Plan Review Details - Permit 04060130
Plan Review Stops For Permit 04060130
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-17 Cont ID  
Sent By btrobaug Date 2004-06-17 Time 10:17 Rev Time 0.33
Received By btrobaug Date 2004-06-17 Time 10:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-06-16 Time 12:01 Rev Time 0.00
Received By btrobaug Date 2004-06-07 Time 13:13 Sent To  
Notes
2004-06-07 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9 NEC.
  
 2} PROVIDE A RISER DIAGRAM PER 215.5,
 AND INCLUDE GROUNDING DETAIL PER 250.50
 & 250.66.
  
 3} THE PERSON RESPONSIBLE FOR THE
 DESIGN SHALL PUT THEIR NAME AND
 SIGNATURE ON THE DRAWING PER 104.2.1,
 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-16 Time 12:01 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 12:01 Sent To E
Notes
2004-06-16 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 11:02 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 11:01 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved