| Plan Review Stops For Permit 04060478 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-11 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-11 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-11 |
Time |
11:06 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-06-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-11 |
Time |
11:06 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2004-06-14 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2004-06-14 00:00:00 | PROVISO: | | | PLAN INDICATES EMERGENCY DRAIN LOCATED | | | OUTSIDE TO THE OPEN PORCH.PER 2001 | | | FBC(M) 307.2.3, EMERGENCY DRAIN SHALL | | | TERMINATE AT A CONSPICUOUS POINT TO | | | SERVE AS AN ALARM THAT THE PRIMARY DRAIN | | | IS RESTRICTED OR HAVE A FLOAT SWITCH. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|