| Plan Review Stops For Permit 04060275 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-03-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-25 |
Time |
10:24 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-03-25 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2005-03-25 00:00:00 | TRUSS ENGINEERING |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2005-03-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-07 |
Time |
17:40 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-03-07 |
Time |
17:17 |
Sent To |
PC |
|
| Notes |
| 2005-03-07 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE STRUCTURAL ENGINEER OF RECORD | | | SHALL REVIEW THE DESIGN DOCUMENTS OF THE | | | DELEGATED ENGINEER, FAC61G15031.003. | | | | | | 2.) SEAL AND TITLE BLOCK REQUIRED FOR | | | THE TRUSS PLACEMENT PLAN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-11-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-11-13 |
Time |
12:50 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2004-11-13 |
Time |
12:28 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-09-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-09-21 |
Time |
08:07 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2004-09-21 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2004-09-21 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEE PREVIOUS LIST; PLEASE CORRECT | | | THE ADDRESS ON THE PERMIT APPLICATION. | | | | | | 2.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 FOR MORE | | | INFORMATION. | | | | | | 4.)SEE PREVIOUS LIST; PLEASE SIGN | | | THE OWNER/AGENT LINE OF THE ENERGY | | | CALC. | | | | | | 5.)PLEASE NOTE THAT ADDITIONAL PERMITS | | | REQUIRED FOR TRADES, SIGN, DUMPSTER. | | | | | | 6.)SEE PREVIOUS LIST, ITEM #8, PROVIDE | | | A LICENSE NUMBER FOR LAND DESIGN SOUTH; | | | SIGN, SEAL AND DATE.THE RESPONSE | | | LETTER INDICATED THAT THIS SHEET WAS | | | REMOVED, BUT IT IS STILL IN THE PLAN. | | | IF YOU REMOVE THIS SHEET, A NEW SITE | | | PLAN SHOWING HORIZONTAL CONTROL LINES | | | MUST BE SUBMITTED.PLEASE ALSO HAVE | | | THE DESIGNER OF RECORD REVIEW THE SITE | | | PLAN PREPARED BY LAND DESIGN SOUTH | | | SHOULD YOU CHOOSE TO INCLUDE THIS AS | | | THE SITE PLAN OF RECORD.SEE ATTACHED | | | FS553.80(2)(B).SITE PLAN REQUIRED | | | FBC104.3.1.1(1). | | | | | | 7.)PHOTOCOPIES OF ENGINEERING (SOILS | | | REPORT) ARE NOT ACCEPTABLE; SEE FAC | | | 61G15-23.002. | | | | | | 8.)THE PRODUCT APPROVAL FOR THE | | | STOREFRONT GLASS APPEARS TO BE CODE | | | COMPLIANT BUT IS ILLEGIBLE.PLEASE | | | PROVIDE LEGIBLE COPIES.ALSO PROVIDE | | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | AS REQUIRED BY FAC9B72.THE NOAS ARE | | | AVAILABLE AT WWW.MIAMIDADE.GOV (FIND A | | | DEPARTMENT, BUILDING CODE COMPLIANCE, | | | PRODUCT SEARCH) AND THE FLORIDA STATE | | | PRODUCT APPROVAL MAY BE AVAILABLE AT | | | WWW.FLORIDABUILDING.ORG (PRODUCT | | | APPROVAL, PRODUCT SEARCH).SHOULD YOU | | | HAVE ANY QUESTIONS ABOUT THE PRODUCT | | | APPROVAL REQUIREMENTS (TEST REPORT AND | | | FLORIDA OR LOCAL PRODUCT APPROVAL) | | | PLEASE CONTACT ME. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-07-07 |
Time |
12:25 |
Rev Time |
5.00 |
| Received By |
shill |
Date |
2004-07-07 |
Time |
12:25 |
Sent To |
|
|
| Notes |
| 2004-07-07 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PLEASE NOTE THAT THE ADDRESS ON THE | | | PERMIT APPLICATION DOES NOT MATCH OUR | | | RECORDS.PLEASE CONTACT ME IF YOU | | | NEED FURTHER INFORMATION OR WOULD LIKE | | | TO CLARIFY. | | | | | | 2.)PROVIDE PROOF OF OWNERSHIP.OUR | | | RECORDS AND THE PROPERTY APPRAISERS | | | SHOWS LENNAR LAND PARTNERS AS THE OWNER. | | | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 4.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION. | | | | | | 5.)SEPARATE PERMITS REQUIRED. | | | | | | 6.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC FBC13-400. | | | | | | 7.)SEPARATE PERMITS REQUIRED FOR | | | THE SIGN, DUMPSTER, SUBCONTRACTORS. | | | | | | 8.)PROVIDE LICENSE NUMBER FOR LAND | | | DESIGN SOUTH; SIGN, SEAL AND DATE. | | | (SITE PLAN) | | | | | | 9.)PROVIDE A SOILS INVESTIGATION | | | REPORT. | | | | | | 10.) ADDITIONAL FEES DUE (RADON, BALANCE | | | OF PERMIT FEE). | | | | | | 11.) PROVIDE A COPY OF THE SURVEY FOR | | | THIS PROPERTY. | | | | | | 12.) LIGHT POLE (PH-1) TO MEET 140 MPH | | | (3 SECOND GUST), NOT 110 (NOTE 1, PH1). | | | | | | 13.) THE SQUARE FOOTAGE IS SHOWN AS | | | 3990 ON THE ENERGY CALCS, 3800 ON THE | | | SITE PLAN, 3975 WITH AN OCCUPANT LOAD | | | OF 39 ON THE INDEX SHEET, AND AND 4279 | | | WITH AN OCCUPANT LOAD OF 43 ON LS1. | | | PLEASE MAKE ALL CONSISTENT WITH THE | | | CORRECT AREA. | | | | | | 14.)NOTE 10, A9.1 IS MISSING (MEN | | | ELEVATION D). | | | | | | 15.)A6.1 SHOWS ASPHALT SHINGLES, IS | | | THIS CORRECT?IF NOT, CHECK ALL | | | DETAILS. | | | | | | 16.)PROVIDE PRODUCT APPROVALS FOR: | | | STOREFRONT GLASS, IMPACT | | | ROOF (TILE AND SHINGLES IF APPLICABLE) | | | | | | 17.) PLEASE PROVIDE TRUSS LOAD | | | INFORMATION TO VERIFY CONNECTORS. | | | FBC1606. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-09-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-09-20 |
Time |
16:35 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-09-20 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-06-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-16 |
Time |
10:37 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2004-06-16 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2004-06-16 00:00:00 | ********** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE PH-1 AND E-SP. | | | PLEASE CORRELATE INFORMATION FOR WIND | | | LOADS. PLEASE ALSO PROVIDE INFORMATION/ | | | WIND LOADS FOR THESE AT THIS TIME. | | | CALCS ARE REQUIRED TO BE SIGNED, DATED | | | AND SEALED. FS 471.025 | | | PLEASE ALSO SEE PH-1 MENTIONS ONE OF | | | THE "HANDHOLE" BELOW GRADE? PLEASE SEE | | | ANY WIRING REQUIRING TO BE ACCESSED | | | SHALL NOT BE BELOW GRADE AS IT IS SHOWN | | | BEING INCASED IN CONCRETE? | | | PLEASE ALSO SEE PLANS MENTIONS TO HAVE | | | POWER ALSO CONNECTED TO EM POWER FROM | | | PUBLIX GENERATOR SYSTEM. THIS IS NOT | | | PERMITTED. POLES MAY BE FED FROM AN | | | EMERGANCY SYSTEM PROVIDED AT BANK BUT | | | NOT FROM SEPARTE SERVICE FROM PUBLIX. | | | PLANS AS SHOWN HAS THE POTENIAL OF | | | POWER COMING INTO POLES FROM TWO | | | SEPARATE SERVICES AT THE SAME TIME. | | | PLEASE SEE NOTES ON THIS SAME SHEET | | | ONLY GO THROUGH NOTE#7, NOTES 8,9 AND 10 | | | SEEM TO BE MISSING AS SHOWN ON DETAIL. | | | | | | 2)NOTE: PLEASE VERIFY IF MCB SHOWN AS | | | SHUNT TRIP HAS THE REQUIRED MANUAL MEANS | | | OF DISCONNECT PER 230.76/230.79 | | | | | | 3)NOTE: PLEASE VERIFY NOTE #6 TO RISER, | | | MENTIONS MORE CONDUCTORS NEEDED AND | | | NOT CLEAR WHAT THESE "EXTRA" CONDUCTORS | | | ARE FOR? | | | | | | 4)NOTE: PLEASE SEE "GROUNDING GEN NOTE" | | | MENTIONS GROUNDING ELECTRODE CONDUCTOR | | | IS TO BE CONTINUOUS AS REQUIRED UNDER | | | NEC 250.64C, HOWEVER PLANS SHOW GEC | | | GOING TO GROUND BAR SEPARATELY?? | | | PLEASE CLARIFY. | | | | | | 5)NOTE: PLEASE SEE A COUPLE OF LOCATIONS | | | ON PLANS WHERE THE CODES REFERENCED ARE | | | FROM THE 96 NEC. PLEASE SEE WE ARE UNDER | | | THE 2002 NEC. | | | | | | 6)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | FOR INDIVIDUAL PANELS. 215.5/220 | | | UNABLE TO VERIFY AT THIS TIME. | | | | | | 7)NOTE: PLEASE INCLUDE ALL LICENSE #'S | | | ON TITLE BLOCK AS REQUIREDUNDER | | | FAC 61G15-23.002, FS 471.023. | | | PLEASE SEE THIS INFORMATION IS REQUIRED | | | FOR ALL SHEETS, WHEATHER OR NOT COMMENT | | | IS MADE BY OTHER REVIEWERS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | ONE SET IF OLD/VOIDED SHEETS MAY BE | | | SENT BACK IN FOR REFERENCE ONLY. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2004-08-27 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-08-27 |
Time |
14:58 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2004-08-27 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2004-06-08 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-06-08 |
Time |
15:30 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2004-06-08 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2004-06-08 00:00:00 | FAILED: | | | 1. CIVIL PLANS MUST BE REVIEWEED AND | | | APPROVED FOR ALL THE CONNECTIONS FOR | | | SERVICES AND FOR THE LOCATION OF METERS, | | | BACKFLOWS, ETC. ATT: MANNY GONZALEZ | | | 2. ALL PARKING STALLS MUST BE PAINTED | | | WITH DOUBLE 4" WIDE WHITE STRIPES, | | | PLEASE REVISED DETAILS. | | | 3. PLEASE SUBMIT PERVIOUS AND IMPERVIOUS | | | CALCULATIONS FOR THE ENTIRE SITE, SIGNED | | | AND SEALED. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-10-05 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-10-05 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-10-05 |
Time |
11:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-06-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-06-10 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-06-10 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2004-06-10 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | | IN PROJECT BOX. SHOULD READ NFPA 101, | | | LIFE SAFETY CODE 2000 EDITION. | | | | | | 2) THE PROPOSED FIRE HYDRANT SHOULD | | | BE LOCATED CLOSER TO THE DRIVEWAY | | | OPENING. THE LOCATION SHOWN WOULD | | | BE DIFFICULT TO USE. | | | | | | 3) TWO DIFFERENT OCCUPANT LOADS ARE | | | REFLECTED IN PLANS. PLEASE CLARIFY. | | | | | | 4) WET FIRE HYDRANTS ARE REQUIRED | | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | | | | 5) SUITABLE ROADS ARE TO BE PROVIDED | | | DURING CONSTRUCTION. | | | | | | 6) SINCE THE BUILDING WILL NOT BE | | | FIRE SPRINKLER PROTECTED, THE | | | ELECTRICAL ROOM AND MECHANICAL ROOM | | | SHALL BE AT LEAST ONE HOUR FIRE | | | RATED. | | | | | | 7) THE BUILDING ADDRESS IS REQUIRED. | | | A MINIMUM OF 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 8) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING. | | | | | | 9) PLEASE INDICATE FIRE EXTINGUISHER | | | LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-03-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-25 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-25 |
Time |
08:20 |
Sent To |
B |
|
| Notes |
| 2005-03-25 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-03-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-03 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-03 |
Time |
11:24 |
Sent To |
B |
|
| Notes |
| 2005-03-03 00:00:00 | TO "SHILL DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-01 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-01 |
Time |
15:47 |
Sent To |
B |
|
| Notes |
| 2004-11-01 00:00:00 | TO SH DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-08-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-25 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-25 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2004-08-25 00:00:00 | TO COMM BD#39 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-07-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-07-08 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2004-06-07 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2004-06-07 00:00:00 | TO COMM BD#25 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-09-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-09-22 |
Time |
07:35 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-09-22 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2004-09-22 00:00:00 | PROVISO: | | | PLEASE NOTE THE LOCATION OF THE FRESH | | | AIR PLENUM IN RELATION TO THE CONDENSING | | | UNITS.FRESH AIR INTAKE SHOULD BE | | | LOCATED WHERE IT CAN RECIRCULATE HOT | | | AIR DISTRIBUTED BY THE CONDENSING UNITS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-06-18 |
Time |
10:15 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-06-18 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2004-06-18 00:00:00 | DENIED: | | | 1.SYSTEMS WITH THE DESIGN CAPACITY | | | GREATER THAN 2,000 CFM SHALL HAVE DUCT | | | SMOKE DETECTORS IN THE SUPPLY AIR DUCT. | | | | | | 2.FAN SHUTDOWN SHALL HAVE NOTIFICATION | | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS PER NFPA 90A 6.4.4.3 (1). | | | | | | 3.PER COMMENTS BY ASST FIRE MARSHAL, | | | MIKE CARSILLO MECHANICAL ROOM SHALL BE | | | 1 HR FIRE RATING.FIRE DAMPERS WILL BE | | | REQUIRED. | | | | | | 4.SEE COMMENT #7 BY DEWEY PALMER, | | | ELECTRICAL PLAN REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-10-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-07 |
Time |
09:59 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-10-07 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-06-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-21 |
Time |
10:36 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2004-06-21 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2004-06-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHTS 5 0F 9, IRR 1, AND IRR 3. SHEET | | | 5 OF 9 SHOWS WATER METERS AND BACKFLOWS | | | FOR IRRIGATION, BUT SHEETS IRR. 1 & 3 | | | INDICATE 2" WELLS FOR IRRIGATION WATER. | | | PLEASE CLARIFY AND CORRELATE PLANS. | | | WELL PERMITS SHALL BE ISSUED BY PALM BCH | | | HEALTH DEPT. SECTION 104.2.1 | | | 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR | | | THE URINAL. SECTION 11-4.18.3 | | | 3) SHT P-2 CONDENSATE LINE SHALL HAVE A | | | RELIEF VENT (GOOSE NECK) INSTALLED AS | | | THE CONDENSATE LINE EXITS THE BLDG. | | | SECTION 104.2.1 | | | 4) SHT P-3 WATER PIPING NOTES: #4, DI- | | | ELECTRIC UNIONS NOT APPROVED FOR WATER | | | DISTRIBUTION PIPING. DELETE REFERENCE OR | | | MODIFY NOTE TO READ "DIELECTRIC COUPLING | | | SECTION 104.2.1 | | | 5) FOLLOWING INFORMATION FOR ENGINEER: | | | A PROFESSIONAL ENGINEER SHALL SIGN HIS | | | NAME AND AFFIX HIS SEAL TO ALL PLANS, | | | SPECIFICATIONS, REPORTS AND FINAL BID | | | DOCUMENTS PROVIDED TO THE OWNER OR THE | | | OWNER'S REPRESENTATIVE, OR OTHER DOCU- | | | MENTS PREPARED OR ISSUED BY SAID REGIS- | | | TRANT AND BEING FILED FOR PUBLIC RECORD. | | | THE DATE THAT THE SIGNATURE AND SEAL IS | | | AFFIXED AS PROVIDED HEREIN SHALL BE EN- | | | TERED ON SAID PLANS, SPECIFICATIONS, RE- | | | PORTS, OR OTHER DOCUMENTS IMMEDIATELY | | | UNDER THE SIGNATURE OF THE PROFESSIONAL | | | ENGINEER, FAC 61G15-23.002(1) | | | FS 471.025 - INITIALS ARE NOT APPROVED | | | FULL SIGNATURE REQUIRED, MINIMUM FIRST | | | AND LAST NAME REQUIRED. | | | EACH SHEET OF PLANS AND PRINTS WHICH | | | MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 471 SHALL BE SEALED, SIGNED AND | | | DATED BY THE PROFESSIONAL ENGINEER IN | | | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) | | | FS 471.025 | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | | WILL SATISFY THIS REQUIREMENT. FAC | | | 61G15-23.002(2) - FS 471.025 | | | -- SEAL SHOWS FIST NAME DAVOOD, BUT THE | | | TITLE BLOCK SHOWS FIRST NAME AS DAVID. | | | CORRELATE NAME ON SEAL AND NAME ON TITLE | | | BLOCK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-08-30 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2004-08-30 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2004-08-30 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2004-06-25 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2004-06-25 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2004-06-25 00:00:00 | 6/25/04 - ***FAILED*** | | | | | | 1) PLEASE PROVIDE DETAILS OF LIGHT | | | FIXTURES LOCATED UNDERNEATH THE CANOPY. | | | | | | 2) ALL LIGHTS LOCATED UNDER THE CANOPY | | | SHALL BE RECESSED TO REDUCE GLARE. | | | | | | 3) ALL LIGHT POLE FIXTURES SHALL BE | | | SHIELDED TO REFLECT LIGHT/GLARE AWAY | | | FROM ADJACENT RESIDENTIAL DEVELOPMENT. | | | | | | QUESTIONS, PLEASE CONTACT JOHN ROACH, PL | | | ANNER (561)659-8031. |
|
|