Plan Review Details - Permit 04060338
Plan Review Stops For Permit 04060338
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-04-06 Cont ID  
Sent By shill Date 2005-04-06 Time 14:16 Rev Time 0.50
Received By shill Date 2005-04-06 Time 14:16 Sent To  
Notes
2005-04-06 00:00:00REVISION DATED 3/8/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-03-18 Cont ID  
Sent By shill Date 2005-03-18 Time 16:53 Rev Time 1.00
Received By shill Date 2005-03-18 Time 16:29 Sent To  
Notes
2005-03-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DETAILS 12 THROUGH 15, SHEET A4.2
 REFER TO "ADDITION".THE FREEZER WAS
 SHOWN AS EXISTING ON THE PERMIT SET OF
 PLANS.IF THIS IS AN ADDITION, PROVIDE
 AREA CALCULATIONS.IMPACT FEES
 (233-5025) AND ZONING REVIEWS REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-11-24 Cont ID  
Sent By shill Date 2004-11-24 Time 13:55 Rev Time 2.00
Received By shill Date 2004-11-24 Time 11:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-11-03 Cont ID  
Sent By shill Date 2004-11-03 Time 16:48 Rev Time 2.00
Received By shill Date 2004-11-03 Time 16:20 Sent To PC
Notes
2004-11-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LISTS; BEFORE
 RESUBMITTING PLEASE SIGN THE OWNER/AGENT
 LINE OF THE ENERGY CALC.THIS CAN BE
 DONE BY AN OWNER OR AGENT FOR THE OWNER;
 NOT REQUIRED TO BE DONE BY THE
 ARCHITECT.
  
 2.)SEE PREVIOUS LISTS; FLORIDA STATE
 OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOAS SUBMITTED.
 WWW.FLORIDABUILDING.ORG.FAC9B-72.
  
 3.)PLEASE PROVIDE DESIGN LOAD
 INFORMATION FOR THE TRUSS STORAGE.THE
 LETTER STATES THAT "ANALYSIS" HAS BEEN
 DONE.PLEASE PROVIDE THE INFORMATION -
 ADDITIONAL LOAD, DESIGN LOAD OF EXISTING
 TRUSSES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-31 Cont ID  
Sent By shill Date 2004-08-31 Time 10:11 Rev Time 4.00
Received By shill Date 2004-08-31 Time 10:11 Sent To  
Notes
2004-08-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC BEFORE ISSUANCE.
  
 2.)DOOR #2 LACKS THE MANEUVERING
 CLEARANCE REQUIRED BY FBC11 FIGURE 25
 (MIN 12", PLAN SHOWS 7 1/2").REVISE
 AFFECTED SHEETS.
  
 3.)PROVIDE LOADING INFORMATION FOR
 THE SHUTTER STORAGE, A4.2.SHOW THAT
 THE EXISTING TRUSSES CAN ACCOMODATE THIS
 ADDITIONAL LOAD.
  
 4.)THERE IS A STRUCTURAL MULLION FOR
 THE STOREFRONT SYSTEM THAT DOES NOT
 APPEAR TO BE INCLUDED IN THE NOA
 (ANGLED APPLICATION).ADDRESS.
  
 5.)SOME SHEETS ARE NOT SIGNED, SEALED
 AND DATED (EC1, EC2, EC3, A2.3, A3, A6.2
 A7, A7.1, A8, A9, A9.1, M0, M3, M4, M5,
 P0, E0, E1, E4, E6), ONE SET.
  
 6.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 TEST REPORT.WWW.FLORIDABUILDING.ORG
 THIS IS REQUIRED FOR ALL OF THE DADE
 COUNTY NOAS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-15 Cont ID  
Sent By shill Date 2004-07-13 Time 16:31 Rev Time 4.00
Received By shill Date 2004-07-13 Time 16:31 Sent To PC
Notes
2004-07-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC (P2) .PROVIDE THE PRINTED
 NAME AND LICENSE NUMBER OF THE PERSON
 WHO PREPARED THE ENERGY CALC.
  
 2.)FLORIDA STATE, LOCAL OR SITE
 SPECIFIC PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOAS.PLEASE SEE
 WWW.FLORIDABUILDING.ORG (PRODUCT
 APPROVAL) FOR MORE INFORMATION.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.FS713.13
  
 4.)THE DOUBLE DOORS 1A AND 1B ARE
 REQUIRED TO COMPLY WITH FBC11-4.13.7
 (MINIMUM OF 48" PLUS THE WIDTH OF THE
 DOOR), FIGURE 26(A).
  
 5.)REGARDING DOORS #7 AND #2 (SERVICE&
 COMMUNITY ROOM) DOUBLE LEAF DOORS ARE
 TO COMPLY WITH 11-4.13.4 AND 11-4.13.5.
  
 6.)THE DOOR TO THE WOMEN'S
 ACCESSIBLE STALL IS TO HAVE THE
 MANUEVERING CLEARANCE AS REQUIRED BY
 FBC11-4.13.6, FBC11-4.23.2, FIGURE 25.
  
 7.)PROVIDE INFORMATION AS TO WHERE
 AND HOW THE HURRICANE SHUTTERS WILL BE
 STORED.IF THEY ARE STORED VERTICALLY,
 PROVIDE A STRUCTURAL RACK DETAIL.
  
 8.)THE PRODUCT APPROVAL FOR DOOR #6,
 THE STEEL ENTRY DOOR, HAS A PRODUCT
 LIMITATION 3.2, UNIT SHALL BE INSTALLED
 ONLY AT LOCATIONS PROTECTED BY A CANOPY
 OR OVERHANG SUCH THAT THE ANGLE BETWEEN
 THE EDGE OF CANOPY OR OVERHANG TO SILL
 IS LESS THAN 45 DEGREES.ADDRESS.
  
 9.)PROVIDE PRODUCT APPROVALS FOR THE
 ENTRY DOORS #1A AND #5.
  
 10.) PROVIDE A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE, SEE ATTACHED FORM.
 IF NOT PROVIDED BEFORE PERMIT ISSUANCE,
 THE SHUTTERS WILL REQUIRE A SEPARATE
 PERMIT.
  
 11.) ANY PRODUCT APPROVALS REQUIRED BUT
 NOT SUBMITTED PROPERLY BEFORE ISSUANCE
 WILL REQUIRE SEPARATE PERMITS FOR THOSE
 ITEMS.
  
 12.) IT APPEARS THAT THERE IS A
 STRUCTURAL ANGLED MULLION AT DOOR #1A.
 PLEASE PROVIDE PRODUCT APPROVAL/TEST
 REPORTS.
  
 13.)SEPARATE PERMITS REQUIRED FOR THE
 SIGNS.
  
 14.)PROVIDE SIGNAGE TO COMPLY WITH
 FBC704.2.1.4; NOTE ON PLAN.
  
 15.)PROVIDE A LOCATION FOR THE
 STORAGE OF THE HURRICANE SHUTTERS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-04-05 Cont ID  
Sent By dpalmer Date 2005-04-05 Time 14:34 Rev Time 0.50
Received By dpalmer Date 2005-04-05 Time 14:27 Sent To  
Notes
2005-04-05 00:00:00REDLINED 2002 NEC 210.8

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-03-14 Cont ID  
Sent By dpalmer Date 2005-03-14 Time 17:27 Rev Time 0.50
Received By dpalmer Date 2005-03-14 Time 17:07 Sent To  
Notes
2005-03-14 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002,
 PLEASE INCLUDE ALL INFORMATION ON TITLE
 BLOCK AS REQUIRED.
 PLEASE SEE THIS WAS NOTED ON ALL
 PREVIOUS REVIEWS ON LAST THREE
 ELECTRICAL REVIEWS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE INCLUDE NOTE FOR REQUIRED
 GFI PROTECTION. PLEASE SEE SECTION
 210.8(B)(3) IS NEW FOR THE 2002 CODE AND
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 3)NOTE: PLEASE SEE TITLE AREA ON PLANS
 FOR REVISIONS. PLEASE SEE NEW REVISION
 IS INDICATED AS # 7 AND PREVIOUS
 REVISION WAS REV #1? PLEASE VERIFY
 REVISIONS #2-#6?? PLEASE SHOW AND
 INDICATE ANY OTHER REV'S.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 15:55 Rev Time 1.50
Received By dpalmer Date 2004-10-08 Time 15:37 Sent To  
Notes
2004-10-08 00:00:00PE'S PRINTED LICENSE # AS REQUIRED UNDER
 FAC 61G15-23.002 NOT PRINTED ON TITLE
 BLOCK. HAND WROTE ON E-SHEETS ONLY.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-31 Cont ID  
Sent By dpalmer Date 2004-08-31 Time 13:44 Rev Time 0.75
Received By dpalmer Date 2004-08-31 Time 13:20 Sent To  
Notes
2004-08-31 00:00:00*************** UNSAT ***************
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED..
  
 1)NOTE: PLEASE SEE BOTH SETS OF PLANS
 ARE REQUIRED TO BE SIGNED, DATED AND
 SEALED. FS 471.025 FAC 61G15-23.002
  
 2)NOTE: PLEASE SEE ABOVE FAC FOR MISSING
 INFORMATION REQUIRED ON TITLE BLOCKS.
  
 THE ABOVE TWO ARE FOR ALL TRADES
 WHEATHER OR NOT COMMENT IS MADE BY THOSE
 REVIEWERS.
  
 3)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS
 REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By dpalmer Date 2004-06-15 Time 13:06 Rev Time 2.00
Received By dpalmer Date 2004-06-15 Time 08:04 Sent To  
Notes
2004-06-15 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCKS AS REQUIRED UNDER
 FAC 61G15-23.002/ 61G1-16.004
 PLEASE INCLUDE ALL NAMES AND LICENSE #'S
  
 PLEASE ALOS SEE ONLY ONE SET OF PLANS
 ARE SIGNED, DATED AND SEALED AS REQUIRED
 UNDER FS 471.025/ 61G15-23.002
  
 2)NOTE: PLEASE VERIFY REQUIRED SIGN
 CIRCUIT PER 600.5
  
 3)NOTE: PLEASE SEE PANEL "P1", SHOWS
 A PANEL "ILG", YET RISER SHOWS "IGP".
 (MISPRINT)
  
 4)NOTE: PLEASE PROVIDE COMPLETE LOAD
 CALCULATION ON EXISTING SERVICE AND
 SEC'S. SOME OF THE SERVICES ON THIS
 MALL ARE IN DANGER OF HEATED CONDUCTORS
 AND OVERLOADED SERVICES AND SOME
 SEEM TO BE "MAXED" OUT AND CLOSE TO
 BEING OVERLOADED AT PRESENT TIME.
 215.5/220
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS SOME MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-04-12 Cont ID  
Sent By mwennerg Date 2005-04-12 Time 09:43 Rev Time 0.00
Received By mwennerg Date 2005-04-12 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-03-23 Cont ID  
Sent By mwennerg Date 2005-03-23 Time 13:44 Rev Time 0.00
Received By mwennerg Date 2005-03-23 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-10-20 Cont ID  
Sent By mcarsill Date 2004-10-20 Time 16:26 Rev Time 0.00
Received By mcarsill Date 2004-10-20 Time 16:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-09-16 Cont ID  
Sent By mcarsill Date 2004-09-16 Time 12:34 Rev Time 0.00
Received By mcarsill Date 2004-09-16 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-10 Cont ID  
Sent By mcarsill Date 2004-06-10 Time 16:14 Rev Time 0.00
Received By mcarsill Date 2004-06-10 Time 16:14 Sent To  
Notes
2004-06-10 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) ALL COOLERS AND FREEZERS ARE TO
 BE FIRE SPRINKLER PROTECTED AS NOTED
 ON THE PLANS.
  
 3) PLEASE INDICATE ALL INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY NEW HOOD, DUCTS, OR SUPPRESSION
 SYSTEMS.
  
 5) A MINIMUM OF AT LEAST 10 FEET
 CLEARANCE IS REQUIRED BETWEEN EXHAUST
 AND SUPPLY EQUIPMENT.
  
 6) PLEASE INDICATE OCCUPANT LOAD FOR
 THE LOCATION INCLUDING EMPLOYEES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-30 Cont ID  
Sent By adarroug Date 2005-03-30 Time 09:23 Rev Time 0.00
Received By adarroug Date 2005-03-30 Time 09:23 Sent To  
Notes
2005-03-30 00:00:00TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 13:14 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 13:14 Sent To  
Notes
2005-03-10 00:00:00TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-02 Cont ID  
Sent By adarroug Date 2005-03-02 Time 13:09 Rev Time 0.00
Received By adarroug Date 2005-03-02 Time 13:08 Sent To M
Notes
2005-03-02 00:00:00TO "M" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 10:10 Rev Time 0.00
Received By csiegber Date 2004-11-09 Time 10:10 Sent To  
Notes
2004-11-09 00:00:00TO COMM BD#37

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 16:36 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 16:36 Sent To  
Notes
2004-10-05 00:00:00TO COMM BD#39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-19 Time 14:09 Rev Time 0.00
Received By csiegber Date 2004-08-19 Time 14:09 Sent To  
Notes
2004-08-19 00:00:00TO COMM BD#40

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-14 Cont ID  
Sent By shill Date 2004-07-14 Time 16:56 Rev Time 0.00
Received By shill Date 2004-06-08 Time 15:58 Sent To  
Notes
2004-06-08 00:00:00TO COMM BD#63

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-04-26 Cont ID  
Sent By hmoser Date 2005-04-26 Time   Rev Time 0.00
Received By hmoser Date 2005-04-26 Time 17:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date 2005-03-08 Cont ID  
Sent By pkrauss Date 2005-03-08 Time 11:46 Rev Time 0.00
Received By pkrauss Date 2005-03-08 Time 11:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-10-15 Cont ID  
Sent By pkrauss Date 2004-10-15 Time 08:41 Rev Time 0.40
Received By pkrauss Date 2004-10-15 Time 07:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-08-31 Cont ID  
Sent By pkrauss Date 2004-08-30 Time 09:30 Rev Time 0.55
Received By pkrauss Date 2004-08-30 Time 09:15 Sent To  
Notes
2004-08-30 00:00:00DENIED:
 PLAN SHEETS M0, M3, M4,AND M5 IN ONE
 SET OF PLANS ARE NOT SIGNED, SEALED, OR
 DATED IN ACCORDANCE WITH FS 471.025 &
 FAC 61G15-23.002.PLEASE ALSO PROVIDE
 ALL LICENSE NUMBERS OF ENGINEERS.
  
 PROVISO:
 ADDITIONAL PERMITS REQUIRED FOR THE
 WALK-IN COOLER & HOOD.PLANS SUBMITTED
 WITH THE BUILDING PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-12 Cont ID  
Sent By pkrauss Date 2004-06-21 Time 07:43 Rev Time 1.55
Received By pkrauss Date 2004-06-21 Time 07:15 Sent To  
Notes
2004-06-21 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.PROVIDE MANUFACTURER SUBMITTAL AND
 INSTALLLATION INSTRUCTIONS FOR THE
 OVENS, AND WALK-IN COOLERS.
  
 PLEASE NOTE, ADDITIONAL PERMITS
 REQUIRED FOR THE HOOD, WALK-IN COOLERS
 AND FIRE SUPPRESSION.
  
 2.PLEASE CLARIFY HOOD, TYPE I OR TYPE
 II.
  
 3.INDICATE CLEARANCE TO COMBUSTIBLES.
  
