Plan Review Details - Permit 04060393
Plan Review Stops For Permit 04060393
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-08-25 Cont ID  
Sent By jwitmer Date 2004-08-25 Time 09:56 Rev Time 0.75
Received By jwitmer Date 2004-08-25 Time 09:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-08-02 Cont ID  
Sent By jwitmer Date 2004-08-02 Time 16:32 Rev Time 0.55
Received By jwitmer Date 2004-08-02 Time 16:31 Sent To  
Notes
2004-08-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04060393
 ADD: 1801 S FLAGLER DR# 403
 CONT: ODUM CONSTRUCTION
 TEL: (561)272-9702
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION
 ACTION: DENIED
  
 1)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 2) PERMIT VALUE INCREASE, ADDITIONAL
 FEES DUE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-24 Cont ID  
Sent By jwitmer Date 2004-06-24 Time 09:07 Rev Time 0.55
Received By jwitmer Date 2004-06-24 Time 09:07 Sent To PC
Notes
2004-06-24 00:00:00REVISION COFFER CEILING DINING ROOM OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-06-11 Cont ID  
Sent By dpalmer Date 2004-06-21 Time 10:20 Rev Time 0.33
Received By jwitmer Date 2004-06-11 Time 13:22 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2004-08-23 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 11:25 Rev Time 0.25
Received By dpalmer Date 2004-08-23 Time 11:24 Sent To  
Notes
2004-08-23 00:00:00EXTEND ELEC BOX ONLY.
 NEW ELEC FOR UNDER CABINET LTS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-08-02 Cont ID  
Sent By dpalmer Date 2004-08-02 Time 14:08 Rev Time 0.00
Received By dpalmer Date 2004-08-02 Time 14:10 Sent To  
Notes
2004-08-02 00:00:00***UNSAT **
  
 1)NOTE: PLEASE SEE NEW ELECTRIC NOW
 BEING SHOWN.
 ORIG REVIEW, EXTEND J-BOX ONLY.
  
 2)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 REQUIRED TO HAVE PRINTED NAME AND
 SIGNATURE OF PERSON RESPONSIBLE FOR
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2004-07-01 Cont ID  
Sent By dpalmer Date 2004-07-01 Time 11:14 Rev Time 0.26
Received By dpalmer Date 2004-07-01 Time 11:13 Sent To  
Notes
2004-07-01 00:00:00EXTEND ELEC BOX DOWN ONLY FOR NEW COFFER
 CEILING. NO NEW ELECTRIC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-21 Cont ID  
Sent By dpalmer Date 2004-06-21 Time 10:19 Rev Time 0.33
Received By dpalmer Date 2004-06-21 Time 10:19 Sent To B
Notes
2004-06-21 00:00:00************** UNSAT ************
  
 1)NOTE: PLANS ORIG CAME IN SHOW NEW
 ELECTRICAL FOR FOYER ONLY .
 PLANS ARE NOT BEING SUBMITTED NOTED
 AS ADDING COFFER CELING, YET PLANS ARE
 NOW SHOWING A COMPLERE REWIRE OF UNIT?
 PLEASE CLARIFY.
 IF ALL SHOWN IS NEW, PLEASE THEN SUBMIT
 COMPLETE PLAN FOR 2002 NEC CODE COMPL-
 -IANCE, FBC, NFPA-72 8-1
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-06-17 Time 07:34 Rev Time 0.25
Received By dpalmer Date 2004-06-10 Time 14:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-13 Cont ID  
Sent By nmccray Date 2004-09-13 Time 16:12 Rev Time 0.00
Received By nmccray Date 2004-09-13 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-19 Time 14:19 Rev Time 0.00
Received By csiegber Date 2004-08-19 Time 14:19 Sent To  
Notes
2004-08-19 00:00:00TO COMM BD#3

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-07-29 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-07-29 Time 16:30 Sent To  
Notes
2004-07-29 00:00:00TO COMM BD#19

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 09:04 Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 09:04 Sent To  
Notes
2004-06-28 00:00:00TO COMM BD#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-06-15 Time 16:54 Rev Time 0.00
Received By csiegber Date 2004-06-15 Time 16:54 Sent To E
Notes
2004-06-17 00:00:00TO DP DESK/REV(COMM)
2004-06-15 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-11 Cont ID  
Sent By jwitmer Date 2004-06-11 Time 13:24 Rev Time 0.00
Received By jwitmer Date 2004-06-09 Time 12:58 Sent To PC
Notes
2004-06-09 00:00:00TO COMM BD#5

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-18 Cont ID  
Sent By kstevens Date 2004-08-18 Time 15:41 Rev Time 0.50
Received By kstevens Date 2004-08-18 Time 15:41 Sent To  
Notes
2004-08-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) A 2" TRAP IS REQUIRED FOR THE SHOWER.
 TABLE 709.1. IF A 2" TRAP IS NOT AVAIL-
 ABLE AT THE TUB, AN ENGINEER SHALL SUB-
 MIT A SIGNED/SEALED/DATED LETTER INDI-
 CATING THAT THE 1-1/2" TRAP IS SUFFICI-
 ENT TO EXCEPT THE FLOW FROM THE SHOWER
 HEAD. ALL INFORMATION FOR THE TITLE
 BLOCK REQUIRED BY FAC 61G15-23.002 AND
 FS 471.025 IS REQUIRED ON LETTER.
  
 2) ALL INFORMATION AND DRAWINGS SHALL
 BEAR THE NAME AND SIGNATURE OF THE PER-
 SON RESPONSIBLE FOR THE DESIGN. SECTION
 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]