| 2004-06-19 00:00:00 | PLAN REVIEW DENIED, FBC 2001 FUEL GAS |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | (2)104.6.5 BUILDING PERMIT VALUATION. |
| | IN THE OPINION OF THE BUILDING OFFICIAL |
| | THE CLAIMED VALUATION OF BUILDING, AL- |
| | TERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED ESTIMATES |
| | AND/OR BONA FIDED SIGNED CONTRACTS (EX- |
| | CLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION FOR BUILDINGS AND |
| | SYSTEMS SHALL BE FOUND IN MARSHALL AND |
| | SWIFT OR THE SOUTHERN BUILDING CODE |
| | CONGRESS INTERNATIONAL VALUATION TABLES, |
| | LATEST EDITION, AND SHALL BE BASED ON |
| | TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- |
| | ICAL, INTERIOR FINISH, NORMAL SITE WORK |
| | (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, OVERHEAD |
| | AND PROFIT, EXCLUDING ONLY LAND VALUE. |
| | (3) BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | (4) SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |