Plan Review Details - Permit 04060361
Plan Review Stops For Permit 04060361
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-01-28 Cont ID  
Sent By shill Date 2005-01-28 Time 12:17 Rev Time 0.50
Received By shill Date 2005-01-28 Time 12:17 Sent To  
Notes
2005-01-28 00:00:00REVISION A2, A8 DATED 12/9/04, PRODUCT
 APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-01-11 Cont ID  
Sent By shill Date 2005-01-11 Time 10:43 Rev Time 2.00
Received By shill Date 2005-01-11 Time 10:13 Sent To  
Notes
2005-01-11 00:00:00PROVISO - SUBMIT STEEL DOOR PRODUCT
 APPROVAL AS REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-01-11 Cont ID  
Sent By shill Date 2005-01-11 Time 10:12 Rev Time 2.00
Received By shill Date 2005-01-11 Time 10:11 Sent To PC
Notes
2005-01-11 00:00:00TRUSS ENGINEERING (CALLED MITEK/TRUSS
 CO
 RE:CALCS), OKAY

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-01-10 Cont ID  
Sent By shill Date 2005-01-10 Time 10:04 Rev Time 2.00
Received By shill Date 2005-01-10 Time 09:46 Sent To PC
Notes
2005-01-10 00:00:00****CORRECTIONS****
 TRUSS ENGINEERING
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROPERLY IDENTIFY THE PROJECT AS
 REQUIRED BY FAC61G15-31.-003(5)(C) (THE
 INDEX SHEET IS LACKING AN ADDRESS OR
 LOT/BLOCK).
  
 2.)THE TRUSS SYSTEM IS TO BE SEALED
 WITH A TITLE BLOCK, SEE FAC61G15-31.003
 (3)(A) AND (4).

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-12-20 Cont ID  
Sent By shill Date 2004-12-20 Time 11:37 Rev Time 1.00
Received By shill Date 2004-12-20 Time 11:37 Sent To PC
Notes
2004-12-20 00:00:00****CORRECTIONS****
 TRUSS SUBMITTALS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DELEGATED ENGINEERING TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FAC61G15-30.005.
  
 2.)ORIGINAL SIGNATURE REQUIRED FOR THE
 SEAL.
  
 3.)TRUSS LAYOUT TO BE DESIGNED BY
 ENGINEER, PLEASE INCLUDE TITLE BLOCK,
 SIGN AND SEAL.HAVE TRUSS LAYOUT ALSO
 REVIEWED BY DESIGNER OF RECORD.
  
 4.)TRUSS ENGINEERING TO BE SIGNED AND
 SEALED, EACH SHEET.FAC61G15-31.003(5)
 IS FOR WOOD TRUSS SYSTEMS.THIS IS A
 STEEL TRUSS SYSTEM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-12-20 Cont ID  
Sent By shill Date 2004-12-20 Time 09:23 Rev Time 1.00
Received By shill Date 2004-12-20 Time 09:23 Sent To PC
Notes
2004-12-20 00:00:00REVISION - STOREFRONT SYSTEM, GLASS
 DOORS, SGD - IMPACT, NONIMPACT DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-12-10 Cont ID  
Sent By shill Date 2004-12-10 Time 08:21 Rev Time 1.00
Received By shill Date 2004-12-10 Time 08:21 Sent To PC
Notes
2004-12-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ONE OF THE PRODUCT APPROVALS
 SUBMITTED WAS NOT A PART OF THE APPROVED
 PERMIT PACKAGE (ARCHITECTURAL TRADITIONS
 DOOR).PROVIDE DESIGN PRESSURES.
  
 2.)IMPACT PROTECTION REQUIRED,
 FBC1606.1.4.
  
 3.)PLEASE NOTE THAT THE FIXED WINDOWS
 ARE SMALL MISSILE IMPACT ONLY.THESE
 WINDOWS WILL ALSO REQUIRE SHUTTERS,
 FBC1606.1.4.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-10 Cont ID  
Sent By shill Date 2004-12-10 Time 07:35 Rev Time 1.00
Received By shill Date 2004-12-10 Time 07:35 Sent To PC
Notes
2004-12-10 00:00:00STAMPED CONTRACTOR COPY OF PRODUCT
 APPROVALS PREVIOUSLY REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-22 Cont ID  
Sent By csiegber Date 2004-10-26 Time 12:13 Rev Time 3.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-16 Cont ID  
Sent By shill Date 2004-07-15 Time 10:17 Rev Time 0.00
Received By shill Date 2004-07-15 Time 10:13 Sent To  
Notes
2004-07-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THE PRINTED NAME OF THE PERSON
 SEALING THE PLAN IS REQUIRED TO BE ON
 EACH SHEET, FAC61G15-23.002 (SHEET C1).
 THE CA NUMBER FOR SMITH & MOORE IS TO
 BE ON THE TITLE BLOCK FAC61G1-16.003,004
 THE CA NUMBER FOR METRO DESIGN GROUP
 IS TO BE ON THE TITLE BLOCK.
  
 3.)A CONSTRUCTION TYPE OF IV IS
 DECLARED ON A1, BUILDING INFORMATION,
 BUT SHEET A9 SHOWS WOOD TRUSSES.SHEET
 A4 SHOWS METAL TRUSSES.
  
 4.)THE SCOPE OF WORK IS NOT ENTIRELY
 CLEAR.THE PERMIT APPLICATION STATES
 ONLY "REMODEL RESTAURANT".REVISE THE
 PERMIT TO INCLUDE THE DUMPSTER, ROOF AND
 PAVING.THE SITE PLAN DATA (C1) SHOW AN
 INCREASE IN THE BUILDING SIZE, BUT IT
 IS NOT CLEAR WHERE THIS ADDITION IS.
  
 5.)THE PRIVATE TOILET IS TO BE
 ADAPTABLE; THE STAFF TOILET IS TO BE
 ACCESSIBLE FBC11-4.1.3(11).
  
 6.)PROVIDE PRODUCT APPROVALS FOR:
 ROOF
 OVERHEAD DOORS (OUTDOOR DINING)
 DRIVE-THRU WINDOWS
 WINDOWS W1, S2, W3 (SHEET A8)
 DOORS D01,D02,D22 (SHEET A8)
  
 FLORIDA STATE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVALS REQUIRED IN ADDITION
 TO THE TEST REPORT.
 WWW.FLORIDABUILDING.ORG
  
 ANY PRODUCT APPROVALS NOT PROPERLY
 SUBMITTED BEFORE PERMIT ISSUANCE WILL
 REQUIRE SEPARATE PERMITS FOR THOSE
 ITEMS.
  
 7.)PORCH RAILING IS TO COMPLY WITH
 FBC1608.2.2.NOTE DESIGN CRITERIA ON
 THE PLAN.
  
 8.)THE GRAB BARS SHEET A7 APPEAR TO
 BE MISMARKED ON THE ELEVATIONS AND THE
 FLOOR PLAN (SHOULD BE E).
  
 9.)IT IS NOT CLEAR AS TO WHERE THE
 NEW ROOF AREA IS.SHEET A4 SHOWS THE
 ENTIRE BUILDING (NO NOTES AS TO PROPOSED
 OR EXISTING), SHEET A9 SHOWS TRUSS
 DETAILS.
  
 10.) STRUCTURAL NOTES, A9, WIND LOAD,
 CITY OF WEST PALM BEACH IS NOT IN THE
 HIGH-VELOCITY ZONE.ALSO, INTERNAL
 PRESSURE COEFFICIENT IS NOTED AS -1.45,
 PLEASE CLARIFY.
  
 11.)PROVIDE A CURB RAMP DETAIL.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 15:05 Rev Time 0.30
Received By dpalmer Date 2005-01-24 Time 15:05 Sent To  
Notes
2005-01-24 00:00:00ONLY REVISED MEP-8.
 SHEET MEP-6 VOIDED AS NEW MEP-6 SHEET
 WAS SUBMITTED PER PREVIOUS COMMENTS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-12-27 Cont ID  
Sent By dpalmer Date 2004-12-27 Time 08:57 Rev Time 0.33
Received By dpalmer Date 2004-12-27 Time 08:57 Sent To  
Notes
2004-12-27 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS STILL SHOWN FROM
 METER TO MAIN (FIRST MEANS OF DISC).
 PLEASE SEE 250.6,250.24. NO EQUIPMENT
 GRND UNTIL AFTER THE FIRST MEANS OF
 DISC.
  
 2)NOTE: PLEASE SEE MEP PLANS HAVE TWO
 DIFFERENT SIGNATURES FOR THE SAME PE.
 PLEASE HAVE ENGINEER SIGN WITH LEGAL
 SIGNATURE AS ON FILE.
 FS 471.025
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-22 Cont ID  
Sent By dpalmer Date 2004-10-22 Time 13:15 Rev Time 0.33
Received By dpalmer Date 2004-10-22 Time 13:12 Sent To  
Notes
2004-10-22 00:00:00REDLINED: NO EQUIPMENT GROUNDING COND-
 -UCTOR FROM METER TO MAIN(FIRST MEANS OF
 DISC) PER 250.24,250.6.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-16 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 19:10 Rev Time 0.50
Received By dpalmer Date 2004-09-16 Time 18:55 Sent To  
Notes
2004-09-16 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE COMMENT FROM FIRE
 PLAN REVIEW WHICH WILL AFFECT ELECTRICAL
 PLANS.
  
 2)NOTE: PLEASE SEE RISER, SHOWSEQUIP-
 -MENT GRONDING FROM METER TO MAIN/FIRST
 MEANS OF DISC.
 PLEASE SEE 250.24,250.6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-14 Cont ID  
Sent By dpalmer Date 2004-06-14 Time 12:39 Rev Time 1.50
Received By dpalmer Date 2004-06-14 Time 11:26 Sent To  
Notes
2004-06-14 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE THAT ONE SET OF MEP
 PLANS HAVE BEEN RETAINED FOR FILE.
 NOTICE HAS BEEN GIVEN ON PREVIOUS REVIEW
 -S TO INCLUDE ALL LICENSE # 'S AS
 REQUIRED BY FAC 61G15-23.002 ANDFS471.
 023. WE HAVE BEEN IN CONTACT WITH DBPR
 AND FBPE'S AND METRO DESIGN GROUP INC
 DOES NOT CONTAIN LICENSE #(S) AS REQ'D.
  
 2)NOTE: PLEASE SEE PLANS ARE NOT COM-
 -PLETE AT THIS TIME FOR FULL REVIEW.
 PLEASE SUBMIT PANE SCHEDULES TO CORRE-
 -LATE WITH CIRCUITING SHOWN ON PLANS.
 PLEASE INCLUDE LOAD CALCULATIONS AND
 INFORMATION ON SERVICE. NEW OR EXSITING?
  
 3)NOTE: IF SERVICE IS NEW, PLEASE SUBMIT
 AIC RATING FOR ALL NEW EQUIPMENT. 110.9
  
 4)NOTE: PLEASE GIVE INFORMATION ON GFI
 PROTECTION FOR KITCHEN RECEPTS ARE
 REQUIRED UNDER THE 2002 NEC. 210.8B3
  
 5)NOTE: PLEASE SEE 210.63 FOR REQUIRED
 RECEPTS FOR RT EQUIPMENT.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-07-16 Cont ID  
Sent By mamini Date 2004-07-16 Time 10:44 Rev Time 1.00
Received By mamini Date 2004-07-16 Time 10:44 Sent To  
Notes
2004-07-16 00:00:00PASSED WITH PROVISOS:
 1. ANY NEW CONNECTIONS TO THE CITY
 SERVICES REQUIRES APPROVAL FROM THE
 PUBLIC UTILITIES & ENGINEERING SERVICES
 949-1085 MANNY GONZALEZ AND A SEPARATE
 PERMIT FROM THE CONSTRUCTION SERVICES
 DEPT.
 2. ANY WORK WITHIN PUBLIC R.O.W REQUIRES
 A SEPARATE PERMIT FORM THE PUBLIC
 UTILITIES & ENGINEERING SERVICES,
 494-1086, WINDAL PALMER AND FROM THE
 PB COUNTY AS THEY APPLY.
 3. EROSION & SEDIMENTATION CONTROL
 DEVICES MUST BE IN PLACE PRIOR TO
 BEGINNING THE PROJECT AND MUST BE
 MONITORED, AND MAINTAINED THROUGHOUT.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-02-11 Cont ID  
Sent By mwennerg Date 2005-02-11 Time 11:40 Rev Time 0.00
Received By mwennerg Date 2005-02-11 Time 11:29 Sent To  
Notes
2005-02-11 00:00:001) PLEASE EXPLAIN HOW ACCESS INTO THE
 BUILDING WILL BE ACCOMPLISHED THROUGH
 THE OVERHEAD ROLLING DOORS AFTER
 BUSINESS HOURS.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-01-07 Cont ID  
Sent By mcarsill Date 2005-01-07 Time 14:55 Rev Time 0.00
Received By mcarsill Date 2005-01-07 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-10-22 Cont ID  
Sent By lmartine Date 2004-10-22 Time 11:43 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
2004-10-22 00:00:00SEE APPROVAL SIGNATURE ON PLANS BY MIKE
 CARSILLOLM

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-09-16 Cont ID  
Sent By mcarsill Date 2004-09-16 Time 10:13 Rev Time 0.00
Received By mcarsill Date 2004-09-16 Time 10:13 Sent To  
Notes
2004-09-16 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. A MINUMUM OF AT
 LEAST 6" HIGH NUMBERS ARE REQUIRED.
  
