| 2004-06-04 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | IT IS NOTED THAT THE EXISTING ROOF |
| | STRUCTURE WILL BE GENERALLY REINFORCED |
| | BUT, IN ADDITION, THE "PARAPET & CRICKET |
| | MODIFICATION DETAIL" REQUIRES AMENDMENT |
| | AS FOLLOWS: |
| | |
| | 1) FBC 2108.2.1HOW IS THE NEW PARAPET |
| | WALL TIED TO THE EXISTING SLAB/WALL |
| | BELOW?AMEND THE DETAIL TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 2) FBC 2319.12.2COLLAR TIES.THE CUT |
| | ENDS OF THE RAFTERS SHALL BE TIED/BRACED |
| | BACK TO THE CONCRETE SLAB TO RESIST THE |
| | HORIZONTAL THRUST FROM THE INCLINED |
| | RAFTER.AMEND THE DETAIL. |
| | |
| | 3) FBC 1601.2.1NEW FRAMING UNDER |
| | RAFTER TO RESIST UPLIFT AND GRAVITY |
| | LOADS.THE DETAIL DOES NOT STATE WHAT |
| | IS THE SIZE (AND SPACING) OF THE MEMBERS |
| | TO BE USED FOR THIS FRAMING, HOW IT IS |
| | TO BE TIED TO THE SLAB/WALL BELOW, HOW |
| | THE RAFTER IS SEATED ON THE TOP PLATE OR |
| | WHAT IS THE CALCULATED UPLIFT AND |
| | MANUFACTURERS REFERENCE FOR THE RAFTER |
| | UPLIFT ANCHOR.AMEND THE DETAIL TO |
| | CLARIFY ALL OF THESE ITEMS. |
| | |
| | 4) 61G15-23.002(1)FL. ADMIN. CODE. |
| | PLANS SIGNED & SEALED BY A PROFESSIONAL |
| | ENGINEER SHALL INCORPORATE THE FULL |
| | SIGNATURE OF THE ENGINEER.THE |
| | SIGNATURE ON THE SUBMITTED SHEETS IS NOT |
| | THE FULL SIGNATURE OF RIZA NUR ALTAN,P.E |
| | THE SHEET ATTACHED TO THESE COMMENTS, |
| | FOR YOUR INFORMATION, SHOWS THE FULL |
| | SIGNATURE.WE HAVE RECENTLY CONTACTED |
| | THE FLORIDA BOARD OF ENGINEERS ABOUT |
| | SIMILAR CASES AND THEY HAVE ADVISED THAT |
| | PROFESSIONAL ENGINEER'S SIGNATURES |
| | SHOULD INCORPORATE A LEGIBLE FIRST AND |
| | LAST NAME.INITIALS ARE NOT SUFFICIENT. |
| | RIZA NUR ALTAN, P.E. SHALL PROVIDE A |
| | FULL SIGNATURE ON EACH RESUBMITTED SHEET |
| | OR SUBMIT A NOTARIZED SIGNED/SEALED |
| | LETTER STATING THAT THE SIGNATURE ON THE |
| | LETTER IS THE SAME AS THAT HELD ON FILE |
| | BY THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS.THAT LETTER WILL BE |
| | SUBMITTED TO THE BOARD FOR VERIFICATION. |
| | (471.025 F.S.). |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |