Plan Review Details - Permit 04060240
Plan Review Stops For Permit 04060240
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-07-30 Cont ID  
Sent By mjacobs Date 2004-07-30 Time 07:45 Rev Time 0.50
Received By mjacobs Date 2004-07-30 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-07-15 Cont ID  
Sent By csiegber Date 2004-07-19 Time 09:41 Rev Time 1.00
Received By mjacobs Date 2004-06-23 Time 13:34 Sent To  
Notes
2004-07-15 00:00:00BUILDING PLAN REVIEW
 PERMIT:04060240
 ADD: 400 N FLAGLER DR.
 CONT: SHORE & COUNTY CONST. INC
 TEL: (561)793-6967
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED
  
 2)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL STATE STAT: 61G16.003 ARCHITECTS
  
 3) WALL SHALL BE NONCOMBUSTIBLE. PLEASE
 SEE FBC SEC. 609.2.1 ALSO ADDITIONAL
 INFORMATION NEEDED ON CONSTRUCTION OF
 WALLS AND SOFFITS.
  
 4) PLEASE SUBMIT MORE INFO. IN REFERENCE
 TO TOP OF WALL AND SOFFIT, ATTATCHMENTS,
 AND FRAMING SPACING.
  
 5) SUBMIT ONFORMATION FOR TYPE OF FLOOR
 TILES THAT WILL BE USED. ALSO SPECIFY
 TYPE OF TILE ADDHESIVE.
  
 6)FL BLDG CODE 2405.2HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION.
 SWING DOOR REQUIRES TEMPERED GLASS.
  
 7) TRAY CEILING IS THIS NEW OR EXISTING?
 IF NEW SUPPLY DETAILS.
  
 8) NOTE: NO WORK SHOWN ON BALCONY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 MYRON JACOBS (561) 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-15 Cont ID  
Sent By mjacobs Date 2004-07-15 Time 13:12 Rev Time 3.00
Received By mjacobs Date 2004-07-15 Time 13:10 Sent To  
Notes
2004-07-15 00:00:00BUILDING PLAN REVIEW
 PERMIT:04060240
 ADD: 400 N. FLAGLER DR.
 CONT: SHORE & COUNTY CONST. INC.
 TEL: (561)793-6967
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 2ND REVIEW
 ACTION: DENIED
  
 1) PLEASE ADDRESS NOTES #4-#5 AND #7
 IN REFERENCE TO FRAMING SPACING BOTH
 SOFFITS AND WALLS,ATTATCHMENTS AND
 INFORMATION ON FLOOR AND TRAY CEILING.
  
 2) IF MARBLE TILES ARE THICKER THAN 3/8"
 AND INSTALLED USING DRY PACK, A
 CERTIFIED ENGINEER HAS TO APPROVE THE
 FLOOR DESIGN DUE TO LOADING BEARING
 ISSUES. FBC. SEC.1603.1
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 MYRON JACOBS: (561) 805-6726

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-10-26 Cont ID  
Sent By btrobaug Date 2004-10-26 Time 08:28 Rev Time 0.33
Received By btrobaug Date 2004-10-26 Time 08:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-25 Time 14:26 Rev Time 0.50
Received By dpalmer Date 2004-10-20 Time 17:17 Sent To  
Notes
2004-10-20 00:00:00********* UNSAT ***********
  
 PLEASE SEE MOST NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEENOTES FROM PREVIOUS REVIEW
 ARE STILL ATTACHED.
 SEE NOTES: 1,2,3,4
  
 1)NOTE: PLEASE SEE A RESPONSE NOTE
 ON ELECTRICAL NOTES MENTIONS, ELECTRICAL
 SD'S W/ BATTERY BACK UP ARE NOT REQUIRED
 ON EXISTING.
 PLEASE SEE PREVIOUS NOTE W/ REFERENCE
 TO CHAPTER 34 OF THE FBC FOR REMODEL OF
 EXISTING DWELLINGS. ALL GFI'S AND SD'S
 ARE REQUIRED TO BROUGHT UP TO CODE.
 CODE REQUIRES 120V W/ BATTERY BACK-UP.
  
 *** NO HAND DRAWN CHANGES MAY BE PLACED
 ON PLANS WHICH ARE SIGNED AND SEALED
 BY AND ARCH OR ENGINEER.
 FS 471.025,481.221
  
 *** PLEASE SEE THE JOBSITE/CONTRACTORS
 COPY OF PLANS WERE SUBMITTED WITH
 REVISED PLANS. PLEASE SEE THESE PLANS
 SHOULD REMAIN ON JOBSITE AND SHOULD NOT
 BE SUBMITTED WITH REVISIONS.****
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 19:57 Rev Time 0.33
Received By dpalmer Date 2004-09-21 Time 19:49 Sent To  
Notes
2004-09-21 00:00:00********* UNSAT *************
  
 1)NOTE: PLEASE SEE PREVIOUS PLANS SHOW
 EXSITING ELECTRICALWHICH IS NOW MISS-
 -ING FROM THESE PLANS.
 PLEASE ALSO SEE MISSING PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE NOW NEW ITEMS ARE
 BEING ADDED TO BATHS ETC.
 PLEASE SEE 210.52D,210.11C3 FOR BATH
 CIRCUIT TO BE 20A #12.
  
 3)NOTE: PLEASE SEE SCOPE OF WORK HAS
 ALSO INCREASED. VALUE MUST BE INCREASED
 PER FBC 104.6.5
  
 4)NOTE: PLEASE SEE FBC CHAPTER 34 WHICH
 REQUIRES BRINGING ELECTRICAL UP TO CODE
 FOR ALTERATIONS AND % OF REMODEL.
 PLEASE SEESD'S INSIDE AND OUTSIDE
 BEDRMS WILL BE REQUIRED ALONG WITH GFI'S
 IN ANY LOCATIONS WHERE REQUIRED AND NOT
 EXISTING.210.8
  
 5)NOTE: PLEASE SUBMIT TWO COPIES OF
 PLANS FOR REVIEW AND STAMPING .
 FBC 104.2.1
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-08 Cont ID  
Sent By dpalmer Date 2004-07-08 Time 08:08 Rev Time 0.33
Received By dpalmer Date 2004-07-08 Time 08:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-21 Cont ID  
Sent By csiegber Date 2004-06-30 Time 15:02 Rev Time 0.25
Received By dpalmer Date 2004-06-21 Time 09:53 Sent To  
Notes
2004-06-21 00:00:00**** UNSAT ****
  
 1)NOTE: PLANS NOTED FOR ELECTRIC BUT
 NONE SHOWN.
 PLEASE SHOW.
 210.52D, 210.11C3, 210.52C1,210.52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 14:26 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 14:26 Sent To E
Notes
2004-10-25 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-15 Cont ID  
Sent By csiegber Date 2004-10-15 Time 09:56 Rev Time 0.00
Received By csiegber Date 2004-10-15 Time 09:56 Sent To  
Notes
2004-10-15 00:00:00TO COMM BD#51

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 08:43 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 08:43 Sent To  
Notes
2004-09-15 00:00:00TO COMM BD#10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 09:41 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 09:40 Sent To B
Notes
2004-07-19 00:00:00TO MJ DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-06-30 Time 15:02 Rev Time 0.00
Received By csiegber Date 2004-06-30 Time 15:02 Sent To  
Notes
2004-07-01 00:00:00TO COMM BD#55
2004-06-30 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-06-30 Time 15:02 Rev Time 0.00
Received By csiegber Date 2004-06-04 Time 16:47 Sent To  
Notes
2004-06-04 00:00:00TO COMM BD#8

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-11-05 Cont ID  
Sent By kstevens Date 2004-11-05 Time 17:07 Rev Time 0.75
Received By kstevens Date 2004-11-05 Time 17:06 Sent To  
Notes
2004-11-05 00:00:00REVISION OK - NOT MOVING LAVS -
 EXISTING
 LAV TO STAY IN PRESENT LOCATION.

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 10:15 Rev Time 0.33
Received By kstevens Date 2004-10-09 Time 10:15 Sent To  
Notes
2004-10-09 00:00:00REVISION DENIED
  
 1) SUBMIT TWO SETS OF SIGNED/SEALED/DAT-
 ED PLANS FOR REVIEW. SECTION 104.2.1
 2) INDICATE REVISION WITH A REVISION
 NUMBER, AND CLOUD REVISION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-10 Cont ID  
Sent By kstevens Date 2004-07-10 Time 10:39 Rev Time 0.33
Received By kstevens Date 2004-07-10 Time 10:38 Sent To  
Notes
2004-07-10 00:00:00PASSED/PROVISO - ALL CAPPED PLUMBING
 PIPES SHALL BE INSPECTED PRIOR TO COVER-
 ING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-19 Cont ID  
Sent By kstevens Date 2004-06-19 Time 09:51 Rev Time 0.50
Received By kstevens Date 2004-06-19 Time 09:51 Sent To  
Notes
2004-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) SUBMIT PLANS THAT SHOW EXISTING FLOOR
 PLAN, & NEW FLOOR PLAN. SECTION 104.2.1
 2) SUBMIT SANITARY AND WATER RISER DIA-
 GRAMS. SECTION 104.3.1.1
 3) PLANS SHALL BE SIGNED, SEALED, AND
 DATED BY A DESIGN PROFESSIONAL. ALL
 LICENCES, ADDRESS, PHONE NUMBER REQUIRED
 FOR THE TITLE BLOCK SHALL BE ON PLANS.
 FS 481.229(1)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]