| 2004-07-15 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04060444 |
| | ADD: 534 DATURA ST |
| | CONT: TAYCON CONSTRUCTION |
| | TEL: (561)622-2699 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) "FIRE DISTRICT" 609.2.1 NO TYPE VI |
| | CONSTRUCTION ON EXTERIOR WALLS. INFILL |
| | WALLS AT OLD DOORWAYS. |
| | |
| | 3) LEASE SPACE, E-1 DOES NOT PROVIDE |
| | EXIT LIGHTING FOR LEASE SPACE NOR FOR |
| | BAY# 2. |
| | |
| | 4)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | A) MISSING THE PRODUCT TESTING REPORTS |
| | FOR SIMPSON AND USP PRODUCTS. |
| | B) MISSING HOLLOW METAL DOOR |
| | C) SITE SPECIFIC ENGINEERING. |
| | 1)) INFORMATION ON THE SITE SPECIFIC |
| | FORM 1-5 HAS TO DO WITH THE MANUFACTURER |
| | NOT THE JOBSITE. |
| | 2)) #7 NAME OF APPROVED THIRD PARTY |
| | QUALITY ASSURANCE ENTITY NOT COMPLETE, |
| | IF THE DESIGNER OF RECORD TO BE THE |
| | QUALITY ASSURANCE ENTITY, TO GO TO THE |
| | MANUFACTURING PLANT VERIFY PRODUCTION. |
| | THEN INSPECT THE ASSEMBLIES AT INSTALA- |
| | TION. PRODUCE AN AFFIDAVIT. |
| | 3)) THE SITE SPECIFIC ENGINEERING DOES |
| | NOT PROVIDE ANY INFORMATION AS TO THE |
| | STRENGTH OF GLAZING. |
| | 4)) 3401.7.2.4. PROVIDE INFORMATION ON |
| | THE LARGE MISSLE IMPACT PROTECTION |
| | REQUIRED BY CHAPTER 1606.6.SEE GLAZING |
| | NOTE ON A-5. |
| | 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE SPECIFIC |
| | AND THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE |
| | TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". |
| | |
| | 5)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 6) SHEET A-5 INDICATES THE USE OF A |
| | 1-HR WALL, WITH A U. L. LISTING OF 401, |
| | THERE IS NO SUCH LISTING, THERE IS A |
| | U401,OR V401? |
| | |
| | 7) SHEET A-5 SECTIONS 8 & 9 INDICATE |
| | WOOD INFILL BUT NO MENTION AS TO THE |
| | ATTACHMENT OT THE SUBSTRATA. |
| | |
| | 8) SITE SPECIFIC ENGINEERING SUBMITTED |
| | SEE SHEET 12 (TABLE 1606.2B) IS TO BE |
| | USED WITH BUILDINGS WITH A ROOF HEIGTH |
| | OF 30' OR LESS, SEE TABLE 1606.2D FOR |
| | BUILDINGS OVER 30' WITH ASSOCIATED |
| | MULTIPLIER, BUILDINGS 55'= 1.19. RE- |
| | EVALUATE SUBMITTED CALCULATIONS! |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |