Plan Review Details - Permit 04060556
Plan Review Stops For Permit 04060556
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 16:28 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:28 Rev Time 0.35
Received By pkrauss Date 2004-06-18 Time 11:34 Sent To  
Notes
2004-06-18 00:00:00PROVISO:
 TRANSFER GRILLE FROM BEDROOM WITH 300
 CFM OF SUPPLY AIR, PER THE REVISED 2001
 FBC(M) 601.4 EXCEPTION #2 - TRANSFER
 GRILLES SHALL USE 50 SQ IN OF GRILLE
 AREA TO 100 CFM OF SUPPLY AIR.PLEASE
 SIZE TRANSFER GRILLE ACCORDINGLY.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.