Plan Review Details - Permit 04060275
Plan Review Stops For Permit 04060275
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-25 Cont ID  
Sent By shill Date 2005-03-25 Time 10:24 Rev Time 0.50
Received By shill Date 2005-03-25 Time 10:24 Sent To  
Notes
2005-03-25 00:00:00TRUSS ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-03-07 Cont ID  
Sent By shill Date 2005-03-07 Time 17:40 Rev Time 1.00
Received By shill Date 2005-03-07 Time 17:17 Sent To PC
Notes
2005-03-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE STRUCTURAL ENGINEER OF RECORD
 SHALL REVIEW THE DESIGN DOCUMENTS OF THE
 DELEGATED ENGINEER, FAC61G15031.003.
  
 2.) SEAL AND TITLE BLOCK REQUIRED FOR
 THE TRUSS PLACEMENT PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-13 Cont ID  
Sent By shill Date 2004-11-13 Time 12:50 Rev Time 2.00
Received By shill Date 2004-11-13 Time 12:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-09-21 Cont ID  
Sent By shill Date 2004-09-21 Time 08:07 Rev Time 2.00
Received By shill Date 2004-09-21 Time 08:07 Sent To  
Notes
2004-09-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST; PLEASE CORRECT
 THE ADDRESS ON THE PERMIT APPLICATION.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 4.)SEE PREVIOUS LIST; PLEASE SIGN
 THE OWNER/AGENT LINE OF THE ENERGY
 CALC.
  
 5.)PLEASE NOTE THAT ADDITIONAL PERMITS
 REQUIRED FOR TRADES, SIGN, DUMPSTER.
  
 6.)SEE PREVIOUS LIST, ITEM #8, PROVIDE
 A LICENSE NUMBER FOR LAND DESIGN SOUTH;
 SIGN, SEAL AND DATE.THE RESPONSE
 LETTER INDICATED THAT THIS SHEET WAS
 REMOVED, BUT IT IS STILL IN THE PLAN.
 IF YOU REMOVE THIS SHEET, A NEW SITE
 PLAN SHOWING HORIZONTAL CONTROL LINES
 MUST BE SUBMITTED.PLEASE ALSO HAVE
 THE DESIGNER OF RECORD REVIEW THE SITE
 PLAN PREPARED BY LAND DESIGN SOUTH
 SHOULD YOU CHOOSE TO INCLUDE THIS AS
 THE SITE PLAN OF RECORD.SEE ATTACHED
 FS553.80(2)(B).SITE PLAN REQUIRED
 FBC104.3.1.1(1).
  
 7.)PHOTOCOPIES OF ENGINEERING (SOILS
 REPORT) ARE NOT ACCEPTABLE; SEE FAC
 61G15-23.002.
  
 8.)THE PRODUCT APPROVAL FOR THE
 STOREFRONT GLASS APPEARS TO BE CODE
 COMPLIANT BUT IS ILLEGIBLE.PLEASE
 PROVIDE LEGIBLE COPIES.ALSO PROVIDE
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 AS REQUIRED BY FAC9B72.THE NOAS ARE
 AVAILABLE AT WWW.MIAMIDADE.GOV (FIND A
 DEPARTMENT, BUILDING CODE COMPLIANCE,
 PRODUCT SEARCH) AND THE FLORIDA STATE
 PRODUCT APPROVAL MAY BE AVAILABLE AT
 WWW.FLORIDABUILDING.ORG (PRODUCT
 APPROVAL, PRODUCT SEARCH).SHOULD YOU
 HAVE ANY QUESTIONS ABOUT THE PRODUCT
 APPROVAL REQUIREMENTS (TEST REPORT AND
 FLORIDA OR LOCAL PRODUCT APPROVAL)
 PLEASE CONTACT ME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-08 Cont ID  
Sent By shill Date 2004-07-07 Time 12:25 Rev Time 5.00
Received By shill Date 2004-07-07 Time 12:25 Sent To  
Notes
2004-07-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE NOTE THAT THE ADDRESS ON THE
 PERMIT APPLICATION DOES NOT MATCH OUR
 RECORDS.PLEASE CONTACT ME IF YOU
 NEED FURTHER INFORMATION OR WOULD LIKE
 TO CLARIFY.
  
 2.)PROVIDE PROOF OF OWNERSHIP.OUR
 RECORDS AND THE PROPERTY APPRAISERS
 SHOWS LENNAR LAND PARTNERS AS THE OWNER.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 5.)SEPARATE PERMITS REQUIRED.
  
 6.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-400.
  
 7.)SEPARATE PERMITS REQUIRED FOR
 THE SIGN, DUMPSTER, SUBCONTRACTORS.
  
 8.)PROVIDE LICENSE NUMBER FOR LAND
 DESIGN SOUTH; SIGN, SEAL AND DATE.
 (SITE PLAN)
  
 9.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 10.) ADDITIONAL FEES DUE (RADON, BALANCE
 OF PERMIT FEE).
  
 11.) PROVIDE A COPY OF THE SURVEY FOR
 THIS PROPERTY.
  
 12.) LIGHT POLE (PH-1) TO MEET 140 MPH
 (3 SECOND GUST), NOT 110 (NOTE 1, PH1).
  
 13.) THE SQUARE FOOTAGE IS SHOWN AS
 3990 ON THE ENERGY CALCS, 3800 ON THE
 SITE PLAN, 3975 WITH AN OCCUPANT LOAD
 OF 39 ON THE INDEX SHEET, AND AND 4279
 WITH AN OCCUPANT LOAD OF 43 ON LS1.
 PLEASE MAKE ALL CONSISTENT WITH THE
 CORRECT AREA.
  
 14.)NOTE 10, A9.1 IS MISSING (MEN
 ELEVATION D).
  
 15.)A6.1 SHOWS ASPHALT SHINGLES, IS
 THIS CORRECT?IF NOT, CHECK ALL
 DETAILS.
  
 16.)PROVIDE PRODUCT APPROVALS FOR:
 STOREFRONT GLASS, IMPACT
 ROOF (TILE AND SHINGLES IF APPLICABLE)
  
 17.) PLEASE PROVIDE TRUSS LOAD
 INFORMATION TO VERIFY CONNECTORS.
 FBC1606.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-20 Cont ID  
Sent By dpalmer Date 2004-09-20 Time 16:35 Rev Time 1.00
Received By dpalmer Date 2004-09-20 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-16 Cont ID  
Sent By dpalmer Date 2004-06-16 Time 10:37 Rev Time 2.00
Received By dpalmer Date 2004-06-16 Time 08:51 Sent To  
Notes
2004-06-16 00:00:00********** UNSAT ****************
  
 1)NOTE: PLEASE SEE PH-1 AND E-SP.
 PLEASE CORRELATE INFORMATION FOR WIND
 LOADS. PLEASE ALSO PROVIDE INFORMATION/
 WIND LOADS FOR THESE AT THIS TIME.
 CALCS ARE REQUIRED TO BE SIGNED, DATED
 AND SEALED. FS 471.025
 PLEASE ALSO SEE PH-1 MENTIONS ONE OF
 THE "HANDHOLE" BELOW GRADE? PLEASE SEE
 ANY WIRING REQUIRING TO BE ACCESSED
 SHALL NOT BE BELOW GRADE AS IT IS SHOWN
 BEING INCASED IN CONCRETE?
 PLEASE ALSO SEE PLANS MENTIONS TO HAVE
 POWER ALSO CONNECTED TO EM POWER FROM
 PUBLIX GENERATOR SYSTEM. THIS IS NOT
 PERMITTED. POLES MAY BE FED FROM AN
 EMERGANCY SYSTEM PROVIDED AT BANK BUT
 NOT FROM SEPARTE SERVICE FROM PUBLIX.
 PLANS AS SHOWN HAS THE POTENIAL OF
 POWER COMING INTO POLES FROM TWO
 SEPARATE SERVICES AT THE SAME TIME.
 PLEASE SEE NOTES ON THIS SAME SHEET
 ONLY GO THROUGH NOTE#7, NOTES 8,9 AND 10
 SEEM TO BE MISSING AS SHOWN ON DETAIL.
  
 2)NOTE: PLEASE VERIFY IF MCB SHOWN AS
 SHUNT TRIP HAS THE REQUIRED MANUAL MEANS
 OF DISCONNECT PER 230.76/230.79
  
 3)NOTE: PLEASE VERIFY NOTE #6 TO RISER,
 MENTIONS MORE CONDUCTORS NEEDED AND
 NOT CLEAR WHAT THESE "EXTRA" CONDUCTORS
 ARE FOR?
  
