Plan Review Details - Permit 04060487
Plan Review Stops For Permit 04060487
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-06-22 Cont ID  
Sent By alange Date 2004-06-22 Time 15:06 Rev Time 0.66
Received By alange Date 2004-06-22 Time 15:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-06 Cont ID  
Sent By dpalmer Date 2004-07-06 Time 08:29 Rev Time 0.33
Received By dpalmer Date 2004-07-06 Time 08:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By dpalmer Date 2004-06-15 Time 08:43 Rev Time 0.33
Received By dpalmer Date 2004-06-15 Time 08:43 Sent To  
Notes
2004-06-15 00:00:00************* UNSAT ******************
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE. PLEASE SHOW NEW AND
 OR EXSITNG TIE-INS FOR CIRCUITS.
 215.5
  
 2)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 3)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK. THIS IS TO INCLUDE THE
 REQUIRED CERTIFICATE OF AUTHORIZATION
 PER FS 481.219.
 FAC 61G1-16.004
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE FROM OTHER REVIEW
 -ERS.
  
 4)NOTE: PLEASE SEE 2002 NEC FOR ARC
 FAULT PROTECTION FOR NEW CIRCUITING TO
 BEDRMS. 210.12
  
 PLEASE SEE COMMENT S FROM OTHER REVIEWER
 -S WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-06-11 Cont ID  
Sent By mcarsill Date 2004-06-11 Time 13:22 Rev Time 0.00
Received By mcarsill Date 2004-06-11 Time 13:20 Sent To  
Notes
2004-06-11 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3) ALL EXITS SHALL REMAIN CLEAR AND
 ACCESSIBLE.
  
 4) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL IF IT EXCEEDS
 FIVE OR MORE SPRINKLER HEADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 11:02 Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 11:02 Sent To  
Notes
2004-06-28 00:00:00TO COMM BD#22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-22 Cont ID  
Sent By alange Date 2004-06-22 Time 15:06 Rev Time 0.00
Received By alange Date 2004-06-11 Time 10:53 Sent To  
Notes
2004-06-11 00:00:00TO COMM BD#27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-06 Cont ID  
Sent By pkrauss Date 2004-07-06 Time 15:36 Rev Time 0.30
Received By pkrauss Date 2004-07-06 Time 15:36 Sent To  
Notes
2004-07-06 00:00:00PROVISO:
 PLANS DO NOT INDICATE RETURN AIR.PER
 2001 FBC(M) 601.4, ROOMS THAT ARE
 SEPARATED BY DOORS FROM THE RETURN AIR,
 SHALL HAVE A RETURN AIR JUMPER, TRANSFER
 OR DUCTED RETURN FROM THAT SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-18 Cont ID  
Sent By pkrauss Date 2004-06-18 Time 10:49 Rev Time 0.25
Received By pkrauss Date 2004-06-18 Time 10:31 Sent To  
Notes
2004-06-18 00:00:00DENIED:
 CERTIFICATE OF AUTHORIZATION # REQUIRED
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.