Plan Review Details - Permit 04060031
Plan Review Stops For Permit 04060031
Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-15 Cont ID  
Sent By kstevens Date 2004-06-15 Time 10:12 Rev Time 0.50
Received By kstevens Date 2004-06-15 Time 10:11 Sent To  
Notes
2004-06-15 00:00:00 
  
  
  
  
  
 IF WATER HEATER IS IN A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 3,000 CUBIC FEET REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By kstevens Date 2004-06-15 Time 07:44 Rev Time 1.00
Received By kstevens Date 2004-06-15 Time 07:43 Sent To  
Notes
2004-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) PLANS INDICATE 3" PVC VENT PIPE, BUT
 MANUF. INFORMATION STATES VENT HOODS MAY
 BE EXTREAMLY HOT DURING OPERATION.
 PLEASE CLARIFY. SUBMIT MANUF INFO FOR
 THE VENTING.
 2) PIPE SIZE FROM METER TO EXISTING TEE
 SHALL BE CHANGED TO 1-1/2" PER TABLE
 402(2) FOR 620,000 BTU'S @ 50 FEET.
 3) ALL INFORMATION, DRAWINGS, SPECIFIC-
 ATIONS AND ACCOMPANYING DATA SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]