 4.PLANS SHALL COMPLY WITH FS 471.025
 & FAC 61G15-23.002, PROVIDE NAMES AND
 LICENSE #'S.PLANS ARE TO BE SIGNED,
 SEALED, AND DATED.
  
 5.PLAN SHEET A2.2 #11 INDICATES NEW
 GAS FIRE PLACE FLUE.PLEASE CLARIFY
 HEIGHT REQUIREMENT.PLEASE NOTE
 PROXIMITY TO PARAPET WALL.TERMINATION
 SHALL COMPLY WITH 2001 FBC(F) 506.6.2.
  
 6.PLAN SHEET M2 HVAC PLAN NOTE #9, SEE
 3/M4.PLAN SHEET M4 DOES NOT INDICATE
 DETAIL 3.
  
 7.PROVIDE DETAILS FOR SECURING FLUES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 7 Status P Date 2005-11-30 Cont ID  
Sent By pschmitz Date 2005-11-30 Time 09:49 Rev Time 0.00
Received By pschmitz Date 2005-11-30 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status F Date 2005-04-23 Cont ID  
Sent By kstevens Date 2005-04-23 Time 17:15 Rev Time 1.00
Received By kstevens Date 2005-04-23 Time 17:15 Sent To  
Notes
2005-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) SHTS A6 & A6.1 - CHANGES TO THE
 EQUIPMENT SHOWN ON SHT A6, SHALL BE
 REFLECTED ON THE EQUIPMENT SCHEDULE SHT
 A6.1. SECTION 104.2.1.
 2) SHT P-1 LATEST REVISION SHOWN IS
 REVISION #5. THERE ARE OTHER CHANGES
 WITH NO REVISION NUMBER SHOWN. PLEASE
 SHOW ALL REVISIONS WITH CLOUDS AND
 REVISION NUMBERS. SECTION 104.2.1.
 3) SHT P-2 REVISION #7 WAS NOT FOUND.
 NUMEROUS UN-NUMBERED REVISIONS ON THE
 SHEET. SHOW REVISION NUMBER ON ALL
 CHANGES. SECTION 104.2.1.
 4) SHT P-3 NO REVISION #5 FOUND. SOME
 CLOUDS WITH OUT NUMBERS. - RED LINE
 CHANGES TO GAS RISER & GAS NOTES ON THE
 PERMITTED SET OF PLANS WERE NOT SHOWN ON
 THE REVISION. THESE RED LINE CHANGES
 SHALL BE INCORPORATED INTO THE LATEST
 REVISION TO MAKE THE INFORMATION REFLECT
 WHAT WAS APPROVED. MAKE CHANGES PRIOR TO
 RESUBMITTING REVISIONS. SECTIONS 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 5) SHTS P-4 & P-5 NO REVISIONS WERE
 NOTED ON THESE SHEETS. DO NOT SUBMIT
 SHEETS WITHOUT REVISIONS AS A REVISION.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-03-22 Cont ID  
Sent By kstevens Date 2005-03-22 Time 11:29 Rev Time 1.36
Received By kstevens Date 2005-03-22 Time 11:29 Sent To  
Notes
2005-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ENGINEER SHALL LEGIBLY THEIR NAME,
 ADDRESS, AND LICENSE NUMBER ON EACH
 SHEET. FAC 61G15-23.002 & FS 471.025
 2) SHT P3 INDICATES A REVISION WITH THE
 NUMBER 5 THAT WAS NOT ON THE PREVIOUS
 SHEET P3. PLEASE CLARIFY. SECTION
 104.2.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-11-23 Cont ID  
Sent By kstevens Date 2004-11-23 Time 16:01 Rev Time 1.75
Received By kstevens Date 2004-11-22 Time 17:25 Sent To  
Notes
2004-11-23 00:00:00SEPARATE GAS PERMIT REQUIRED. - PER
 CONVERSATION WITH ENGINEER 11-23-4 ALL
 PIPE WILL BE SCREW PIPE. NO WELD PIPE IN
 SYSTEM. - PER MANUF. SPECIFICATION SHEET
 THE ROOF TOP UNIT IS 129,600 BTU NOT
 100,000 BTU AS SHOWN. - TOLD ENGINEER
 AND ADVISED THAT NO PIPE SIZE CHANGES
 WERE REQUIRED AND THAT I WILL INDICATE
 THE CHANGE ON PLANS. HE AGREED. KSTEVENS
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-10-22 Cont ID  
Sent By kstevens Date 2004-10-22 Time 17:55 Rev Time 2.50
Received By kstevens Date 2004-10-21 Time 18:19 Sent To  
Notes
2004-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 PLUMBING
  
 1) STAMPED SHEETS FROM DBPR RESTURANT &
 HOTEL DIVISION ARE REQUIRED IN EACH SET
 OF PLANS WITH THE WORKSHEETS FROM DBPR
 INCLUDED. SECTION 101.4.7
 2) APPROVAL SHEET FROM RODNEY COMPO FOR
 THE GREASE INTECEPTOR REQUIRED. WASTE
 ORD. 2938-96
 3) WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 SHALL BE SHOWN ON THE
 WATER RISER DIAGRAM. (AT ICE MAKER, AND
 DISH WASHER). W.H.A.'S SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT IN THE CEILING. PDI-WH 201.
 4) GAS REQUIREMENTS: - THE DOUBLE RACK
 OVEN DOES NOT SHOW A GAS LISTING. UL
 LISTING DOES NOT ADDRESS GAS CONCERNS. -
 FIRE PLACE MANUF. SHEET SHOWS 17,OOO BTU
 MAXIMUM INPUT, BUT GAS RISER SHOWS
 30,000 BTU. PLEASE CLARIFY. - MANUF.
 SHEET FOR THE SF-1 UNIT ON THE ROOM &
 THE WATER HEATER ARE NOT SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-09-17 Cont ID  
Sent By kstevens Date 2004-09-17 Time 09:02 Rev Time 2.00
Received By kstevens Date 2004-09-17 Time 09:02 Sent To  
Notes
2004-09-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESS-
 ED, OR NOT ADDRESSED PROPERLY. THE SAME
 COMMENT NUMBER WILL BE USED FROM THE
 FIRST REVIEW TO AVOID CONFUSION.
 6) BOTY SETS OF PLANS SHALL BE SIGNED -
 SEALED & DATED BY THE ARCHITECT OR ENG-
 INEER AS REQUIRED BY FAC 61G1-16.003 OR
 61G15-23.002 & FS 481.2055 OR FS 471.025
 SOME SHEETS HAVE NOT BEEN SIGNED/SEALED/
 DATED.
 8) SHT P0 SEC 15000 PLUMBING (3)(D) AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 NOTES. PDI-WH 201. THIS NOTE HAS NOT
 BEEN DELETED.
 10) NO REPLY FROM RODNEY COMPO CONCERN-
 ING GREASE INTECEPTOR RECIEVED. WASTE
 ORD. 2938-96 (561) 837-4074.
 12) INFORMATION REQUIRED FOR GAS PERMIT
 B) SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED.
 14) SHT P3 WATER ISOMETRIC, WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS. - STILL SHOWN
 IN CEILING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-07 Cont ID  
Sent By kstevens Date 2004-07-06 Time 16:36 Rev Time 7.00
Received By kstevens Date 2004-07-06 Time 16:12 Sent To  
Notes
2004-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PLANS HAVE BEEN ROUTED TO THE DBPR
 HOTEL AND RESTURANT DIVISION. THE TWO
 PAGE WORKSHEETS RETURNED FROM DBPR SHALL
 BE ATTACHED TO EACH SET OF PLANS FOR RE-
 VIEW. SECTIONS 101.4.7 & 104.2.1.
 2) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER TABLES 1003.1 & 403.1. INDI-
 CATE IF SEATING IS FIXED OR NOT FIXED.
 3) SHT D1, ALL CAPPED AND/OR ABANDONED
 PLUMBING PIPING SHALL BE INSPECTED PRIOR
 TO COVERING. NO DEAD ENDS ALLOWED PER
 SECTION 704.5
 4) SHT A2.2 KEYED NOTES: #11 STATES FLUE
 TO BE A MINIMUM OF 2' FROM VERTICAL WALL
 BUT FUEL GAS SECTION 506.6.2 REQUIRES A
 MINIMUM OF 8' FROM VERTICAL WALLS. NOTE
 #11 ALSO STATES 1' ABOVE ROOF, BUT CODE
 SECTION 506.6.2 STATES THE VENT SHALL
 TERMINATE NOT LESS THAN 2 FEET HIGHER
 THAN ANY PORTION OF A BUILDING WITHIN 10
 FEET. SEE DETAIL 17 ON SHT A7.1
 5) SUBMIT MANUF. SPECIFICATION/INSTALL-
 ATION SHEETS FOR THE FIREPLACE AND THE
 VENTING SYSTEM.
 6) BOTH SETS OF PLANS SHALL BE SIGNED -
 SEALED & DATED BY THE ARCHITECT/ENGINEER
 OF RECORD. FAC 61G1-16.003/61G15-23.002
 FS 481.2055/471.025.
 7) SHT P0 DETAIL #2 FILTERS SHALL BE
 "NSF" COMPLIANT. SUBMIT MANUF. SPECIFIC-
 ATION SHEETS.
 8) SHT P0 SEC 15000 PLUMBING (3)(D) AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 NOTES. PDI-WH 201.
 9) P0 GENERAL NOTES #4 ADOPTED CODE IS
 FLA. BUILDING CODE - 2001 PLUMBING, NOT
 SBCCI-94 STANDARD PLUMBING CODE AS INDI-
 CATED. UPDATE GENERAL NOTES. SEC 104.2.1
 10) GREASE INTERCEPTOR SHALL BE SIZED BY
 RODNEY COMPO ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT HIM AT (561) 837-4074.
 WASTE ORD. #2938-96.
 11) RPZ BACKFLOW REQUIRED ON THE WATER
 SERVICE. SECTION 608.13.2
 12) FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 - SHT P2 PLAN NOTES #9 INDICATES 7" TO
 12" WATER COLUMN - CHARTS IN FBC-2001
 FUEL GAS ARE FOR 12" TO 14" WATER COLUMN
 WHICH IS 1/2 LB. PRESSURE. PLEASE VERIFY
 DELIVERY PRESSURE WITH FUEL PROVIDER.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 13) DISHWASHER (27A) SHALL DRAIN INTO
 THE SANITARY SYSTEM, NOT THE GREASE SYS-
 TEM. PER UTILITY DEPT.
 14) SHT P3 WATER ISOMETRIC, AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9 SHALL
 BE INSTALLED NEAR THE FIXTURES IN AN
 "EFFICTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 & MANUF. INSTALLATION INSTR.
 15) SHT P3 WATER ISOMETRIC, A SHUT OFF
 VALVE IS REQUIRED ON SUPPLY LINE TO HOSE
 BIBB. SECTION 606.2(2).
 15) SHTS P1 & P5. ITEMS NOT FOUND ON SHT
 P1 BUT SHOWN ON KITCHEN EQUIPMENT SCHED-
 ULE. ITEMS 13, 21C, 23, 23B, 54, 58, AND
 61. - ALSO CLAIRFY ITEM 72A SHOWN ON
 SCHEDULE AS DECK OVEN, BUT ON FLOOR PLAN
 IT IS IN THE FREEZER. PLEASE CORRELATE
 PLANS TO SCHEDULE.
 16) SHT P1, PLAN NOTES #6 INDICATES THAT
 FLOOR DRAINS ARE BEING USED FOR INDIRECT
 WASTE. THIS IS NOT APPROVED. FLOOR SINKS
 OR HUB DRAINS ARE REQUIRED FOR INDIRECT
 WASTE. FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. SECTIONS 802.3
 AND 802.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]