Plan Review Details - Permit 04060490
Plan Review Stops For Permit 04060490
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-08-06 Cont ID  
Sent By btrobaug Date 2004-08-06 Time 13:37 Rev Time 0.50
Received By lsmith Date 2004-08-06 Time 13:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-06 Cont ID  
Sent By btrobaug Date 2004-08-06 Time 13:37 Rev Time 0.33
Received By btrobaug Date 2004-08-06 Time 13:26 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-06-16 Cont ID  
Sent By kstevens Date 2004-08-05 Time 17:28 Rev Time 0.33
Received By btrobaug Date 2004-06-16 Time 17:50 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 14:24 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 14:24 Sent To P
Notes
2004-07-22 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 15:54 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 15:54 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-11 Cont ID  
Sent By mmclean Date 2004-06-14 Time 10:23 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 10:15 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-08-05 Cont ID  
Sent By kstevens Date 2004-08-05 Time 17:28 Rev Time 0.50
Received By kstevens Date 2004-08-05 Time 17:28 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-07-22 Time 14:24 Rev Time 1.25
Received By kstevens Date 2004-06-28 Time 10:40 Sent To B
Notes
2004-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES) - INFORMATION SHALL BE INCORPOR-
 ATED INTO SIGNED/SEALED PLANS, OR IF
 SUBMITTED ON SEPARATE 8-1/2 X 11 SHEET
 SHEET SHALL BE SIGNED/SEALED/DATED AND
 PROPER TITLE BLOCK WITH ALL REQUIRED IN-
 FORMATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-14 Cont ID  
Sent By csiegber Date 2004-06-11 Time 10:15 Rev Time 0.00
Received By mmclean Date 2004-06-14 Time 10:23 Sent To I
Notes
***NONE***