Plan Review Details - Permit 04060406
Plan Review Stops For Permit 04060406
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 15:50 Rev Time 2.22
Received By jwitmer Date 2004-06-25 Time 15:27 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-06-16 Cont ID  
Sent By dpalmer Date 2004-06-16 Time 07:34 Rev Time 0.75
Received By dpalmer Date 2004-06-15 Time 20:48 Sent To  
Notes
2004-06-16 00:00:00REDLINED TRANSFORMER GRNDING PER 250.30
  
 EQUIP GROUNDING METHOD? FROM METER TO
 MAIN. 250.24 THIS IS ALREADY AFTER THE
 FIRST MEANS OF DICONNECT. APPEARS TO
 SHOW GRC> FEILD VERIFY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-06-10 Cont ID  
Sent By mcarsill Date 2004-06-10 Time 15:53 Rev Time 0.00
Received By mcarsill Date 2004-06-10 Time 15:53 Sent To  
Notes
2004-06-10 00:00:001) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) SEPARATE PLANS AND PERMITS FOR
 FIRE ALARM SYSTEM REMODEL.
  
 3) SEPARATE PLANS AND PERMITS FOR FIRE
 SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 15:50 Rev Time 0.00
Received By jwitmer Date 2004-06-09 Time 15:52 Sent To PC
Notes
2004-06-09 00:00:00TO COMM BD#62

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-22 Cont ID  
Sent By pkrauss Date 2004-06-22 Time 16:45 Rev Time 1.10
Received By pkrauss Date 2004-06-22 Time 16:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-22 Cont ID  
Sent By kstevens Date 2004-06-22 Time 18:18 Rev Time 1.00
Received By kstevens Date 2004-06-22 Time 18:18 Sent To  
Notes
2004-06-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A0.1 ACCESSIBLE DETIAL FOR SINK
 SHALL SHOW KNEE CLEARANCE 11-4.24.3,
 DEPTH OF SINK 11-4.24.4, EXPOSED PIPES &
 SURFACES 11-4.24.6.
 2) SHT A0.2 ALL CAPPED AND DEMO'D PLUMB-
 ING PIPES SHALL BE INSPECTED PRIOR TO
 COVERING. SECTION 104.2.1
 3) SHT A1.0 SHOW CLEAR FLOOR SPACE FOR
 SINK IN ROOM 521. 11-4.24.5.
 4) SHT A1.0 SHOW CLEAR FLOOR SPACE FOR
 ACCESSIBLE DRINKING FOUNTAIN. 11-4.15.5
 5) SHT A1.1 SHOW CLEAR FLOOR SPACE FOR
 SINK IN ROOM 643. 11-4.24.5
 6) SHT A1.1 SHOW CLEAR FLOOR SPACE FOR
 ACCESSIBLE DRINKING FOUNTAIN. 11-4.15.5
 7) SHT A2.0 BREAK ROOM/STORAGE ELEVATION
 MAXIMUM 34" TO SINK. 11-4.24.2
 8) SHT P.2 5TH & 6TH FLOOR WATER RISER
 DIAGRAMS ARE MISLABELED AS SANITARY
 RISERS. - WATER HAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURES, NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. SECTION 604.9
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]