| Plan Review Stops For Permit 04060031 |
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-06-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-15 |
Time |
10:12 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-06-15 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2004-06-15 00:00:00 | | | | | | | | | | | | | | | | | | | IF WATER HEATER IS IN A CONFINED SPACE, | | | OPENINGS REQUIRED PER SECTION 304.3.1 0R | | | SECTION 304.3.2 SHALL BE INSTALLED. | | | MINIMUM 3,000 CUBIC FEET REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-06-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-15 |
Time |
07:44 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-06-15 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2004-06-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1) PLANS INDICATE 3" PVC VENT PIPE, BUT | | | MANUF. INFORMATION STATES VENT HOODS MAY | | | BE EXTREAMLY HOT DURING OPERATION. | | | PLEASE CLARIFY. SUBMIT MANUF INFO FOR | | | THE VENTING. | | | 2) PIPE SIZE FROM METER TO EXISTING TEE | | | SHALL BE CHANGED TO 1-1/2" PER TABLE | | | 402(2) FOR 620,000 BTU'S @ 50 FEET. | | | 3) ALL INFORMATION, DRAWINGS, SPECIFIC- | | | ATIONS AND ACCOMPANYING DATA SHALL BEAR | | | THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
|