 4)NOTE: PLEASE SEE "GROUNDING GEN NOTE"
 MENTIONS GROUNDING ELECTRODE CONDUCTOR
 IS TO BE CONTINUOUS AS REQUIRED UNDER
 NEC 250.64C, HOWEVER PLANS SHOW GEC
 GOING TO GROUND BAR SEPARATELY??
 PLEASE CLARIFY.
  
 5)NOTE: PLEASE SEE A COUPLE OF LOCATIONS
 ON PLANS WHERE THE CODES REFERENCED ARE
 FROM THE 96 NEC. PLEASE SEE WE ARE UNDER
 THE 2002 NEC.
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR INDIVIDUAL PANELS. 215.5/220
 UNABLE TO VERIFY AT THIS TIME.
  
 7)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK AS REQUIREDUNDER
 FAC 61G15-23.002, FS 471.023.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 FOR ALL SHEETS, WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWERS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET IF OLD/VOIDED SHEETS MAY BE
 SENT BACK IN FOR REFERENCE ONLY.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-08-27 Cont ID  
Sent By mamini Date 2004-08-27 Time 14:58 Rev Time 1.00
Received By mamini Date 2004-08-27 Time 14:58 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-06-08 Cont ID  
Sent By mamini Date 2004-06-08 Time 15:30 Rev Time 0.50
Received By mamini Date 2004-06-08 Time 15:30 Sent To  
Notes
2004-06-08 00:00:00FAILED:
 1. CIVIL PLANS MUST BE REVIEWEED AND
 APPROVED FOR ALL THE CONNECTIONS FOR
 SERVICES AND FOR THE LOCATION OF METERS,
 BACKFLOWS, ETC. ATT: MANNY GONZALEZ
 2. ALL PARKING STALLS MUST BE PAINTED
 WITH DOUBLE 4" WIDE WHITE STRIPES,
 PLEASE REVISED DETAILS.
 3. PLEASE SUBMIT PERVIOUS AND IMPERVIOUS
 CALCULATIONS FOR THE ENTIRE SITE, SIGNED
 AND SEALED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-05 Cont ID  
Sent By nmccray Date 2004-10-05 Time 11:44 Rev Time 0.00
Received By nmccray Date 2004-10-05 Time 11:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-10 Cont ID  
Sent By mcarsill Date 2004-06-10 Time 16:07 Rev Time 0.00
Received By mcarsill Date 2004-06-10 Time 16:07 Sent To  
Notes
2004-06-10 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 IN PROJECT BOX. SHOULD READ NFPA 101,
 LIFE SAFETY CODE 2000 EDITION.
  
 2) THE PROPOSED FIRE HYDRANT SHOULD
 BE LOCATED CLOSER TO THE DRIVEWAY
 OPENING. THE LOCATION SHOWN WOULD
 BE DIFFICULT TO USE.
  
 3) TWO DIFFERENT OCCUPANT LOADS ARE
 REFLECTED IN PLANS. PLEASE CLARIFY.
  
 4) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 5) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION.
  
 6) SINCE THE BUILDING WILL NOT BE
 FIRE SPRINKLER PROTECTED, THE
 ELECTRICAL ROOM AND MECHANICAL ROOM
 SHALL BE AT LEAST ONE HOUR FIRE
 RATED.
  
 7) THE BUILDING ADDRESS IS REQUIRED.
 A MINIMUM OF 6" HIGH NUMBERS ARE
 REQUIRED.
  
