Plan Review Details - Permit 04060600
Plan Review Stops For Permit 04060600
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-03 Cont ID  
Sent By alange Date 2004-08-03 Time 13:56 Rev Time 0.50
Received By alange Date 2004-08-03 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-03 Cont ID  
Sent By alange Date 2004-08-03 Time 11:10 Rev Time 1.00
Received By alange Date 2004-08-03 Time 11:06 Sent To  
Notes
2004-08-03 00:00:00DENIDE
 DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.ADDITIONAL PERMIT FEES ARE STILL DUE
 OF $81.01
  
 3.INSERT APPROVED MECHANICAL PAGES AND
 REMOVE NEW MECH. PAGES.
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By btrobaug Date 2004-08-02 Time 18:32 Rev Time 1.50
Received By alange Date 2004-06-30 Time 10:42 Sent To  
Notes
2004-06-30 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3.SIGN OWNER/AGENT ON ENERGY CALCS.
 R VALUE ON CALCS DON'T MATCH PLANS.
  
 4.A TITLE BLOCK WITH ALL INFORMATION
 PER 61G1-16 - 16.004 IS REQUIRED ON
 PLANS.DATE REQUIRED WITH SIGNATURE.
  
 5.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUE HAS BEEN ADJUSTED
 ACCORDINGLY.310 SQ. FT. X 76.96 PER
 SQFT. = $23,857ADDITIONAL PERMIT
 FEES ARE DUE.
  
 6. SUBMIT 2 COPIES OF ROOFING PRODUCT
 APPROVALS OR OBTAIN A SEPERATE ROOFING
 PERMIT.
  
 7.SAFTEY GLAZING FOR BATHROOM WINDOW
 "A" MUST COMPLY WITH SEC 2405.2.1 FBC
 SHOW ON PLAN.
  
 8.ON ROOF FRAMING PLAN CHECK
 EMBEDMENT OF ANCHORS FOR LEDGER.
 SPECIFY BOLT SIZE, LENGTH AND EMBEDMENT.
  
 9.IN BEDROOM 2 EXISTING REMAINING
 WINDOW SHALL COMPLY WITH 1005.4 FBC
 FOR AN EMERGENCY ESCAPE RESCUE OPENING.
 SHOW ON PLAN.
  
 10.DOOR #6 IS AN INSWING DOOR,
 PRODUCT APPROVAL IS FOR AN OUT-SWING
 DOOR.SUBMIT CORRECT PRODUCT APPROVAL
 OR CHANGE DOOR SWING.
  
 11.THERE ARE PRODUCT APPROVALS FOR
 1" CLIPPED MULLIONS.WHERE WILL THEY BE
 USED.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-02 Cont ID  
Sent By btrobaug Date 2004-08-02 Time 18:32 Rev Time 0.50
Received By btrobaug Date 2004-08-02 Time 17:56 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-07-22 Time 12:41 Rev Time 0.50
Received By btrobaug Date 2004-06-16 Time 16:08 Sent To P
Notes
2004-06-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE PER 210.11C3.
  
 2} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6',12' RULE. SEE GUEST
 SITTING ROOM.
  
 3} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 4} SMOKE DETECTORS ARE REQUIRED PER 8-1.
 4.1.6.2 NFPA-72.
  
 5} A TITLE BLOCK WITH ALL INFORMATION
 PER 61G1-16.004IS REQUIRED ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 12:41 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 12:41 Sent To E
Notes
2004-07-22 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-16 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 08:43 Rev Time 0.00
Received By mjacobs Date 2004-06-16 Time 08:43 Sent To E
Notes
2004-06-16 00:00:00SENT TO E BOX/ADDITION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-14 Cont ID  
Sent By mmclean Date 2004-06-15 Time 16:16 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 15:26 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-29 Cont ID  
Sent By jleech Date 2004-06-28 Time 19:54 Rev Time 0.25
Received By pkrauss Date 2004-06-29 Time 16:40 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-06-28 Cont ID  
Sent By btrobaug Date 2004-06-16 Time 17:16 Rev Time 0.33
Received By jleech Date 2004-06-28 Time 19:53 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 15:26 Rev Time 0.00
Received By mmclean Date 2004-06-15 Time 16:16 Sent To I
Notes
***NONE***