Plan Review Details - Permit 04060123
Plan Review Stops For Permit 04060123
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-12-28 Cont ID  
Sent By alange Date 2005-12-28 Time 13:52 Rev Time 1.25
Received By alange Date 2005-12-28 Time 12:49 Sent To  
Notes
2005-12-28 00:00:00REVISION TO PAGES 100,102 AND 200 OK FOR
 RAMPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-11-01 Cont ID  
Sent By shill Date 2004-11-01 Time 15:42 Rev Time 0.00
Received By shill Date 2004-11-01 Time 10:40 Sent To I
Notes
2004-11-01 00:00:00***PROVISO***
 SEPARATE PERMITS FOR FENCE, GATE,
 DUMPSTER, ROOFING, DOORS, LOUVERS,
 ROLLUP DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2005-01-24 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:31 Rev Time 0.00
Received By lmartine Date 2004-10-06 Time 11:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-03 Cont ID  
Sent By shill Date 2004-08-03 Time 11:09 Rev Time 4.00
Received By shill Date 2004-08-03 Time 09:03 Sent To  
Notes
2004-08-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SOME SHEETS ARE STILL MARKED WITH
 THE INCORRECT ADDRESS OF 6500 (RATHER
 THAN 6501).PLEASE CHANGE; THE SHEETS
 DO NOT NEED TO BE CHANGED OUT BUT THE
 ADDRESS CAN BE OVERWRITTEN AS PER OUR
 CONVERSATION.
  
 2.)PLEASE NOTE THAT MR. CHEN'S
 ADDRESS ON THE DBPR WEBSITE IS NOT THE
 SAME AS ON THE TITLE BLOCK PROVIDED.
 PLEASE NOTE THAT HE IS TAKING
 RESPONSIBILITY AS PROVIDING THIS AS HIS
 LEGAL ADDRESS.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 4.)PLEASE PROVIDE THREE COPIES OF
 ALL DOCUMENTS.A RESIDENT INSPECTOR
 WILL BE REQUIRED DUE TO THE NATURE OF
 THE CONSTRUCTION.PLEASE CONTACT
 HAROLD PISKURA FOR MORE INFORMATION,
 561-805-6711.
  
 5.)THE ORIGINAL UNITY OF TITLE
 PROVIDED WAS NOT A RECORDED COPY.THIS
 DOCUMENT MUST BE RECORDED WITH THE
 CLERK OF COURTS FOR THIS PLAN TO BE
 REVIEWED AS TWO BUILDINGS ON ONE LOT.
 OTHERWISE, IT MUST BE REVIEWED WITH
 THE EXISTING PROPERTY LINES, WITH
 COMPLIANCE WITH TABLE 600.I HAVE
 ATTEMPTED TO LOCATE PROOF OF RECORDING
 WITH THE CLERK OF COURTS, SEE
 ATTACHED, AND CANNOT CONFIRM THAT IT
 WAS EVER RECORDED.
  
 6.)AS DISCUSSED, THE FOLLOWING ITEMS
 RELATE TO ITEMS NUMBER 7 -24 FROM THE
 PREVIOUS LIST WHICH APPARENTLY WERE
 LEFT OFF OF THE INTERNET SITE.
  
 7.)WHEN CONVERTING TO PERMIT, SEPARATE
 PERMITS WILL BE REQUIRED FOR THE TWO
 DIFFERENT BUILDINGS AND THE DUMPSTER
 ENCLOSURE.ADDITIONAL PERMITS WILL
 ALSO BE REQUIRED FOR THE FENCE, GATE
 AND AWNING.
  
 8.)ZONING APPROVAL REQUIRED BEFORE A
 PERMIT CAN BE ISSUED.
  
 9.)WHEN RESUBMITTING, PLEASE ALSO
 SUBMIT THE OLD SHEETS FOR REFERENCE.
  
 10.) ALL SHEETS REQUIRED TO BE SIGNED
 AND SEALED.
  
