Plan Review Details - Permit 04060406
| Plan Review Stops For Permit 04060406 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-06-25 |
Time |
15:50 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2004-06-25 |
Time |
15:27 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2004-06-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-16 |
Time |
07:34 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-06-15 |
Time |
20:48 |
Sent To |
|
|
| Notes |
| 2004-06-16 00:00:00 | REDLINED TRANSFORMER GRNDING PER 250.30 | | | | | | EQUIP GROUNDING METHOD? FROM METER TO | | | MAIN. 250.24 THIS IS ALREADY AFTER THE | | | FIRST MEANS OF DICONNECT. APPEARS TO | | | SHOW GRC> FEILD VERIFY. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2004-06-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-06-10 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-06-10 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2004-06-10 00:00:00 | 1) ALL DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) SEPARATE PLANS AND PERMITS FOR | | | FIRE ALARM SYSTEM REMODEL. | | | | | | 3) SEPARATE PLANS AND PERMITS FOR FIRE | | | SPRINKLER REMODEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-06-25 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2004-06-09 |
Time |
15:52 |
Sent To |
PC |
|
| Notes |
| 2004-06-09 00:00:00 | TO COMM BD#62 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-06-22 |
Time |
16:45 |
Rev Time |
1.10 |
| Received By |
pkrauss |
Date |
2004-06-22 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-22 |
Time |
18:18 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-06-22 |
Time |
18:18 |
Sent To |
|
|
| Notes |
| 2004-06-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A0.1 ACCESSIBLE DETIAL FOR SINK | | | SHALL SHOW KNEE CLEARANCE 11-4.24.3, | | | DEPTH OF SINK 11-4.24.4, EXPOSED PIPES & | | | SURFACES 11-4.24.6. | | | 2) SHT A0.2 ALL CAPPED AND DEMO'D PLUMB- | | | ING PIPES SHALL BE INSPECTED PRIOR TO | | | COVERING. SECTION 104.2.1 | | | 3) SHT A1.0 SHOW CLEAR FLOOR SPACE FOR | | | SINK IN ROOM 521. 11-4.24.5. | | | 4) SHT A1.0 SHOW CLEAR FLOOR SPACE FOR | | | ACCESSIBLE DRINKING FOUNTAIN. 11-4.15.5 | | | 5) SHT A1.1 SHOW CLEAR FLOOR SPACE FOR | | | SINK IN ROOM 643. 11-4.24.5 | | | 6) SHT A1.1 SHOW CLEAR FLOOR SPACE FOR | | | ACCESSIBLE DRINKING FOUNTAIN. 11-4.15.5 | | | 7) SHT A2.0 BREAK ROOM/STORAGE ELEVATION | | | MAXIMUM 34" TO SINK. 11-4.24.2 | | | 8) SHT P.2 5TH & 6TH FLOOR WATER RISER | | | DIAGRAMS ARE MISLABELED AS SANITARY | | | RISERS. - WATER HAMMER ARRESTORS SHALL | | | BE LOCATED NEAR THE FIXTURES, NOT IN THE | | | CEILING AS SHOWN. PDI-WH 201 AND MANUF. | | | INSTALLATION INSTRUCTIONS. SECTION 604.9 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
|