Plan Review Details - Permit 04060548
Plan Review Stops For Permit 04060548
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-26 Cont ID  
Sent By alange Date 2004-10-26 Time 11:45 Rev Time 1.50
Received By alange Date 2004-10-26 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-19 Time 16:30 Rev Time 0.00
Received By alange Date 2004-10-26 Time 11:44 Sent To  
Notes
2004-10-18 00:00:00 
 DENIED
 NOTES FROM LAST 2 REVIEWS:
  
 3.PRODUCT APPROVALS FOR DOOR MULLIONS
 STILL MISSING, SUBMIT 2 COPIES.
 ALTUSA ROOF TILE, SUBMIT DCA APPROVAL
 SHOWING STYLE OF TILE BEING USED WITH
 FL-NUMBER.
 PGT FIXED WINDOW MISSING SECOND COMPLETE
 SET OF PRODUCT APPROVALS.
 PGT CASEMENT WINDOW MISSING ONE COMPLETE
 SET OF PRODUCT APPROVALS.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-09-23 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:32 Rev Time 1.50
Received By alange Date 2004-09-23 Time 08:02 Sent To  
Notes
2004-09-23 00:00:00DENIED
  
 ITEMS NEEDED FROM LAST REVIEW:
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS MISSING FOR THE
 FOLLOWING;FIXED AND CASEMENT WINDOW,
 DOOR MULLIONS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8. CORRECTION WAS MADE ON A-1 WITH WHITE
 OUT. NOT PERMITTED.
  
 9.SHOWING CODE SECTIONS IS NOT
 SUFFICENT.SHOW HOW YOU ARE COMPLYING
 WITH THIS SECTION.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By pkrauss Date 2004-09-20 Time 07:48 Rev Time 2.75
Received By alange Date 2004-06-30 Time 16:01 Sent To  
Notes
2004-06-30 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT 2 COPIES OF ALL PRODUCT
 APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 5.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUATION HAS BEEN CHANGED TO
 $306,800.ADDITIONAL PERMIT FEES OF
 $1012.68 ARE DUE.SQUARE FOOTAGE HAS
 BEEN ADJUSTED TO REFLECT PLANS.
 3500SQ. FT. X 76.96 = 269,360AC
 900SQ. FT. X 41.60 = 37,440 OTHER
  
 6. SEE OTHER REVIEWERS NOTES REGARDING
 ARCHITECT SIGNING, SEALING AND DATING
 AND TITLE BLOCK INFO.
  
 7.PLEASE SHOW ATTIC ACCESS SIZE.
  
 8.PRODUCT APPROVALS ARE FOR AN
 OUT-SWING DOOR, PLAN SHOWS INSWING.
 PLEASE REVISE.
  
 9.1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
 PLEASE SHOW DETAIL ON PLAN.
  
 10.A SEPERATE DEMO PERMIT IS REQUIRED
 FOR DEMO/REMOVAL OF EXISTING BUILDING.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-13 Cont ID  
Sent By btrobaug Date 2006-11-13 Time 06:56 Rev Time 0.50
Received By btrobaug Date 2006-11-13 Time 06:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-11-01 Cont ID  
Sent By btrobaug Date 2006-11-01 Time 14:10 Rev Time 1.00
Received By btrobaug Date 2006-11-01 Time 12:03 Sent To PC
Notes
2006-11-01 14:10:35 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 CONDUCTOR IS UNDERSIZED PER 250.66.
 SHOULD BE #1/0 FOR 400 AMP SERVICE (400
 MCM).
  
 2} THE GRC MUST COMPLY WITH 250.50 REF
 250.52.( FOOTER STEEL).AS NOTED ON PERMIT SET.
  
 3} THE ARCHITECT OF RECORD MUST CORRECT, REVISE ,SIGN
 AND SEAL THE PLAN PER 481.221(1)(B)FS.
  
 4} A SMOKE DETECTOR IS REQUIRED BY THE
 STAIRWELL ON THE FIRST FLOOR TO COMPLY
 WITH 905.2.2 FBC.
  
 5} RECEPTACLES ARE REQUIRED TO BE ADDED
 IN THE MASTER SUITE #2 AND BEDROOM #3 TO
 COMPLY WITH 210.52(A)(2)(1). 2'OR MORE
  
 6} THE RECEPTACLE ON THE ISLAND (ALL) MUST BE GFI. SEE
 210.8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-17 Cont ID  
Sent By dpalmer Date 2004-09-17 Time 15:26 Rev Time 0.50
Received By dpalmer Date 2004-09-17 Time 14:31 Sent To P
Notes
2004-09-17 00:00:00** NOTES REDLINED/REVISE BEFORE ROUGH**
  
 1)NOTE: PLEASE SEE PANELS ARE SHOWN AS
 MLO AND MCB ON RISER.
  
 2)NOTE: NO ARC FAULT PROTECTION PER
 2002 NEC 210.12
  
 3 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 4)NOTE: PLEASE SEE LIGHT REQUIRED AT
 FRONT ENTRANCE/PORCH. LS 101 5-8,
 210.70 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:54 Rev Time 0.75
Received By btrobaug Date 2004-06-15 Time 11:53 Sent To M
Notes
2004-06-15 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 CONDUCTOR IS UNDERSIZED PER 250.66.
 SHOULD BE #1/0 FOR 400 AMP SERVICE (400
 MCM).
  
 2} THE GRC MUST COMPLY WITH 250.50 REF
 250.52.( FOOTER STEEL).
  
 3} APPLIANCE CIRCUIT #15 INCORRECTLY
 LISTS A 3 KVA LOAD ON A SINGLE POLE 20
 AMP BREAKER & THE #12 WIRE.
  
 4} A SMOKE DETECTOR IS REQUIRED BY THE
 STAIRWELL ON THE FIRST FLOOR TO COMPLY
 WITH 905.2.2 FBC.
  
 5} RECEPTACLES ARE REQUIRED TO BE ADDED
 IN THE MASTER SUITE #2 AND BEDROOM #3 TO
 COMPLY WITH 210.52(A)(2)(1). 2'OR MORE
  
 6} THE ARCHITECTS TITLE BLOCK MUST
 CONTAIN ALL THE INFORMATION REQUIRED BY
 FAC. 61G1-16.004. SEE (2), FIRM LICENSE
 NUMBER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 10:08 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 10:08 Sent To E
Notes
2006-10-27 10:08:40TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-04 Cont ID  
Sent By adarroug Date 2006-10-04 Time 13:48 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 13:48 Sent To M
Notes
2006-10-04 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 10:26 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 10:26 Sent To M
Notes
2005-10-14 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-19 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-10-19 Time 16:29 Sent To B
Notes
2004-10-19 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:32 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 12:32 Sent To B
Notes
2004-10-04 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:54 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 10:54 Sent To E
Notes
2004-08-30 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-30 Cont ID  
Sent By mmclean Date 2004-06-14 Time 12:49 Rev Time 0.00
Received By alange Date 2004-06-11 Time 15:54 Sent To  
Notes
2004-06-14 00:00:00TO SFD RACK/E
2004-06-11 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-09-20 Cont ID  
Sent By pkrauss Date 2004-09-20 Time 07:47 Rev Time 0.30
Received By pkrauss Date 2004-09-20 Time 07:32 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By jleech Date 2004-09-18 Time 12:58 Rev Time 0.40
Received By pkrauss Date 2004-06-24 Time 12:05 Sent To P
Notes
2004-06-24 00:00:00DENIED:
 1. MASTER BEDROOM 1ST FLOOR; RETURN AIR
 SHALL BE A MINIMUM OF 16" PER THE
 REVISED 2001 FBC(M) 601.4 EXCEPTION #1
 AND 3.
  
 2. MASTER SUITE #2 2ND FLOOR; RETURN
 AIR SHALL BE A MINIMUM OF 14".
  
 3.RETURN AIR JUMPER FROM THE LIBRARY
 SHALL BE A MINIMUM OF 12".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.
  
 4. PLAN DOES NOT INDICATE RETURN AIR
 BACK TO THE AIR HANDLING UNITS.A/C 1
 SHALL BE DUCTED INTO THE AHU.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-09-18 Cont ID  
Sent By jleech Date 2004-09-18 Time 12:58 Rev Time 0.50
Received By jleech Date 2004-09-18 Time 12:58 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-28 Cont ID  
Sent By dpalmer Date 2004-09-17 Time 15:26 Rev Time 0.75
Received By jleech Date 2004-06-28 Time 17:34 Sent To B
Notes
2004-06-28 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTE #6
 ARCHITECT TITAL BLOCK.
 2.PAGE P-2. MASTER BATH AND 1/2 BATH.
 HORIZONTAL DRY VENTS NOT PERMITED ( 3"
 MASTER BATH ).
 3.SHOWER AND TUB NOT VENTED AND ONE W/C.
 SEE TABLE 906.1 MAXIMUM DISTANCE OF
 TRAP TO VENT.
 4.W/M DISCHARGE IS 2" MIN. AND MIN. DIA.
 PIPE UNDER SLAB IS 2".
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-14 Cont ID  
Sent By mmclean Date 2004-06-14 Time 12:49 Rev Time 0.00
Received By mmclean Date 2004-06-14 Time 12:49 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved