| Plan Review Stops For Permit 04060055 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-08-09 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-08-09 |
Time |
08:52 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2004-08-09 |
Time |
08:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-07-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-06 |
Time |
11:44 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2004-07-08 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2004-07-08 00:00:00 | DENIED | | | 1.SHOW ON BEDROOMS WINDOWS IF THEY | | | ARE EXISTING OR NEW.BEDROOM #2 | | | WINDOW MUST COMPLY WITH FBC 1005.4 | | | EMERGENCY ESCAPE RESCUE OPENING SIZES. | | | | | | 2.PREMDOR PRODUCT APPROVAL NOT LISTED | | | ON THE PRODUCT APPROVAL SITE. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | SUBMIT PRODUCT APPROVALS FOR WINDOWS AND | | | IMPACT PROTECTION AND ROOFING. TWO | | | COPIES OF EACH. | | | | | | 3. SUBMIT PLANS TO HISTORICAL FOR REVIEW | | | | | | 4.REMOVE ITEMS FROM PLANS THAT WILL | | | NOT BE PERMITTED WITH THESE PLANS. | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-07 |
Time |
11:18 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2004-06-16 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2004-06-16 00:00:00 | DENIED | | | 1.WEST PALM BEACH AMMENDMENTS TO THE | | | FBC 104.2.1 DRAWINGS ARE REQUIRD TO BE | | | DRAWN TO SCALE.SHOW SCALE ON PLANS. | | | | | | 2. SHOW EXISTING FLOOR PLAN AND NEW | | | FLOOR PLANS.CLEARLY MARK ON PLAN. | | | | | | 3.SHOW TYPE OF ROOMS ON PLANS. | | | BEDROOMS WITH WINDOW OR DOOR CHANGES | | | MAY REQUIRE A NEW EMERGENCY ESCAPE | | | RESCUE OPENING.SHOW ON PLAN. | | | | | | 4.SUBMIT PRODUCT APPROVAL FOR NEW | | | EXTERIOR DOORS AND WINDOWS AND IMPACT | | | PROTECTION. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATIONPLEASE SEE THE STATE WEBSITE | | | AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 5.A HISTORICAL REVIEW WILL BE REQUIRED | | | ONCE PRODUCT APPROVALS ARE SUBMITTED. | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-12-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-12-14 |
Time |
10:06 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-12-14 |
Time |
08:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-07-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2004-07-05 |
Time |
18:53 |
Rev Time |
0.30 |
| Received By |
jleahy |
Date |
2004-07-03 |
Time |
18:52 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-06-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-06-30 |
Time |
14:33 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-06-03 |
Time |
15:44 |
Sent To |
Z |
|
| Notes |
| 2004-06-03 00:00:00 | | | | PLEASE SUBMIT A COMPLETE SET OF | | | ELECTRICAL DRAWINGS FOR REVIEW. INCLUDE | | | LOAD CALCULATIONS,SERVICE INFORMATION | | | AND COMPLETE FLOOR PLANS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-08-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-02 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-02 |
Time |
16:15 |
Sent To |
P |
|
| Notes |
| 2005-08-02 00:00:00 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-06-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-27 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-27 |
Time |
15:07 |
Sent To |
P |
|
| Notes |
| 2005-06-27 00:00:00 | TO "KSTEVENS" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
|
Date |
2004-12-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-09 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-09 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2004-12-09 00:00:00 | SENT TP "BT" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-07-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-27 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-27 |
Time |
14:43 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-07-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-07 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-07 |
Time |
11:18 |
Sent To |
B |
|
| Notes |
| 2004-07-07 00:00:00 | TO AL DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-25 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-25 |
Time |
16:19 |
Sent To |
M |
|
| Notes |
| 2004-06-25 00:00:00 | TO PK BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-06-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-07 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-07 |
Time |
08:54 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-06-04 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-02 |
Time |
10:17 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-08-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-06 |
Time |
11:44 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2004-08-06 |
Time |
11:26 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-06-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-27 |
Time |
14:43 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2004-06-30 |
Time |
14:27 |
Sent To |
E |
|
| Notes |
| 2004-06-30 00:00:00 | DENIED: | | | MECHANICAL PLAN IS MISSING THE MAJORITY | | | OF DUCT SIZES (SUPPLY & RETURN).PLEASE | | | PROVIDE DUCT & GRILLE SIZES.PLEASE | | | PROVIDE AN ADDITIONAL COPY OF THE ENERGY | | | AND MANUAL J CALCS.TWO COPIES OF PLANS | | | & ALL SUBMITTALS TO BE PROVIDED PER 2001 | | | FBC 104.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2004-06-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-25 |
Time |
16:21 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2004-06-14 |
Time |
11:05 |
Sent To |
B |
|
| Notes |
| 2004-06-14 00:00:00 | MECHANICAL PERMIT REQUIRED: | | | NO MECHANICAL PLANS SUBMITTED OR | | | CONTRACTOR INDICATED WITH PERMIT | | | APPLICATION.PLEASE PROVIDE PLANS, | | | EQUIPMENT SCHEDULE, ENERGY AND MANUAL | | | J CALCULATIONS WITH MECHANICAL PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-07 |
Time |
08:54 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2004-06-12 |
Time |
09:02 |
Sent To |
M |
|
| Notes |
| 2004-06-12 00:00:00 | NO RISER DIAGRAM. NOT ENOUGH INFORMATION | | | TO DO PLAN REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-06-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-06-03 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-06-04 |
Time |
15:19 |
Sent To |
I |
|
| Notes |
|
|