 11.) TITLE BLOCK REQUIRED FOR STUART
 CUNNINGHAM, PE, ALSO CA NUMBER FOR
 CUNNINGHAM & DURRANCE. (SHEET 102, ANY
 OTHER SHEETS BY MR. CUNNINGHAM).
  
 12.) IT APPEARS THAT THE ACCESSIBLE
 ROUTE TO BLDG 1 IS BLOCKED BY SOD AND
 LANDSCAPING, SHEETS 102 AND 200.THE
 ROUTE FOR BLDG 2 IS OFFSET FROM THE
 MARKED ACCESSIBLE AISLE; THE DOOR
 SWINGS OVER THE ACCESSIBLE PARKING
 SPACE.PLEASE CORRECT AND/OR CLARIFY.
  
 13.)SHEET 400 SHOWS A LL OF 100#; FBC
 TABLE 1604.1 REQUIRES 100 FOR LIGHT
 MANUFACTURING, 150 FOR HEAVY.FBC1604.3
 CONCENTRATED FLOOR LOADS WILL BE
 CONSIDERED BUT NOT LESS THAN TABLE
 160-4.1.INDICATE DESIGN CRITERIA AND S
 HOW COMPLIANCE.ALSO SEE STORAGE
 WAREHOUSE IN TABLE 1604.1.
  
 14.)TEST REPORTS AND FLORIDA STATE,
 LOCAL OR SITE SPECIFIC PRODUCT APPROVALS
 REQUIRED FOR THE DOORS, LOUVERS, ROLLUP
 DOORS, AND ROOF.SUBMIT 3 COPIES.
  
 WWW.FLORIDABUILDING.ORG FOR THE
 FLORIDA STATE PRODUCT APPROVALS
  
 WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING
 CODE COMPLIANCE, PRODUCT CONTROL SEARCH
 FOR DADE COUNTY NOAS)
  
 15.)TABLE 600 REQUIRES 0% OPENINGS FOR
 BUILDINGS ALONG THE WEST AND SOUTH
 PROPERTY LINES.BOTH BUILDINGS SHOW
 A WALL EXHAUST FAN (1-500) ON THE WEST
 SIDE, SHEET 300.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-06 Cont ID  
Sent By shill Date 2004-06-23 Time 16:19 Rev Time 6.00
Received By shill Date 2004-06-23 Time 15:43 Sent To  
Notes
2004-06-23 00:00:00****CORRECTIONS****
  
 *****PAID PLAN CHECK, NOT A PERMIT
 APPLICATION*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE CORRECT ADDRESSES OF THE
 PARCELS ARE 6501 & 6511 (NOT 6500/6511)
 ACCORDING TO THE PROPERTY APPRAISER.
 REVISE THE PERMIT APPLICATION AND PLANS.
  
 2.)RE: STRUCTURAL CALCULATIONS
 PREPARED BY X. CHEN, PE, A TITLE BLOCK
 FOR THE ENGINEER IS REQUIRED FAC61G15.23
 .002.
  
 3.)RE: STRUCTURAL CALCULATION PREPARED
 BY X.CHEN, PE, REVISE THE 4TH SHEET TO
 CORRECTLY SHOW ZONE 3, CITY OF WEST
 PALM BEACH AMENDMENTS TO THE FBC, TABLE
 2306.1, SEE ATTACHED.
  
 4.)PRIOR TO PERMITTING, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY.THE
 PLANS MUST BE STAMPED AND THE RECEIPT
 ATTACHED TO THE APPLICATION.233-5025
  
 5.)PRIOR TO PERMITTING, A NOTICE OF
 COMMENCEMENT MUST BE FILED WITH THE
 CLERK OF COURTS.
  
 6.)PROVIDE A COPY OF THE RECORDED
 UNITY OF TITLE.
  
 7.)WHEN CONVERTING TO PERMIT, SEPARATE
 PERMITS WILL BE REQUIRED FOR THE TWO
 DIFFERENT BUILDINGS AND FOR THE
 DUMPSTER ENCLOSURE.ADDITIONAL PERMITS
 WILL ALSO BE REQUIRED FOR THE FENCE,
 GATE AND AWNING.
  
 8.)ZONING APPROVAL REQUIRED BEFORE A
 PERMIT CAN BE ISSUED.
  
 9.)WHITEOUT HAS BEEN USED TO REVISE
 A SHEET (102, SEE HIGHLIGHT ON REVIEW
 SET).BEFORE RESUBMITTING PLEASE MAKE
 REVISIONS TO THE ORIGINAL SET, DO NOT
 WHITEOUT CHANGES.
  
 10.) SHEET 102, AN ELEVATION OF 17.0 AND
 17.58 ARE GIVEN OUTSIDE OF THE DOOR TO
 BLDG 1.
  
 11.) SHEET 102, ELEVATION OF FLOOR
 SURFACES ON BOTH SIDES OF A DOOR SHALL
 NOT VARY BY MORE THAN 1/2, FBC1012.1.3.
  
 12.)PROVIDE WIDTH AND SLOPE OF THE ADA
 PARKING ACCESS AISLES AND SIDEWALK,
 ACCESSIBLE PARKING SPACE FBC CHAPTER 11.
  
 13.)SHEET LS OF THE REVIEW SET IS NOT
 SIGNED AND SEALED.PLEASE CHECK ALL
 SHEETS BEFORE RESUBMITTAL.
  
 14.)FOR THE SHEETS SEALED BY AN
 ENGINEER, THE TITLE BLOCK IS TO BE IN
 COMPLIANCE WITH FAC61G15-23.002.
 LACKING FOR STUART CUNNINGHAM PE ARE THE
 ADDRESS, CA NUMBER FOR THE COMPANY.
  
 15.)FOR THE SHEETS SEALED BY AN
 ARCHITECT, A TITLE BLOCK IS REQUIRED
 IN ACCORDANCE WITH FAC61G1.
 FOR WILLIAM FLINT, ADDRESS REQUIRED.
 FOR DON BOITNOIT, CA NUMBER FOR AHRENS.
  
 16.)THE TYPICAL H/C PARKING AND
 STANDARD PARKING STALLS (SHEET 103) IS
 TO COMPLY WITH WPB STANDARD, SEE
 ATTACHED.
  
 17.) IT APPEARS THAT THE ACCESSIBLE
 ROUTE TO BLDG 1 IS BLOCKED BY SOD AND
 LANDSCAPING, SHEETS 102 AND 103.THE
 ROUTE FOR BLDG 2 IS OFFSET; THE DOOR
 SWINGS OVER THE ACCESSIBLE PARKING
 SPACE.PLEASE CORRECT AND/OR CLARIFY.
  
 18.) TABLE 600 REQUIRES 0% OPENINGS FOR
 THE WEST AND SOUTH PROPERTY LINES. BOTH
 BUILDINGS SHOW A WALL EXHAUST FAN
 (1-500) ON THE WEST SIDE, SHEET 300.
  
 19.) SHEET 300, THE BATHROOMS ARE
 REQUIRED TO BE ACCESSIBLE.THE DETAIL
 1-304 IS COMPLIANT BUT THE FLOOR PLAN
 ON SHEET 300 SHOWS AN INSWING DOOR WHICH
 ENCROACHES UPON THE CLEAR FLOOR SPACE
 REQUIRED FOR FIXTURES FBC11-4.23.3.
  
 20.) SPECIFY INSULATION R VALUE, 8-306.
  
