Plan Review Details - Permit 04060064
Plan Review Stops For Permit 04060064
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-08-09 Cont ID  
Sent By rmcdouga Date 2004-08-09 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2004-08-09 Time 16:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-29 Time 10:16 Rev Time 1.00
Received By rmcdouga Date 2004-07-06 Time 10:24 Sent To  
Notes
2004-07-06 00:00:00DENIED
  
 1) THE SITE SPECIFIC FORM LISTS THOMAS
 KELAHER AS THE THIRD PARTY QUALITY
 ASSURANCE ENTITY. MR. KELAHER IS NOT
 LISTED WITH THE STATE AS SUCH. PLEASE
 REMOVE HIM FROM ITEM 7 ON THE FORM.
  
 2) THE WIDTH OF THE LEFT PANEL OF THE
 ANGLE BUTT GLASS ASSEMBLY ON THE SITE
 SPECIFIC PRODUCT APPROVAL DIFFERS FROM
 THE ARCHITECTURAL PLANS. SUBMITTALS FOR
 SITE SPECIFIC ASSEMBLIES MUST CORRESPOND
 WITH THE PLANS. REVISE SUBMITTAL OR
 PLANS.
  
 3) THE SIZE OF THE TESTED ASSEMBLY IS
 NOT THE SAME AS THE SIZES OF THE (2)
 ASSEMBLIES BEING INSTALLED AND THE GLASS
 THICKNESS IS DIFFERENT ON THE LIVING
 ROOM BUTT GLASS ASSEMBLY. SIGNED AND
 SEALED CALCULATIONS AND ASSUMPTIONS ARE
 REQUIRED TO BE SUBMITTED. INDICATE HOW
 THE DESIGN PRESSURES FOR THE ASSEMBLIES
 WERE DETERMINED. SEE CITY AMENDMENTS TO
 FBC 104.2.1.2.
  
 4) THE ADDRESS OF THE JOB IS REQUIRED ON
 THE SITE SPECIFIC FORM.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-21 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:25 Rev Time 1.00
Received By rmcdouga Date 2004-06-21 Time 09:58 Sent To  
Notes
2004-06-21 00:00:00DENIED
  
 1) THE SITE SPECIFIC FORM LISTS THOMAS
 KELAHER AS THE THIRD PARTY QUALITY
 ASSURANCE ENTITY. MR. KELAR IS NOT
 LISTED WITH THE STATE AS SUCH. PLEASE
 REMOVE HIM FROM ITEM 7 ON THE FORM.
  
 2) THE WIDTH OF THE LEFT PANEL OF THE
 ANGLE BUTT GLASS ASSEMBLY ON THE SITE
 SPECIFIC PRODUCT APPROVAL DIFFERS FROM
 THE ARCHITECTURAL PLANS. SUBMITTALS FOR
 SITE SPECIFIC ASSEMBLIES MUST CORRESPOND
 WITH THE PLANS.
  
 3) THE SIZE OF THE TESTED ASSEMBLY IS
 NOT THE SAME AS THE SIZES OF THE (2)
 ASSEMBLIES BEING INSTALLED AND THE GLASS
 THICKNESS IS DIFFERENT ON THE LIVING
 ROOM BUTT GLASS ASSEMBLY. THEREFORE,
 SIGNED AND SEALED CALCULATIONS AND
 ASSUMPTIONS BASED ON THE TESTED UNIT ARE
 REQUIRED TO BE SUBMITTED IN ACCORDANCE
 WITH GOOD ENGINEERING PRACTICES
 INDICATING HOW THE DESIGN PRESSURES FOR
 THE ASSEMBLIES WERE DETERMINED.
  
 4) THE BUILDING OFFICIAL REQUIRES THAT
 AN ENGINEER INSPECT AND APPROVE THE
 ASSEMBLY AND INSTALLATION OF SITE
 SPECIFIC (CUSTOM,ONE OF A KIND) PRODUCTS
 AND SUBMIT SIGNED AND SEALED LETTERS
 ATTESTING TO THEIR PROPER ASSEMBLY AND
 INSTALLATION. SUBMIT A SIGNED AND SEALED
 LETTER FROM THE ENGINEER THAT WILL BE
 DOING THE INSPECTIONS STATING THAT HE
 WILL DO THE REQUIRED INSPECTIONS AT TIME
 OF PERMIT APPLICATION. ANOTHER LETTER
 FROM THE ENGINEER IS REQUIRED AFTER THE
 INSTALLATION IS COMPLETED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-16 Time 14:55 Rev Time 1.00
Received By rmcdouga Date 2004-06-03 Time 16:00 Sent To  
Notes
2004-06-03 00:00:00DENIED
  
 SEE BUILDING REVIEW #6 UNDER MASTER
 PERMIT # 04021011.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-06-03 Cont ID  
Sent By rmcdouga Date 2004-06-03 Time 15:57 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-07-29 Time 10:16 Rev Time 0.00
Received By csiegber Date 2004-07-29 Time 10:16 Sent To B
Notes
2004-07-29 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:25 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 16:25 Sent To B
Notes
2004-07-01 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-16 Time 14:55 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 14:55 Sent To B
Notes
2004-06-16 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-02 Time 15:22 Rev Time 0.00
Received By csiegber Date 2004-06-02 Time 15:22 Sent To B
Notes
2004-06-02 00:00:00TO MISC BOX