 2) AN ILLUMINATED EXIT SIGN REQUIRED
 AT MAIN DOOR LEADING TO PATIO AREA.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT, AND SUPPRESSION SYSTEM.
  
 4) AN OCCUPANT LOAD SIGN SHALL BE
 POSTED INDICATING 80 OCCUPANTS ONLY
 SINCE THE BUILDING IS NOT PLANNED TO
 BE FIRE SPRINKLER PROTECTED.
  
 5) COULD NOT LOCATE A DOOR SCHEDULE
 WITH THE PLANS.
  
 6) NO PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS OR GUARDRAILS COULD
 BE LOCATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-10 Cont ID  
Sent By mcarsill Date 2004-06-10 Time 16:00 Rev Time 0.00
Received By mcarsill Date 2004-06-10 Time 16:00 Sent To  
Notes
2004-06-10 00:00:001) SITE PLAN DOES NOT DISPLAY
 LOCATIONS OF ANY EXISTING OR NEW
 FIRE HYDRANTS.
  
 2) PANIC HARDWARE REQUIRED ON ALL
 EXIT DOORS AS NOTED ON THE DOOR
 SCHEDULE SUBJECT TO 100 OR MORE PERSONS.
  
 3) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF 6" HIGH NUMBERS ARE REQUIRED.
  
 4) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS
 AND GUARDRAILS.
  
 5) SOME ELECTRICAL DRAWINGS HAVE
 DOORS SWINGING IN THE WRONG DIRECTION.
  
 6) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT, AND SUPPRESSION SYSTEM.
  
 8) EXIT SIGN DIRECTS PERSONS TO
 OUTDOOR DINING BUT SOME PLANS ARE
 MISSING THE EXIT DOOR.
  
 9) PLEASE PROVIDE DETAILS ON EXIT
 DISCHARGE LOCATIONS.
  
 10) EXIT DOOR IS SHOWN THRU SMOKER
 ROOM. WHAT EQUIPMENT AND ACTIVITIES
 OCCUR. IS THIS AREA CONSIDERED MORE
 DANGEROUS THAN THE DINING ROOM.
  
 11) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-03-30 Cont ID  
Sent By adarroug Date 2005-03-30 Time 13:35 Rev Time 0.00
Received By adarroug Date 2005-03-30 Time 13:35 Sent To P
Notes
2005-03-30 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-03-24 Cont ID  
Sent By adarroug Date 2005-03-24 Time 07:59 Rev Time 0.00
Received By adarroug Date 2005-03-24 Time 07:59 Sent To P
Notes
2005-03-24 00:00:00TO "KSTEVENS" BOX/REVISON

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 13:53 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 13:53 Sent To P
Notes
2005-03-10 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 11:27 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 11:27 Sent To M
Notes
2005-03-10 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 09:13 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 09:13 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#18/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 08:49 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 08:49 Sent To B
Notes
2005-01-06 00:00:00TO "SH" DESK./SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-12-16 Cont ID  
Sent By mjacobs Date 2004-12-16 Time 10:41 Rev Time 0.00
Received By mjacobs Date 2004-12-16 Time 10:40 Sent To B
Notes
2004-12-16 00:00:00SENT TO "SH" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-12-16 Cont ID  
Sent By mjacobs Date 2004-12-16 Time 08:18 Rev Time 0.00
Received By mjacobs Date 2004-12-16 Time 08:18 Sent To B
Notes
2004-12-16 00:00:00SENT TO "SH" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By mjacobs Date   Time   Rev Time 0.00
Received By mjacobs Date 2004-12-15 Time 16:57 Sent To  
Notes
2004-12-15 00:00:00SENT TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-16 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 15:38 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 15:38 Sent To B
Notes
2004-11-16 00:00:00SENT TO "B" TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-26 Cont ID  
Sent By csiegber Date 2004-10-26 Time 12:13 Rev Time 0.00
Received By csiegber Date 2004-10-26 Time 12:13 Sent To B
Notes
2004-10-26 00:00:00TO LM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-26 Cont ID  
Sent By csiegber Date 2004-10-26 Time 12:11 Rev Time 0.00
Received By csiegber Date 2004-10-26 Time 12:11 Sent To P
Notes
2004-10-26 00:00:00TO KS DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-24 Cont ID  
Sent By mmclean Date 2004-09-17 Time 12:29 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 15:17 Sent To  
Notes
2004-08-24 00:00:00TO COMM BD#34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-19 Cont ID  
Sent By mmclean Date 2004-07-19 Time 11:10 Rev Time 0.00
Received By mmclean Date 2004-06-09 Time 12:52 Sent To  
Notes
2004-06-09 00:00:00TO COMM BD#57

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-03-22 Cont ID  
Sent By pkrauss Date 2005-03-22 Time 14:55 Rev Time 0.45
Received By pkrauss Date 2005-03-22 Time 14:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-05 Cont ID  
Sent By pkrauss Date 2005-01-05 Time 06:56 Rev Time 0.40
Received By pkrauss Date 2005-01-05 Time 06:38 Sent To  
Notes
2005-01-05 00:00:00PROVISO:
 ADDITIONAL PERMITA REQUIRED FOR THE
 HOODS, FIRE SUPPRESSION AND WALK-IN
 COOLER/FREEZER.PLEASE PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-09-18 Cont ID  
Sent By pkrauss Date 2004-09-18 Time 08:44 Rev Time 0.55
Received By pkrauss Date 2004-09-18 Time 08:35 Sent To  
Notes
2004-09-18 00:00:00PROVISO:
 ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION, AND WALK-IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-22 Cont ID  
Sent By pkrauss Date 2004-06-22 Time 14:20 Rev Time 0.55
Received By pkrauss Date 2004-06-22 Time 14:19 Sent To  
Notes
2004-06-22 00:00:00DENIED:
 1.SEE COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.PLANS DO NOT
 COMPLY WITH FS 471.025 & FAC61G15-23.002
  
 2.INDICATE IF THE EQUIPMENT IS NEW OR
 EXISTING.PROVIDE EQUIPMENT SCHEDULE.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) 403.3.
  
 4.PROVIDE AIRBALANCE SCHEDULE IN
 ACCORDANCE WITH 2001 FBC(M) 501.4.
  
 5.ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS.PROVIDE PLANS AND MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 6.PROVIDE ADDITIONAL INFORMATION ON
 THE VENTILATION FOR THE SMOKER ROOM.
 PROVIDE SUBMITTAL FOR THE SMOKER.
  
 7.INDICATE CONDENSATE LINE SIZE, PIPE
 MATERIAL, AND TERMINATION.
  
 8.PROVIDE CURB DETAIL FOR RTU'S.
 MINIMUM OF 8" ABOVE THE ROOF SURFACE
 REQUIRED PER 2001 FBC 1511.7.
  
 9.INDICATE IF THE CONDENSER FOR THE
 WALK-IN COOLER IS REMOTE OR PACKAGE.
 REMOTE CONDENSERS LOCATED ON THE ROOF
 SHALL COMPLY WITH 2001 FBC 1511.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 8 Status P Date 2005-04-01 Cont ID  
Sent By kstevens Date 2005-04-01 Time 16:19 Rev Time 2.25
Received By kstevens Date 2005-04-01 Time 16:19 Sent To  
Notes
2005-04-01 00:00:00REVISION FOR GAS RISER DIAGRAM APPROVED
 FULL SIZE REQUIRED TO SHUT OFF VALVE TO
 ALL GAS APPLIANCES. SEE RED LINE
 CORRECTIONS.