 21.) SHEET 400 SHOWS A LL OF 100#;
 FBC TABLE 1604.1 REQUIRES 100 FOR LIGHT
 MANUFACTURING, 150 FOR HEAVY. FBC
 1604.3 CONCENTRATED FLOOR LOADS WILL BE
 CONSIDERED BUT NOT LESS THAN TABLE1604.1
 INDICATE DESIGN CRITERIA AND SHOW
 COMPLIANCE.ALSO SEE STORAGE WAREHOUSE
 IN TABLE 1604.1.
  
 22.)TEST REPORTS AND FLORIDA STATE,
 LOCAL OR SITE SPECIFIC PRODUCT APPROVALS
 REQUIRED FOR THE DOORS, LOUVERS, ROLLUP
 DOORS, AND ROOF.
 WWW.FLORIDABUILDING.ORG FOR THE
 FLORIDA STATE PRODUCT APPROVAL.
  
 23.)NOTE 7.B.1 INDICATES A HAZARDOUS
 OCCUPANCY SEPARATION; CLARIFY AS NO
 OCCUPANCY SEPARATIONS ARE SHOWN ON THE
 PLAN.
  
 24.)NOTE 6.A GIVES A REQUIREMENT OF
 0-400 SMOKE DEVELOPED,, SHOULD BE 0-450
 FBC803.2.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-11-24 Cont ID  
Sent By dpalmer Date 2004-11-24 Time 11:51 Rev Time 0.25
Received By dpalmer Date 2004-11-24 Time 11:49 Sent To  
Notes
2004-11-24 00:00:00ELEC OK,
  
 CALLED "DOVE" , HE IS TO COME IN AND
 REMOVE ALL OLD/VOIDED SHEETS AS
 REQUESTED ONPREVIOUS REVIEWS
 BY THIS AND OTHER TRADES.
 OLD/VOIDED SHEETS SHOULD REMAIN IN A
 SEPARATE ROLL FOR REFERENCE ONLY.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-11-15 Cont ID  
Sent By dpalmer Date 2004-11-15 Time 14:47 Rev Time 0.50
Received By dpalmer Date 2004-11-15 Time 14:47 Sent To  
Notes
2004-11-15 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE NOTES ON TWO PREVIOUS
 REVIEWS REQUESTED ALL OLD/VOIDED SHEETS
 TO BE REMOVED. PLANS STILL CONTAIN OLD
 SHEETS IN SETS.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED SEPARATELY.
  
 2)NOTE: PLEASE SEE SHEET HAS NOW BEEN
 REVISED TO REMOVE EXHAUST FANS,
 THIS WILL REQUIRE MECH/FIRE REVIEW.
 PLEASE SEE PLANS ALSO NEED TO CORRELATE
 WITH PANEL SCHEDULES AND LOAD
 CALCUALTIONS. PANELS ETC ARE STILL
 SHOWING THESE??
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-09-22 Cont ID  
Sent By dpalmer Date 2004-09-22 Time 06:26 Rev Time 0.33
Received By dpalmer Date 2004-09-21 Time 20:45 Sent To  
Notes
2004-09-22 00:00:00ELECTRICAL OK, STAMPED E-SHEETS.
2004-09-21 00:00:00OLD/VOIDED SHEETS NOT REMOVED.
 THIS IS REQUIRED OF CONTRACTOR AND NOTED
 ON PREVIOUS REVIEW AND BY OTHER REVIEW-
 -ERS.
 PLANS IN ELECTRIC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-28 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 12:59 Rev Time 0.33
Received By dpalmer Date 2004-07-28 Time 12:58 Sent To  
Notes
2004-07-28 00:00:00********* UNSAT ****************
  