 8) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 9) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-25 Cont ID  
Sent By adarroug Date 2005-03-25 Time 08:20 Rev Time 0.00
Received By adarroug Date 2005-03-25 Time 08:20 Sent To B
Notes
2005-03-25 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-03 Cont ID  
Sent By adarroug Date 2005-03-03 Time 11:24 Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 11:24 Sent To B
Notes
2005-03-03 00:00:00TO "SHILL DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 15:47 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 15:47 Sent To B
Notes
2004-11-01 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 15:53 Sent To  
Notes
2004-08-25 00:00:00TO COMM BD#39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-08 Cont ID  
Sent By shill Date 2004-07-08 Time 11:10 Rev Time 0.00
Received By shill Date 2004-06-07 Time 14:24 Sent To  
Notes
2004-06-07 00:00:00TO COMM BD#25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-09-22 Cont ID  
Sent By pkrauss Date 2004-09-22 Time 07:35 Rev Time 0.40
Received By pkrauss Date 2004-09-22 Time 07:15 Sent To  
Notes
2004-09-22 00:00:00PROVISO:
 PLEASE NOTE THE LOCATION OF THE FRESH
 AIR PLENUM IN RELATION TO THE CONDENSING
 UNITS.FRESH AIR INTAKE SHOULD BE
 LOCATED WHERE IT CAN RECIRCULATE HOT
 AIR DISTRIBUTED BY THE CONDENSING UNITS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-18 Cont ID  
Sent By pkrauss Date 2004-06-18 Time 10:15 Rev Time 0.55
Received By pkrauss Date 2004-06-18 Time 08:59 Sent To  
Notes
2004-06-18 00:00:00DENIED:
 1.SYSTEMS WITH THE DESIGN CAPACITY
 GREATER THAN 2,000 CFM SHALL HAVE DUCT
 SMOKE DETECTORS IN THE SUPPLY AIR DUCT.
  
 2.FAN SHUTDOWN SHALL HAVE NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS PER NFPA 90A 6.4.4.3 (1).
  
 3.PER COMMENTS BY ASST FIRE MARSHAL,
 MIKE CARSILLO MECHANICAL ROOM SHALL BE
 1 HR FIRE RATING.FIRE DAMPERS WILL BE
 REQUIRED.
  
 4.SEE COMMENT #7 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-07 Cont ID  
Sent By kstevens Date 2004-10-07 Time 09:59 Rev Time 0.50
Received By kstevens Date 2004-10-07 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-21 Cont ID  
Sent By kstevens Date 2004-06-21 Time 10:36 Rev Time 2.00
Received By kstevens Date 2004-06-21 Time 10:36 Sent To  
Notes
2004-06-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS 5 0F 9, IRR 1, AND IRR 3. SHEET
 5 OF 9 SHOWS WATER METERS AND BACKFLOWS
 FOR IRRIGATION, BUT SHEETS IRR. 1 & 3
 INDICATE 2" WELLS FOR IRRIGATION WATER.
 PLEASE CLARIFY AND CORRELATE PLANS.
 WELL PERMITS SHALL BE ISSUED BY PALM BCH
 HEALTH DEPT. SECTION 104.2.1
 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 THE URINAL. SECTION 11-4.18.3
 3) SHT P-2 CONDENSATE LINE SHALL HAVE A
 RELIEF VENT (GOOSE NECK) INSTALLED AS
 THE CONDENSATE LINE EXITS THE BLDG.
 SECTION 104.2.1
 4) SHT P-3 WATER PIPING NOTES: #4, DI-
 ELECTRIC UNIONS NOT APPROVED FOR WATER
 DISTRIBUTION PIPING. DELETE REFERENCE OR
 MODIFY NOTE TO READ "DIELECTRIC COUPLING
 SECTION 104.2.1
 5) FOLLOWING INFORMATION FOR ENGINEER:
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - INITIALS ARE NOT APPROVED
 FULL SIGNATURE REQUIRED, MINIMUM FIRST
 AND LAST NAME REQUIRED.
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 -- SEAL SHOWS FIST NAME DAVOOD, BUT THE
 TITLE BLOCK SHOWS FIRST NAME AS DAVID.
 CORRELATE NAME ON SEAL AND NAME ON TITLE
 BLOCK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-08-30 Cont ID  
Sent By jroach Date 2004-08-30 Time 10:57 Rev Time 0.00
Received By jroach Date 2004-08-30 Time 10:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-25 Cont ID  
Sent By jroach Date 2004-06-25 Time 16:01 Rev Time 0.00
Received By jroach Date 2004-06-25 Time 16:01 Sent To  
Notes
2004-06-25 00:00:006/25/04 - ***FAILED***
  
 1) PLEASE PROVIDE DETAILS OF LIGHT
 FIXTURES LOCATED UNDERNEATH THE CANOPY.
  
 2) ALL LIGHTS LOCATED UNDER THE CANOPY
 SHALL BE RECESSED TO REDUCE GLARE.
  
 3) ALL LIGHT POLE FIXTURES SHALL BE
 SHIELDED TO REFLECT LIGHT/GLARE AWAY
 FROM ADJACENT RESIDENTIAL DEVELOPMENT.
  
 QUESTIONS, PLEASE CONTACT JOHN ROACH, PL
 ANNER (561)659-8031.