Plan Review Details - Permit 04051124
Plan Review Stops For Permit 04051124
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By rmcdouga Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2005-05-10 00:00:00SUMITTAL FOR ENGINEERED ALTERNATE
 FASTENING OF MARVIN WINDOWS WITH 1X
 BUCKS IS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-10-26 Cont ID  
Sent By rmcdouga Date 2004-10-26 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2004-10-26 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:31 Rev Time 0.00
Received By rmcdouga Date 2004-08-20 Time 08:14 Sent To  
Notes
2004-08-20 00:00:00DENIED
  
 1) INCOMPLETE TITLE BLOCK INFORMATION.
 FAC 61G-16.004 REQUIRES THE ARCHITECT'S
 FIRM LICENSE NUMBER AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT
 IS REQUIRED ON EVERY SHEET. SEE FS 481.
  
 FAC 61G15-23.002 IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. SEE FS 471.
  
 2) SHEETS A4.03, A5.03, A7.02, A7.11 AND
 A9.03 ARE MISSING FROM THE NEW PLAN SET.
  
 3) PROVIDE STRUCTURAL DETAILS FOR THE
 CHIMNEY AT THE LOGGIA. SPECIFY THE
 ATTACHMENT TO ROOF, FRAMING, EXTERIOR
 COVERING, ETC. SHOW COMPLIANCE WITH
 FBC 2804.2.4 WHICH REQUIRES CHIMNEY TO
 BE 3 FEET ABOVE THE HIGHEST POINT THAT
 IT PASSES THROUGH THE ROOF AND AT LEAST
 2 FEET HIGHER THAN ANY PORTION OF THE
 ROOF OR BUILDING WITHIN 10 FEET.
  
 4) SUBMIT AN ADDITIONAL COPY OF THE
 SITE SPECIFIC PRODUCT APPROVAL. THE NOA
 NUMBER LISTED ON THE SHEET ATTACHED TO
 THE SITE SPECIFIC FORM FOR THE FRENCH
 DOORS IS THE OLD NUMBER. PLEASE SPECIFY
 THE CURRENT NOA NUMBER.
  
 5) SPECIFY THE FIREBLOCKING AT THE
 CONCEALED SPACE BETWEEN STAIR STRINGERS
 AT THE TOP AND BOTTOM OF RUNS AS
 REQUIRED BY FBC 2305.1.4(3).
  
 6) SPECIFY THE LOCATION AND MATERIAL FOR
 THE DRAFTSTOPPING AT THE FLOOR/CEILING
 ASSEMBLY DIVIDING IT INTO APPROXIMATELY
 500 SQFT AREAS PER FBC 2305.2.2.
  
 7)SUBMIT STATE OR LOCAL PRODUCT APPROVAL
 FOR THE FOLLOWING:
 - DOUBLE HUNG WINDOWS (IMPACT)
 - FIXED WINDOWS (IMPACT)
 - 8 PANEL DOOR TO LAWN STORAGE
 - OVERHEAD GARAGE DOORS
 COORDINATE THE PRODUCT APPROVALS THAT
 ARE SUBMITTED WITH THE WINDOWS AND DOORS
 THAT ARE SPECIFIED IN THE SCHEDULES ON
 THE PLANS. THEY NEED TO CORRESPOND TO
 EACH OTHER.
  
 8) THE NEW PLANS AND PRODUCT APPROVALS
 ARE REQUIRED TO BE REVIEWED BY THE
 HISTORIC PRESERVATION DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-28 Cont ID  
Sent By pkrauss Date 2004-08-16 Time 11:04 Rev Time 6.00
Received By rmcdouga Date 2004-06-28 Time 07:16 Sent To  
Notes
2004-06-28 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 2) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON THE SECOND FLOOR. FBC 2309.6
  
 3) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE A DOOR WITH A 29" CLEAR
 OPENING. FBC 11-4.23.2
  
 4) INCOMPLETE TITLE BLOCK INFORMATION,
 FIRM NUMBER, PRINTED NAME OF PERSON
 SIGNING AND SEALING, ETC. SEE FS 471 AND
 481. ENGINEER'S TITLE BLOCK INFO IS NOT
 ON STRUCTURAL SHEETS.
  
 5) INCOMPLETE DESIGN CRITERIA.
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF. NOTE:
 INTERNAL PRESSURE COEFFICENT IS + OR -
 0.18 FOR ENCLOSED STRUCTURE IF DESIGNING
 TO ASCE 7-98. SPECIFY FBC NOT SBC.
  
 6) SPECIFY HOW TERMITE PROTECTION WILL
 BE PROVIDED. FBC 1816
  
 7) THE UNVENTED ATTIC WITH ICYNENE
 INSULATION IS ACCEPTABLE UNDER FBC 103.7
 ALTERNATE MATERIALS AND METHODS WITH THE
 FOLLOWING CONDITIONS. 1) THE SYSTEM/
 ASSEMBLY MUST BE DESIGNED BY A FLORIDA
 REGISTERED DESIGN PROFESSIONAL, 2)
 INSULATION MUST BE INSTALLED CONTINOUSLY
 IN THE UPPER PLANE OF THE ROOF ASSEMBLY
 DECK/SHEATHING WITH SPECIFIED, APPROVED
 INSULATION PRODUCTS, AND THE CEILING
 SPACE IS NOT SEPARATED FROM THE
 CONDITIONED SPACE BELOW WITH INSULATION.
 SUBMIT SIGNED AND SEALED REPORT SPECIFY-
 ING HOW MATERIAL IS TO BE APPLIED AND
 MATERIAL SPECIFICATIONS.
  
 8) THE BALCONY GUARDRAIL IS REQUIRED TO
 HAVE A BOTTOM RAIL THAT WILL REJECT A
 2" DIAMETER SPHERE. FBC 1015.3
  
 9) SPECIFY THE CONNECTORS THAT WILL BE
 USED TO ATTACH THE 2ND FLOOR POST
 COLUMNS TO THE WOOD BEAMS.
  
 10) SPECIFY THE ATTACHMENT OF THE 2ND
 FLOOR GUARDRAILS TO THE WOOD COLUMNS.
  
 11) INDICATE ON THE PLANS THAT THE SPACE
 BETWEEN THE INTERMEDIATE RAILS AT THE
 INTERIOR STAIRS WILL REJECT A 4" SPHERE.
 SEE FBC 1015.3
  
 12) PROVIDE DETAILS, SECTIONS, ETC.
 INDICATING THE CONSTRUCTION AND
 CONNECTIONS OF THE TWO CHIMNEYS. SPECIFY
 THE REQUIRED HEIGHT ABOVE THE ROOF PER
 FBC 2804.2.4.
  
 13) SPECIFY RING SHANK NAILS FOR ROOF
 SHEATHING IN ZONE 3 FOR MEAN ROOF HEIGHT
 OF 25'- 35' PER CITY AMENDMENTS TO FBC
 TABLE 2306.1.
  
 14) SPECIFY A BOTTOM CORD LIVE LOAD OF
 10 PSF FOR ATTICS WITHOUT STORAGE. SEE
 FBC TABLE 1604.1
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT STATE PRODUCT APPROVAL FOR THE
 FOLLOWING:
 - TRUSS CONNECTORS
 - DOUBLE HUNG WINDOWS (IMPACT)
 - OVERHEAD GARAGE DOORS
 - FIXED WINDOWS (IMPACT)
 - 8-PANEL DOOR TO LAWN STORAGE
 NOTE: PRODUCT APPROVALS MUST BE APPROVED
 BY THE HISTORIC PRESERVATION DEPT.
 THE STOREFRONT DOORS MAY NOT BE ACCEPT-
 ABLE.
 NO CASEMENT WINDOWS ARE SHOWN ON PLANS.
 WHY WAS PRODUCT APPROVAL FOR CASEMENT
 WINDOWS SUBMITTED.
  
 16) THE UPLIFT VALUE FOR THE HETAL 20
 CONNECTOR IN THE ANCHOR SCHEDULE IS
 INCORRECT. THE UPLIFT VALUE IS 1810#
 WITHOUT THE ONE THIRD STRESS INCREASE IN
 THE STEEL CALCULATIONS. SEE 2004 SIMPSON
 CATALOG.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-01 Cont ID  
Sent By jleahy Date 2005-07-01 Time 10:45 Rev Time 0.30
Received By jleahy Date 2005-07-01 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-04 Cont ID  
Sent By btrobaug Date 2004-08-04 Time 10:56 Rev Time 1.00
Received By btrobaug Date 2004-08-04 Time 08:52 Sent To P
Notes
2004-08-04 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
  
 SUBMIT SAME FOR REVIEW PRIOR TO
 INSTALLING ANY GEAR OR CALLING
 INSPECTION ON THE SERVICE.
  
 SUBMIT TWO SETS OF AIC CALCULATIONS AND
 INDICATE COMPLIANCE WITH ARTICLE 110.9
 STATE THE RATING OF THE EQUIPMENT.
 A LETTER AND CALCS SUBMITTED ON A 8 1/2"
 X 11", SIGNED AND SEALED WILL SUFFICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-09 Cont ID  
Sent By csiegber Date 2004-07-29 Time 16:32 Rev Time 0.75
Received By btrobaug Date 2004-06-09 Time 07:05 Sent To M
Notes
2004-06-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} A TITLE BLOCK IS REQUIRED PER 61G15-
 23.002, PLEASE INCLUDE ALL LICENSE
 #'S ON THE REQUIREDBLOCK.
 PLEASE ALSO INCLUDE CERTIFICATE OF
 AUTHORIZATION #'S WHERE REQUIRED.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE SIZED PER 250.66 (# 2).
  
 4} THE RANGE (OVEN) MUST BE CALCULATED
 PER 220.19 (8000 VA., MIN).
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE PER 210.11(C)(3).
  
 6} PROVIDE A RECEPTACLE FOR THE SERVICE
 OF THE A/C EQUIPMENT PER 210.63.
  
 7} A SMOKE DETECTOR IS REQUIRED IN
 PROXIMITY TO THE STAIRS LEADING TO THE
 2ND FLOOR PER 905.2.2 FBC & NFPA-72
 8-1.4.1.6.2.
  
 8} SEE NOTE REFERRING TO200 AMP PANEL
 AND LOCATION ARROW, CORRELATE WITH
 CORRECT LOCATION.
  
 9} THE NOTE REFERRING TO THE AHU-2
 DISCONNECT " ABOVE" IN THE HALL CLOSET
 2ND FLOOR, MUST COMPLY WITH 424-19(A),
 "IN SIGHT OF".
  
 10} A RECCEPTACLE MUST BE ADDED TO THE
 REAR OF THE RESIDENCE TO COMPLY WITH
 210.52(E).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2004-05-26 Cont ID  
Sent By csiegber Date 2004-06-02 Time 09:37 Rev Time 0.00
Received By csiegber Date 2004-05-26 Time 09:37 Sent To  
Notes
2004-06-02 00:00:00NEW CONSTR ONLY NOT DEMO PER S PILAND
 DEE

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 13:50 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 13:50 Sent To E
Notes
2005-06-21 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 13:49 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 13:49 Sent To M
Notes
2005-06-21 00:00:00TO "M" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 13:48 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 13:48 Sent To P
Notes
2005-06-21 00:00:00TO "P" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-06 Cont ID  
Sent By adarroug Date 2005-05-06 Time 13:40 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 13:39 Sent To B
Notes
2005-05-06 00:00:00TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-12-29 Cont ID  
Sent By mjacobs Date 2004-12-29 Time 12:52 Rev Time 0.00
Received By mjacobs Date 2004-12-29 Time 12:52 Sent To P
Notes
2004-12-29 00:00:00TO "P" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:31 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 17:31 Sent To B
Notes
2004-10-18 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-06 Cont ID  
Sent By mmclean Date 2004-10-18 Time 10:01 Rev Time 0.00
Received By csiegber Date 2004-10-06 Time 14:31 Sent To Z
Notes
2004-10-06 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-07-29 Time 16:32 Rev Time 0.00
Received By csiegber Date 2004-07-29 Time 16:32 Sent To E
Notes
2004-07-29 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-29 Cont ID  
Sent By mmclean Date 2004-07-29 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-07-29 Time 09:07 Sent To Z
Notes
2004-07-29 00:00:00TO MM RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-28 Cont ID  
Sent By rmcdouga Date 2004-06-28 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2004-05-27 Time 10:52 Sent To  
Notes
2004-06-02 00:00:00TO SFD RACK/E/PER MM PASS ON TO TRADES
 THEN BACK TO PLANNING AS GRACE ON VAC
2004-05-27 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-07-06 Cont ID  
Sent By prafter Date 2005-07-06 Time 11:40 Rev Time 1.00
Received By prafter Date 2005-07-06 Time 11:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-16 Cont ID  
Sent By pkrauss Date 2004-08-16 Time 11:03 Rev Time 0.30
Received By pkrauss Date 2004-08-16 Time 10:56 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-14 Cont ID  
Sent By kstevens Date 2004-08-14 Time 12:28 Rev Time 0.40
Received By pkrauss Date 2004-06-14 Time 08:30 Sent To P
Notes
2004-06-14 00:00:00PROVISO:
 2001 FBC(M) 307.2.3:
 AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW
 PROTECTION BY MEANS OF A FLOAT SWITCH OR
 AUXILIARY DRAIN LINE TERMATING AT A
 CONSPICUOUS POINT.INDICATE TERMINATION
 OF THE AUXILIARY DRAIN LINE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-07-19 Cont ID  
Sent By kstevens Date 2005-07-19 Time 08:48 Rev Time 2.50
Received By kstevens Date 2005-07-19 Time 08:48 Sent To  
Notes
2005-07-19 00:00:00REVISION OK
  
 UNABLE TO FIND FILE COPY OF MEP'S - TWO
 ADDRESSES 506 & 502 FOR SAME JOB.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-01-08 Cont ID  
Sent By pschmitz Date 2005-01-08 Time 12:04 Rev Time 0.00
Received By pschmitz Date 2005-01-08 Time 12:04 Sent To PC
Notes
2005-01-08 00:00:00REVISION: APPROVED PER NOTE FROM KS
 DATED 08-14-04PES

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-08-14 Cont ID  
Sent By kstevens Date 2004-08-14 Time 12:28 Rev Time 0.50
Received By kstevens Date 2004-08-14 Time 12:28 Sent To M
Notes
2004-08-14 00:00:00PASSED/PROVISO
  
 LAUNDRY SINK SHALL DISCHARGE DOWNSTREAM
 OF THE WET VENT. 909.1 - REVISION REQUI-
 RED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-17 Cont ID  
Sent By btrobaug Date 2004-08-04 Time 10:56 Rev Time 1.00
Received By jleech Date 2004-06-17 Time 18:44 Sent To B
Notes
2004-06-17 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM NOT TO CODE.
 SEE RED LINES ON RISER DIAGRAM. W/C'S
 ON 1ST FLOOR ARE NOT VENTED, W/M TO
 DISCHARGE DOWN STREAM OF THE WET VENT
 OF 1/2 BATH. 909.1
 2.DELETE GAS PIPE RISER. GAS CONTRACTOR
 TO SUBMIT PLANS WITH APPLICATION.
 3.W/H PAN REQUIRES A DRAIN TO THE
 OUTSIDE OF BUILDING. 504.8.1 & 2.
 4.THERMAL EXPANSION CONTROL REQUIRED
 PER. 607.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2004-11-19 Cont ID  
Sent By mmclean Date 2004-11-19 Time 13:41 Rev Time 0.00
Received By mmclean Date 2004-11-19 Time 13:41 Sent To B
Notes
2004-11-19 00:00:00NOTE: APPROVE BY GRACE JOYCE, PLANNER
 822-1447. PLANS GIVEN TO RMCDOUGAL TO
 ISSUE PERMIT MM

Review Stop Z ZONING
Rev No 3 Status F Date 2004-10-18 Cont ID  
Sent By mmclean Date 2004-10-18 Time 10:01 Rev Time 0.00
Received By mmclean Date 2004-10-18 Time 10:01 Sent To I
Notes
2004-10-18 00:00:00DENIED, NEED TO PROVIDE CROSS ACCESS
 AGREEMENT TO ALLOW ONE DRIVEWAY FOR
 BOTH LOT.3RD REQUEST. GRACE JOYCE,
 PLANNER 822-1447 MM

Review Stop Z ZONING
Rev No 2 Status F Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-10-06 Time 14:31 Rev Time 0.00
Received By mmclean Date 2004-07-29 Time 15:52 Sent To I
Notes
2004-07-29 00:00:00DENIED, NEED TO PROVIDE CROSS ACCESS
 AGREEMENT TO ALLOW ONE DRIVEWAY FOR BOTH
 LOT.CALLED STEVE CURRY AND LEFT MSG.
 GRACE JOYCE, PLANNER 822-1447 MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By csiegber Date 2004-07-29 Time 09:07 Rev Time 0.25
Received By gjoyce Date 2004-06-24 Time 10:02 Sent To  
Notes
2004-06-24 00:00:00NEED CROSS ACCESS AGREEMNET TO ALLOW
 ONE DRIVEWAY FOR BOTH LOTS LEFT MESSAGE
 WITH STEVE CURRY 722-0881