 08:31 Sent To  
Notes
2004-09-16 00:00:00TO COMM BD#18

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 16:56 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 16:56 Sent To  
Notes
2004-09-15 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:41 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 15:41 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-15 Cont ID  
Sent By mmclean Date 2004-07-22 Time 11:33 Rev Time 0.00
Received By mjacobs Date   Time   Sent To  
Notes
2004-06-15 00:00:00TO COMM BD #60

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-06 Cont ID  
Sent By shill Date 2004-10-06 Time 10:38 Rev Time 0.50
Received By shill Date 2004-10-06 Time 10:38 Sent To  
Notes
2004-10-06 00:00:00OK PER DAVID KANNING

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:41 Rev Time 0.00
Received By mmclean Date 2004-07-22 Time 11:33 Sent To I
Notes
2004-07-22 00:00:00DENIED, BY DAVID KANNING, PLANNER
 659-8031.ENTRACE SIGN DOES NOT MATCH
 THE APPROVED SIGN PLAN, THE ORNAMENTAL
 FEATURES OF THE ENTRANCE COLUMNS &
 ENTRANCE GATES EXCEED 10% OF HEIGHT
 LIMITATION.CALLED CONTR