Plan Review Details - Permit 04060444
Plan Review Stops For Permit 04060444
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-17 Cont ID  
Sent By pkrauss Date 2004-08-25 Time 10:57 Rev Time 2.22
Received By jwitmer Date 2004-08-17 Time 16:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-15 Cont ID  
Sent By jwitmer Date 2004-07-15 Time 11:29 Rev Time 3.33
Received By jwitmer Date 2004-07-15 Time 09:00 Sent To PC
Notes
2004-07-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04060444
 ADD: 534 DATURA ST
 CONT: TAYCON CONSTRUCTION
 TEL: (561)622-2699
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) "FIRE DISTRICT" 609.2.1 NO TYPE VI
 CONSTRUCTION ON EXTERIOR WALLS. INFILL
 WALLS AT OLD DOORWAYS.
  
 3) LEASE SPACE, E-1 DOES NOT PROVIDE
 EXIT LIGHTING FOR LEASE SPACE NOR FOR
 BAY# 2.
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 A) MISSING THE PRODUCT TESTING REPORTS
 FOR SIMPSON AND USP PRODUCTS.
 B) MISSING HOLLOW METAL DOOR
 C) SITE SPECIFIC ENGINEERING.
 1)) INFORMATION ON THE SITE SPECIFIC
 FORM 1-5 HAS TO DO WITH THE MANUFACTURER
 NOT THE JOBSITE.
 2)) #7 NAME OF APPROVED THIRD PARTY
 QUALITY ASSURANCE ENTITY NOT COMPLETE,
 IF THE DESIGNER OF RECORD TO BE THE
 QUALITY ASSURANCE ENTITY, TO GO TO THE
 MANUFACTURING PLANT VERIFY PRODUCTION.
 THEN INSPECT THE ASSEMBLIES AT INSTALA-
 TION. PRODUCE AN AFFIDAVIT.
 3)) THE SITE SPECIFIC ENGINEERING DOES
 NOT PROVIDE ANY INFORMATION AS TO THE
 STRENGTH OF GLAZING.
 4)) 3401.7.2.4. PROVIDE INFORMATION ON
 THE LARGE MISSLE IMPACT PROTECTION
 REQUIRED BY CHAPTER 1606.6.SEE GLAZING
 NOTE ON A-5.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 5)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 6) SHEET A-5 INDICATES THE USE OF A
 1-HR WALL, WITH A U. L. LISTING OF 401,
 THERE IS NO SUCH LISTING, THERE IS A
 U401,OR V401?
  
 7) SHEET A-5 SECTIONS 8 & 9 INDICATE
 WOOD INFILL BUT NO MENTION AS TO THE
 ATTACHMENT OT THE SUBSTRATA.
  
 8) SITE SPECIFIC ENGINEERING SUBMITTED
 SEE SHEET 12 (TABLE 1606.2B) IS TO BE
 USED WITH BUILDINGS WITH A ROOF HEIGTH
 OF 30' OR LESS, SEE TABLE 1606.2D FOR
 BUILDINGS OVER 30' WITH ASSOCIATED
 MULTIPLIER, BUILDINGS 55'= 1.19. RE-
 EVALUATE SUBMITTED CALCULATIONS!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-16 Cont ID  
Sent By dpalmer Date 2004-08-16 Time 12:01 Rev Time 0.33
Received By dpalmer Date 2004-08-13 Time 14:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-14 Cont ID  
Sent By dpalmer Date 2004-06-14 Time 16:27 Rev Time 1.00
Received By dpalmer Date 2004-06-14 Time 16:27 Sent To  
Notes
2004-06-14 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE SEE FS 481.219, FAC 61G1-
 16.004. PLEASE INCLUDE LICENSE #S'
 FOR COMPANY/FIRM. M"SBA".
  
 2)NOTE: PLEASE SEE PLANS ARE MISSING
 MIN REQUIRED FOR UNITS.
 PANEL SCHEDULES?
 CIRCUITING ON PLANS AND CORRELATE WITH
 SUBMITTED PANEL SCHEDULES TO BE SUBMITT-
 -ED.
  
 3)NOTE: PLEASE SEE 600.5 FOR MIN SIGN
 CIRCUIT(S).
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO
 METERBANK. 250.122
  
 5)NOTE: PLEASE PROVIDE INFORMATION FOR
 NEW SERVICE/METERBANK MAINS. FEEDS TO
 PANELS.215.5/250
 PLEASE PROVIDE LETTER FROM FPL PERMITT-
 -ING METERBANK TO BE ON THE LOAD SIDE
 OF NEW MAIN WITHOUT ANY CT OR FPL
 MEASURING DEVICE ON LINE-SIDE OF MAIN
 DISCONNECT.
  
 6)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR EXIT/EM LTS. PLEASE SEE 700.12E FOR
 CIRCUITING.
  
 7)NOTE: PLEASE SEE PERMIT APPLICATION,
 NEEDS TO CORRELATE WITH PLANS SUBMITTED
 FOR SCOPE OF WORK.
  
 8)NOTE: PLEASE SEE FBC 104.6.5 FOR
 VALUE TO INCLUDE ALL LABOR AND MATERIALS
 PLEASE SEE BLDG VALUATION.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD PLANS MAY BE SUBMITTED
 FOR REFERENCE ONLY. THIS MAY BE REQUIRED
 OF SOME REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-08-13 Cont ID  
Sent By mcarsill Date 2004-08-13 Time 14:06 Rev Time 0.00
Received By mcarsill Date 2004-08-13 Time 14:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-10 Cont ID  
Sent By mcarsill Date 2004-06-10 Time 15:56 Rev Time 0.00
Received By mcarsill Date 2004-06-10 Time 15:56 Sent To  
Notes
2004-06-10 00:00:001) PERMIT APPLICATION DOES NOT APPEAR
 TO REFLECT THE PROPOSED WORK SHOWN
 ON THE PLANS.
  
 2) THE BUILDING IS LOCATED WITHIN
 THE CITY FIRE LIMITS. CERTAIN
 RESTRICTIONS APPLY. PLEASE SEE
 APPENDIX F, LOCAL AMENDMENTS TO
 THE FLORIDA BUILDING CODE. PLEASE
 SEE APPENDIX F, SECTION 102.2.8.
  
 3) PLEASE PROVIDE UL NUMBERS FOR NEW
 ONE HOUR WALL SECTIONS.
  
 4) PLEASE ILLUSTRATE EXIT SIGNS AND
 EMERGENCY LIGHTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-09 Cont ID  
Sent By csiegber Date 2004-08-09 Time 14:14 Rev Time 0.00
Received By csiegber Date 2004-08-09 Time 14:14 Sent To  
Notes
2004-08-09 00:00:00TO COMM BD#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-15 Cont ID  
Sent By jwitmer Date 2004-07-15 Time 13:42 Rev Time 3.33
Received By jwitmer Date 2004-06-10 Time 13:34 Sent To PC
Notes
2004-06-10 00:00:00COMM BD#20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-08-25 Cont ID  
Sent By pkrauss Date 2004-08-24 Time 09:26 Rev Time 0.40
Received By pkrauss Date 2004-08-24 Time 08:56 Sent To B
Notes
2004-08-24 00:00:00MECHANICAL PLANS AND APPLICATION TO
 BE APPLIED FOR SEPARATELY.NO NEW
 MECHANICAL WORK INDICATED ON THE PLANS
 DEMO ONLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-29 Cont ID  
Sent By pkrauss Date 2004-06-29 Time 15:01 Rev Time 0.40
Received By pkrauss Date 2004-06-29 Time 14:49 Sent To  
Notes
2004-06-29 00:00:00DENIED:
 1.PLEASE INDICATE SCOPE OF WORK.
  
 2.WILL THIS BE A CHANGE IN OCCUPANCY?
  
 3.IDENTIFY NEW AND EXISTING EQUIPMENT.
 PROVIDE EQUIPMENT SCHEDULE FOR NEW
 EQUIPMENT.
  
 4.PROVIDE OUTSIDE AIR CALUCALTIONS PER
 2001 FBC(M) 403.3.
  
 5.INDICATE ALL NEW OR EXISTING FIRE
 DAMPERS PER 2001 FBC(M) 607.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-08-25 Cont ID  
Sent By kstevens Date 2004-08-25 Time 10:04 Rev Time 0.50
Received By kstevens Date 2004-08-25 Time 10:04 Sent To  
Notes
2004-08-25 00:00:00 
  
  
  
  
 NO PLUMBING WORK THIS PERMIT - SEPARATE
 PLANS/PERMIT REQUIRED FOR COMMERCIAL
 REMODEL.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-06-23 Cont ID  
Sent By pkrauss Date 2004-08-24 Time 16:31 Rev Time 0.25
Received By kstevens Date 2004-06-23 Time 07:45 Sent To  
Notes
2004-06-23 00:00:00NO PLUMBING PLANS SUBMITTED - NO PLUMB-
 ING WORK SHOWN.