Review Stop P PLUMBING
Rev No 7 Status F Date 2005-03-26 Cont ID  
Sent By kstevens Date 2005-03-26 Time 06:19 Rev Time 1.00
Received By kstevens Date 2005-03-26 Time 06:19 Sent To  
Notes
2005-03-26 00:00:00GAS REVISION DENIED
  
 1) GAS RISER DIAGRAM MEASURMENTS FOR GAS
 LEG #1 ARE NOT ALL SHOWN. SEE
 HIGHLIGHTED SECTIONS AND INDICATE THE
 LENGHT FOR EACH SECTION. THERE IS
 CONFUSION ON THE MEASURMENT 18'@ 2".
 PLEASE INDICATE WHICH SECTION OF PIPE
 THIS MEASURMENT IS FOR, THEN SHOW THE
 MEASUREMENT FOR THE OTHER SECTION OF
 PIPE. SECTION 104.2.1.
 2) ADDING UP THE AVAILABLE MEASURMENTS
 FOR GAS LEG #1, THE TOTAL DEVELOPED
 LENGTH OF THAT LEG IS MORE THAN THE 89'
 INDICATED. PLEASE RECALCULATE THE
 DEVELOPED LENGTH AFTER ADDING ADDITIONAL
 PIPE LENGHTS ON ISOMETRIC. IF OVER 100'
 THAN 2-1/2" PIPE WILL BE REQUIRED. SEE
 TABLE 402(2) FUEL GAS CODE.
 3) NO MANUF. SPECIFICATION SHEET FOR THE
 WATER HEATER HAS BEEN SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2005-03-15 Cont ID  
Sent By kstevens Date 2005-03-15 Time 17:19 Rev Time 0.95
Received By kstevens Date 2005-03-15 Time 17:19 Sent To  
Notes
2005-03-15 00:00:00REVISION/DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A) THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS REVISION.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - MANY CUT SECTIONS DO
 NOT SHOW THE LENGTH REQUIRED.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 - NEW
 GAS FIXTURES NOT SHOWN ON PREVIOUS
 REVIEWS ARE "CHAR GRILLE", AND "STOCK
 POT RANGE". SUBMIT MANUF. SPECIFICATION
 SHEETS SHOWING BTU'S AND LISTING BY AN
 APPROVED TESTING AGENCY. - RANGE ON
 PREVIOUS REVIEW AND MANUF. SHEET
 INDICATED 230,000 BUT. REVISION SHOWS
 110,000 BTU. PLEASE CLARIFY, AND IF
 DIFFERENT APPLIANCES NEW SHEETS WILL BE
 REQUIRED. - STEAM TABLE SHOWS 15,000 BTU
 PREVIOUS SHOWED 27,500 BTU. PLEASE
 CLARIFY AND IF DIFFERENT APPLIANCES NEW
 SHEETS WILL BE REQUIRED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-02-08 Cont ID  
Sent By kstevens Date 2005-02-08 Time 12:11 Rev Time 1.84
Received By kstevens Date 2005-02-08 Time 12:11 Sent To  
Notes
2005-02-08 00:00:00REVISION OK - GAS REVISION SHT MPE-9 -
 MPE-2 FIXTURE SCHEDULE OK PENDING
 APPROVAL OF DBPR FIELD INSPECTOR.

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-01-11 Cont ID  
Sent By kstevens Date 2005-01-11 Time 18:30 Rev Time 0.70
Received By kstevens Date 2005-01-11 Time 18:30 Sent To  
Notes
2005-01-11 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) MEP SHEETS HAVE TWO DIFFERENT
 SIGNATURES FOR THE SAME PE. PLEASE HAVE
 ENGINEER SIGN WITH LEGAL SIGNATURE. FAC
 61G15-23.002 & FS 471.025
 2) SHT MEP-9 INDICATES "GAS RUN UNDER
 SLAB (SEE DETAIL)" IN TWO LOCATIONS. NO
 DETAIL FOR THIS IS SHOWN. PLEASE
 INDICATE WHERE THE DETAIL CAN BE
 LOCATED. - REQUIRED INSTALLATION WILL BE
 TO HAVE THE SLAB CUT OUT AND GALV. PIPE
 RUN IN SLAB, PAINTED WITH BITUMINOUS
 PAINT, THEN LIGHT WEIGHT CONCRETE POURED
 OVER THE PIPE AFTER TESTING AND APPROVAL
 BY INSPECTOR.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-26 Time 12:11 Rev Time 3.25
Received By kstevens Date 2004-10-22 Time 17:48 Sent To  
Notes
2004-10-26 00:00:00SEPARATE PLANS/PERMIT REQUIRED FOR CAR
 WASH - SEPARAGE GAS PERMIT REQUIRED -
 REVISION REQUIRED FOR SHT MEP-9 SHOWING
 CORRECT PIPE SIZES FOR GAS PIPING
 - PROVISO - NO CONTACT FROM R. COMPO -
 EXISTING 1500 GAL GREASE INTECEPTOR -
 NEED LETTER FROM MR. COMPO APPROVING THE
 EXISTING GREASE INTECEPTOR OR OTHER RE-
 QUIREMENTS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-09-22 Cont ID  
Sent By kstevens Date 2004-09-22 Time 18:00 Rev Time 3.00
Received By kstevens Date 2004-09-22 Time 18:00 Sent To  
Notes
2004-09-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 A) FOLLOWING COMMENTS FROM THE FIRST RE-
 VIEW HAVE NOT BEEN ADDRESSED. THE COMME-
 NT NUMBER FROM THE FIRST REVIEW WILL BE
 USED TO AVOID CONFUSION.
 1) ROUTE PLANS TO DBPR HOTEL AND RESTUR-
 ANT DIVISION FOR REVIEW. PLANS SHALL BE
 STAMPED AND WORK SHEETS ATTACHED TO EACH
 SET OF PLANS FOR REVIEW WHEN RESUBMITT-
 ING TO CITY WPB FOR REVIEW. SECTION 101.
 4.7
 2) SHT A-2 PRIVATE TOILET ROOM SHALL BE
 ADAPTABLE. SHOW TURNING AREA IN ROOM AND
 INDICATE TOILET TO BE 18" OFF WALL TO
 THE CENTER OF THE FIXTURE. SECTION 11-4.
 1.3(11)
 4) SHT A-4 SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SECT-
 IONS 1106, & 1107. SHOW SQUARE FOOTAGE
 OF EACH ROOF SECTION BEING DRAINED. SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS BEING ADDED TO S.F. OF ROOF
 AREAS. INDICATE SIZE OF GUTTER. SHOW THE
 HIGH POINTS OF THE GUTTERS. TABLE 1106.6
 5) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD 2938-96 @ (561) 837-
 4074. - SUBMIT REQUIREMENT SHEET
 8) SUBMIT A WATER RISER DIAGRAM IN ISO-
 METRIC FORM AS REQUIRED BY SEC 104.3.1.1
 9) SUBMIT A STORM RISER DIAGRAM. SHOW
 TERMINATION OF STORM PIPING. SECTION
 104.3.1.1
 10) GAS REQUIREMENTS
 B) SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED.
 F) SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER FBC-2001 FUEL GAS CODE SECTION
 304 - WATER HEATER ROOM REQUIRES COMBUS-
 TION AIR.
 H) SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH THE
 STANDARDS NFPA 54, AND THE FBC-2001 FUEL
 GAS CODE SECTION 402.2
 11) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. UTILITY ORD./SECTION 608.
 13.2.
 **************NEW COMMENTS**************
 1B) SHT A-2 STAFF TOILET ROOM REQUIRES
 MINIMUM 5"3" WIDE TO ACCOUNT FOR 18" TO
 CENTER OF W/C OFF WALL, 30" CENTER OF
 W/C TO LAV, AND 15" OFF WALL TO CENTER
 OF LAV. SECTION 405.3.1
 2B) SHT MEP9 GREASE WASTE RISER DIAGRAM.
 FLOOR DRAIN SHALL NOT SAFEWASTE INTO THE
 FLOOR SINK, BUT SHALL TIE INTO THE VENT-
 ED LINE SEPARATELY. (TAKE 0UT KITCHEN)
 ALSO MAXIMUM DISTANCE FROM VENT TO TRAP
 IS 6 FEET. TABLE 906.1
 3B) SHT MEP9 TAKE OUT DRIVE THRU, FLOOR
 DRAIN IS NOT AN APPROVED INDIRECT WASTE
 RECEPTOR. USE A FLOOR SINK OR A HUB
 DRAIN PER SECTION 802.3 OR 802.3.2.
 4B) SHT MEP9 GAS RISER DIAGRAM AND GAS
 LOAD CALCULATIONS DO NOT REFLECT EACH
 OTHER. BOILER @ 150,000 BTU & FRYER @
 98,000 BTU ARE NOT SHOWN ON RISER DIAGR-
 AM. PLEASE CLAIRFY/CORRELATE. SECTION
 104.2.1.
 ********WHEN RESUBMITTING PLANS*********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-17 Cont ID  
Sent By kstevens Date 2004-07-17 Time 08:29 Rev Time 2.50
Received By kstevens Date 2004-07-17 Time 08:29 Sent To  
Notes
2004-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ROUTE PLANS TO DBPR HOTEL AND RESTUR-
 AND DIVISION FOR REVIEW. PLANS SHALL BE
 STAMPED AND WORK SHEET ATTACHED TO EACH
 SET OF PLANS FOR REVIEW WHEN RESUBMITT-
 ING TO CITY WPB FOR REVIEW.
 2) SHT A-2 PRIVATE TOILET ROOM SHALL BE
 ADAPTABLE. INDICATE BACKING FOR GRAB
 BARS, SHOW TURING AREA IN ROOM AND IN-
 DICATE TOILET TO BE 18" OFF WALL. SECT-
 ION 11-4.1.3(11).
 3) SHT A-2 STAFF TOILET ROOM SHALL BE
 ACCESSIBLE. SECTION 11-4.1.3(11). SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECT-
 IONS 11-4.16, 11-4.19, & 11.4.22 AND ALL
 SUBSECTIONS.
 4) SHT A-4 SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SECT-
 IONS 1106, & 1107. SHOW SQUARE FOOTAGE
 OF EACH ROOF SECTION BEING DRAINED. SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS BEING ADDED TO SF OF ROOF. SHOW
 ALL AREAS OF ROOFS DRAINING ONTO THE
 ROOF FROM ABOVE ADDED TO ROOF SF. - IN-
 DICATE SIZE AND SLOPE OF GUTTER. SHOW
 HIGH POINT OF GUTTER. SHOW SIZE OF DOWN-
 SPOUTS. SEE TABLE 1106.6. - PLEASE INDI-
 CATE HOW THE ROOF OVER THE SMOKER ROOM
 IS BEING DRAINED. GUTTERS AND DOWNSPOUTS
 ARE REQUIRED ON ALL BUILDINGS WITH EAVES
 OF LESS THAN 6" HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES. SECTION
 1503.4.4
 5) CONTACT RODNEY COMPO ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD #2938-96 @ (561) 837-
 4074.
 6) SHT A-7 ROOM ELEVATION SHOWS ACCESS-
 IBLE URINAL ON RIGHT SIDE, BUT FLOOR
 PLAN SHOWS CLEAR FLOOR SPACE FOR URINAL
 ON THE LEFT SIDE. PLEASE CORRELATE FLOOR
 PLAN AND ELEVATION DETAIL. SEC 104.2.1.
 7) SHT MEP-4 ICE MAKER DOES NOT SHOW A
 FLOOR SINK OR HUB DRAIN FOR DRAINING
 FIXTURE. PLEASE CLARIFY. SECTION 301.3
 8) A SANITARY AND A WATER RISER DIAGRAM
 IN ISOMETRIC FORM ARE REQUIRED PER SEC
 104.3.1.1
 9) SUBMIT A STORM RISER DIAGRAM AND A
 SECONDARY DRAIN STORM RISER DIAGRAM.
 SECTION 104.3.1.1
 10) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR REQUIRED GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 11) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. UTILITY ORD/SEC 608.13.2.
 12) THE FIRM LICENSE NUMBER AND PRINTED
 NAME OF THE ARCHITECT SHALL APPEAR ON
 THE TITLE BLOCK ON EACH SHEET SIGNED/
 SEALED/DATED BY ARCHITECT OF RECORD.
 FAC 61G1-16.004(2)(5) & FS 481.2055.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2004-09-17 Cont ID  
Sent By mmclean Date 2004-09-17 Time 12:28 Rev Time 0.00
Received By mmclean Date 2004-09-17 Time 12:28 Sent To I
Notes
2004-09-17 00:00:00APPROVED BY SHIRLEY GRAHAM MM

Review Stop Z ZONING
Rev No 2 Status F Date 2004-08-30 Cont ID  
Sent By mmclean Date 2004-08-30 Time 12:37 Rev Time 0.00
Received By mmclean Date 2004-08-30 Time 12:37 Sent To  
Notes
2004-09-01 00:00:00DENIED, NEED LANDSCAPE PLANS TO CODE
 CALLED MARK R
2004-08-30 00:00:00WAITING FOR LANDSCAPE TO COMPLETE REVIEW
 PLANS WILL BE DELIVERED ON 8/31/04

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-11 Cont ID  
Sent By mmclean Date 2004-07-19 Time 11:08 Rev Time 0.25
Received By mmclean Date 2004-07-19 Time 11:08 Sent To  
Notes
2004-07-19 00:00:00DENIED, NEED TO PROVIDE LANDSCAPE
 DRAWINGS TO CODE.CALLED CONTR FILE
 UNDER R FOR P/Y MM