Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-06-24 Cont ID  
Sent By pkrauss Date 2004-06-22 Time 08:09 Rev Time 0.00
Received By mcarsill Date 2004-06-24 Time 12:53 Sent To  
Notes
2004-06-24 00:00:001) PROVIDE SEPARATE PLANS AND PEMITS
 FOR REQUIRED FIRE SUPPRESSION SYSTEM.
  
 2) SUBMIT DUCTWRAP INFORMATION.
  
 3) FUEL SHUNT REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 08:33 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 08:33 Sent To M
Notes
2004-06-15 00:00:00TO PK BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-22 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 08:33 Rev Time 0.45
Received By pkrauss Date 2004-06-22 Time 08:06 Sent To FIRE
Notes
2004-06-22 00:00:00PROVISO:
 PLEASE NOTE, THE PLAN DOES NOT INDICATE
 THE DISTANCE BETWEEN THE SF-1 AND THE
 PARAPET WALL.PROVIDE ENOUGH CLEARANCE
 AS TO SERVICE PROPERLY & THE INTAKE HAS
 FREE SURFACE AREA FOR PROPER AIR FLOW.
  
 PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS ON THE JOBSITE FOR THE 3M
 FASTWRAP+ AT THE TIME OF INSPECTION.
 WELDS ARE TO BE INSPECTED PRIOR TO
 COVERING.
  
 ADDITIONAL PERMIT REQUIRED FOR FIRE
 SUPPRESSION.PLEASE PROVIDE PLANS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.