 1)NOTE: PLEASE SEE NEW REVISED SHEETS
 ARE NOT SIGNED,DATED OR SEALED BY THE
 ENGINEER OF RECORD.
 PLEASE SEE FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-11 Cont ID  
Sent By dpalmer Date 2004-06-11 Time 16:49 Rev Time 1.00
Received By dpalmer Date 2004-06-11 Time 16:02 Sent To  
Notes
2004-06-11 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE CIRCUITING FOR EM LTS
 ,NOTES MENTION ALL TO BE WIRED AHEAD OF
 LOCAL LIGHTING,HOWEVER, PLEASE SEE BLDG
 #1, ONE SHOWN ON RECEPT CIRCUIT.
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004,
 FS 471.219. PLANS REQUIRE ALL LICENSE
 #'S TO BE PRINTED ON TITLE BLOCK.
 THIS NOTE IS FOR ARCH/ ARCH'S CERTIFI-
 -CATE OF AUTHORIZATION #.FIRM LIC #.
 THIS IS REQUIRED FOR ALL TRADES AND
 SHEETS, WHEATHER OR NOT COMMENT IS
 MADE FROM OTHER REVIEWERS.
  
 3)NOTE: PLEASE SEE ZONING COMMENTS,
 FENCE/WALL/GATE IS REQUIRED TO BE UNDER
 SEPARATE PERMIT. MAYBE SHOWN ON ELEC-
 -TRICAL FOR REFERENCE ONLY.
  
 PLEASE SEE "PLAN REVIEW" FEE BALANCE IS
 REQUIRED TO BE PAID BEFORE PICKING UP
 PLANS FOR COMMENTS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 6 Status P Date 2005-09-26 Cont ID  
Sent By mamini Date 2005-09-26 Time 15:23 Rev Time 0.50
Received By mamini Date 2005-09-26 Time 15:23 Sent To  
Notes
2005-09-26 00:00:00PASSED:
  
 1. REVIEWED FOR THE REVISION AS
 SUBMITTED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2005-01-19 Cont ID  
Sent By mamini Date 2005-01-19 Time 10:38 Rev Time 0.50
Received By mamini Date 2005-01-19 Time 10:38 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2004-11-12 Cont ID  
Sent By mamini Date 2004-11-12 Time 14:06 Rev Time 1.00
Received By mamini Date 2004-11-12 Time 14:07 Sent To  
Notes
2004-11-12 00:00:00FAILED:
  
 1. REVIEW NOTE DATED 09/01/04
  
 "DISCHARGE OF STORM RUN-OFF TO NORTON
 AVE. AS PROPOSED MUST BE APPROVED BY
 THE CITY DRAINAGE ENGINEER, STEVE
 SARLEY,P.E, 494-1095, SUBMIT UPON
 COMPLETION OF HIS REVIEW".
  
 2. REVIEW NOTE DATED 06/07/04
  
 "WATER AND SEWER LINE TO THE PROPOSED
 BUILDING MUST BE SHOWN ON CIVIL PLANS,
 AND TYPE, SIZE MUST BE SPECIFIED".
  
 3. SHEET 102, SITE PAVING AND DRAINAGE
 PLANS, SHOW THE PROPOSED INLET.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2004-09-01 Cont ID  
Sent By mamini Date 2004-09-01 Time 09:02 Rev Time 1.00
Received By mamini Date 2004-09-01 Time 09:01 Sent To  
Notes
2004-09-01 00:00:00FAILED:
 1. DISCHARGE OF STORM RUN-OF TO NORTON
 AVE. AS PROPOSED MUST BE APPROVED BY THE
 CITY DRAINAGE ENGINEER, STEVE SARLEY,P.E
 949-1095, SUBMIT UPON COMPLETION OF HIS
 REVIEW.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2004-07-19 Cont ID  
Sent By mamini Date 2004-07-19 Time 15:22 Rev Time 1.00
Received By mamini Date 2004-07-19 Time 15:22 Sent To  
Notes
2004-07-19 00:00:00FAILED:
 1. CIVIL PLANS MUST BE REVIEWED AND
 APPROVED BY THE PUBLIC UTILITIES AND
 ENGINEERING ( STEVE SARLEY FOR THE
 PROPOSED DISCHARG ONTO THE NORTON, AND
 MANNY GONZALEZ FOR THE CONNECTIONS )
 PRIOR TO APPROVAL BY THE CONSTRUCTION
 SERVICES DEPT.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-06-07 Cont ID  
Sent By mamini Date 2004-06-07 Time 09:00 Rev Time 0.50
Received By mamini Date 2004-06-07 Time 08:59 Sent To  
Notes
2004-06-07 00:00:00FAILED:
 1. WORK WITHIN PUBLIC R.O.W REQUIRES
 A SEPARATE PERMIT FROM PUBLIC UTILITIES
 & ENGINEERING, 494-1086 WINDEL PALMER,
 NOTE TO G.C.
 2. ALL DRIVEWAY APPROACHES MUST BE
 CONSTRUCTED PER CITY OF WEST PALM BEACH'
 STANDARD AND REQUIREMENTS.
 3. CIVIL PLANS MUST BE REVIEWED AND
 APPROVED BY THE PUBLIC UTILITIES AND
 ENGINEERING FOR ALL THE CONNECTIONS
 TO THE CITY SERVICES, PLEASE CONTACT
 494-1085, MANNY GONZALEZ.
 4. WATER AND SEWER LINES TO THE PROPOSED
 BUILDING MUST BE SHOWN ON CIVIL PLANS
 AND TYPE, SIZES MUST BE SPECIFIED.
 5. CITY STANDARDS AND DETAILS MAY BE
 OBTAINED FROM THE PUBLIC UTILITIES AND
 ENGINEERING, 494-1085,MANNY GONZALEZ.
 6. DISCHARG OF STORM RUN-OFF TO NORTON
 AVE. AS PROPOSED MUST BE APPROVED BY THE
 CITY DRAINAGE ENGINEER, STEVE SARLEY,P.E
 494-1095, PLEASE SUBMIT DRAINAGE PLANS
 FOR HIS REVIEW AND APPROVAL.
 7. POLLUTION PREVENTION PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO ANY WORK
 BEGINS, NOTE TO G.C.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-01-24 Cont ID  
Sent By mcarsill Date 2004-11-19 Time 10:29 Rev Time 0.00
Received By lmartine Date 2004-11-19 Time 10:28 Sent To  
Notes
2005-01-24 00:00:00APPROVED BY MIKE CARSILLO, SEE SUBMITTAL
 FORM. LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-09-23 Cont ID  
Sent By nmccray Date 2004-09-23 Time 14:54 Rev Time 0.00
Received By nmccray Date 2004-09-23 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-29 Cont ID  
Sent By mcarsill Date 2004-07-29 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2004-07-29 Time 10:58 Sent To  
Notes
2004-07-29 00:00:00BUILDING ADDRESSES REQUIRED ON PROPER
 ELEVATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By mcarsill Date 2004-06-30 Time 15:51 Rev Time 0.00
Received By mcarsill Date 2004-06-30 Time 15:51 Sent To  
Notes
2004-06-30 00:00:00FAILED OTHER REVIEWS. CORRECTIONS ARE
 NEEDED PRIOR TO APPROVAL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 15:37 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 15:37 Sent To B
Notes
2005-12-16 00:00:00TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 10:08 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 10:08 Sent To ENG
Notes
2005-01-19 00:00:00TO "ENG" BOX./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-04 Cont ID  
Sent By csiegber Date 2004-11-04 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-11-04 Time 15:23 Sent To  
Notes
2004-11-04 00:00:00TO COMM BD#39

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-29 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:31 Rev Time 0.00
Received By csiegber Date 2004-10-29 Time 14:31 Sent To B
Notes
2004-10-29 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-26 Cont ID  
Sent By csiegber Date 2004-08-26 Time 16:34 Rev Time 0.00
Received By csiegber Date 2004-08-26 Time 16:34 Sent To  
Notes
2004-08-26 00:00:00TO COMM BD#43

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 12:17 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 12:17 Sent To  
Notes
2004-07-19 00:00:00TO COMM BD#59

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-06 Cont ID  
Sent By shill Date 2004-07-06 Time 13:09 Rev Time 0.00
Received By shill Date 2004-06-03 Time 10:10 Sent To  
Notes
2004-06-03 00:00:00TO COMM BD#45

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-11-30 Cont ID  
Sent By pkrauss Date 2004-11-30 Time 13:18 Rev Time 0.30
Received By pkrauss Date 2004-11-30 Time 13:18 Sent To  
Notes
2004-11-30 00:00:00APPROVED BY H. MOSER.NO A/C; EXHUAST
 FANS AND O.A. CALCULATIONS FOR MINIMUM
 VENTILATION ON PLAN SHEET 500.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-07 Cont ID  
Sent By hmoser Date 2004-08-07 Time 09:17 Rev Time 0.50
Received By hmoser Date 2004-08-07 Time 09:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-21 Cont ID  
Sent By pkrauss Date 2004-06-21 Time 08:59 Rev Time 0.25
Received By pkrauss Date 2004-06-21 Time 08:59 Sent To  
Notes
2004-06-21 00:00:00DENIED:
 PERMIT APPLICATION INDICATES THE
 PROPOSED WAREHOUSES ARE NOT AIR
 CONDITIONED.PROVIDE CALCULATION FOR
 THE REQUIRED VENTILATION AS PER 2001
 FBC(M) 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-10-07 Cont ID  
Sent By kstevens Date 2004-10-07 Time 16:45 Rev Time 1.25
Received By kstevens Date 2004-10-07 Time 16:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-31 Cont ID  
Sent By kstevens Date 2004-07-30 Time 18:49 Rev Time 1.00
Received By kstevens Date 2004-07-30 Time 18:49 Sent To  
Notes
2004-07-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
  
 1) FROM PREVIOUS REVIEW: SUBMIT CALCUL-
 ATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS. SHOW AREA OF ROOF AND 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO ROOF AREAS. SECTIONS 1106 AND
 1107. RESPONSE NOTED BUT NO CALCULATIONS
 ARE SHOWN. PLEASE CLARIFY.
 5) FROM PREVIOUS REVIEW: SUBMIT CLACUL-
 ATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS FOR THE EXISTING ROOF. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO AREA OF ROOF IN THE
 CALCULATIONS. SECTIONS 1106 AND 1107 AND
 ALL SUBSECTIONS. - NO RESPONSE NOTED.
 7) FROM PREVIOUS REVIEW: SHT 601 SANIT-
 ARY RISER DIAGRAM DOES NOT REFLECT THE
 LAYOUT. CLEANOUTS NEAR THE BLDG. DRAIN
 AND SEWER JUNCTION ARE NOT TWO-WAY ON
 THE RISER DIAGRAM. THE LAUNDRY SINK
 SHALL NOT DRAIN THROUGH THE WET VENT FOR
 THE BATHROOM FIXTURES. THIS SINK SHALL
 CONNECT DOWNSTREAM OF THE TOILET ROOM
 FIXTURES. SECTION 909.1 - THE WATER
 CLOSETS SHALL NOT BE DOUBLE TRAPPED. THE
 W/C'S HAVE INTEGRAL TRAPS AND DO NOT RE-
 QUIRE A TRAP PRIOR TO THE FIXTURE. SECT-
 ION 1002.1 EXCEPTION (1).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-19 Cont ID  
Sent By kstevens Date 2004-06-19 Time 06:19 Rev Time 2.00
Received By kstevens Date 2004-06-19 Time 06:19 Sent To  
Notes
2004-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) IRRIGATION PLANS/PERMIT REQUIRED.
 2) INDICATE LOCATION OF WATER COOLERS
 ON THE FLOOOR PLAN. SECTION 104.2.1
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW AREA OF ROOF
 AND 1/2 AREA OF ALL VERTICAL WALLS IN-
 CLUDING PARAPETS ADDED TO ROOF AREAS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 4) SHT 306 DETAIL #11, OVERFLOW SCUPPER,
 INDICATE WIDTH ON DETAIL TO DETERMINE
 AREA OF SCUPPER. SECTION 104.2.1
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS FOR THE EXISTING
 BLDG. SHOW LOCATION OF PRIMARY AND SEC-
 ONDARY ROOF DRAINS. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO AREA OF ROOF IN CALCULATIONS. SECTION
 1106 & SECTION 1107 AND ALL SUBSECTIONS.
 6) SHTS 101 AND 600. SHT 101 SHOWS THE
 METER AND BACKFLOW EXISTING, BUT SHT 600
 SHOWS A PRESSURE REDUCING VALVE. PLEASE
 CLARIFY. SECTION 104.2.1.
 7) SHT 601 SANITARY AND WATER RISER DIA-
 GRAMS DO NOT REFLECT THE FLOOR PLAN. MOP
 SINKS ARE NOT SHOWN ON THE RISER. CLEAN-
 OUTS NEAR THE BLDG. DRAIN & BLDG. SEWER
 JUNCTION SHOULD BE 2-WAY CLEANOUTS. SEC.
 708.3.5 - PVC IS NOT APPROVED FOR DIST-
 RIBUTION PIPE. TABLE 605.5 (SEE NOTE #6)
 8) SHT 601, SHOW HEIGHT OF W/C 11-4.16.3
 FLUSH CONTROLS 11-4.16.5 - FOR LAVS SHOW
 CLEARENCES OF 29" 11-4.19.2, AND EXPOSED
 PIPES AND SURFACES 11-4.19.4.
 9) SHTS 300 & 600 FLOOR PLANS SHOW DOORS
 TO TOILET ROOMS SWINGING INTO THE TOILET
 ROOMS. DETAIL #1 SHOWS OUTWARD SWINGS.
 SECTION 11-4.22.2 DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. CORRELATE FLOOR PLAN AND
 TOILET ROOM DETAIL. SECTION 104.2.1.
 10) A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL DRAWINGS AND MUST CONTAIN
 A) FIRM NAME, ADDRESS, AND TELEPHONE NUM
 BER.
 B) FIRM LICENSE NUMBER
 61G1-16.004(1)(2) & FS 481.2055
 11) UNABLE TO READ THE INFORMATION REQ-
 UIRED TO BE IMPRESSED BY THE SEAL OF THE
 ARCHITECT ON SHEETS 600 & 601.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2005-12-23 Cont ID  
Sent By mmclean Date 2005-12-23 Time 16:56 Rev Time 0.00
Received By mmclean Date 2005-12-23 Time 16:56 Sent To B
Notes
2005-12-23 00:00:00GIVEN TO LUIS. APPROVED BY SHIRLEY
 GRAHAM.

Review Stop Z ZONING
Rev No 3 Status P Date 2004-10-21 Cont ID  
Sent By sgraham Date 2004-10-21 Time 08:54 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2004-10-21 00:00:001. PROVIDE NEW LANDSCAPE PLAN BEFORE
 C/O OF BLDG
 2. SEAGRAPES REPLACED WITH SHADE TREES

Review Stop Z ZONING
Rev No 2 Status F Date 2004-08-30 Cont ID  
Sent By mmclean Date 2004-08-30 Time 13:04 Rev Time 0.00
Received By mmclean Date 2004-08-30 Time 13:03 Sent To  
Notes
2004-08-30 00:00:00DENIED, CONTRACTOR MUST ADDRESS THE PPRC
 COMMENTS BEFORE APPROVAL #2 REQUEST.
 CALL SHIRELY AT 822-1458

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By sgraham Date 2004-06-24 Time 11:11 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2004-06-24 00:00:00CONTRACTOR MUST ADDRESS THE PPRC
 COMMENTS BEFORE APPROVAL OF PLANS CALL
 SHIRLEY AT 659-8031.