Plan Review Details - Permit 04060528
Plan Review Stops For Permit 04060528
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-06-28 Cont ID  
Sent By kstevens Date 2004-07-26 Time 15:32 Rev Time 0.50
Received By lsmith Date 2004-06-28 Time 12:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By btrobaug Date 2004-07-12 Time 14:14 Rev Time 0.33
Received By btrobaug Date 2004-07-12 Time 14:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-07-09 Time 16:30 Rev Time 0.33
Received By btrobaug Date 2004-06-16 Time 14:22 Sent To P
Notes
2004-06-16 00:00:00 
 PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-07-09 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 16:30 Sent To E
Notes
2004-07-09 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 15:52 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 15:52 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-11 Cont ID  
Sent By mmclean Date 2004-06-14 Time 11:43 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 15:11 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-26 Cont ID  
Sent By kstevens Date 2004-07-26 Time 15:32 Rev Time 0.75
Received By kstevens Date 2004-07-26 Time 15:31 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-28 Cont ID  
Sent By btrobaug Date 2004-07-12 Time 14:14 Rev Time 1.50
Received By kstevens Date 2004-06-28 Time 09:56 Sent To B
Notes
2004-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 3) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL) - SUBMITTAL
 SHALL BE OF SUFFICIENT CLARITY TO BE
 ABLE TO READ ALL INFORMATION. SUBMITTAL
 SHEET HAS MANY DARK AREAS THAT MAKE THE
 SHEET UNREADABLE IN SOME AREAS. SECTION
 104.2.1.
 4) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 5) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 6) SUBMIT INFORMATION FOR LENGTH OF VENT
 PIPE ON THE ENTRAPMENT AVOIDANCE DETAIL
 REQUIRED BY SECTION 424.2.6.6.3(2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-14 Cont ID  
Sent By csiegber Date 2004-06-11 Time 15:11 Rev Time 0.00
Received By mmclean Date 2004-06-14 Time 11:43 Sent To I
Notes
***NONE***