| 2004-06-11 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04051056 |
| | ADD: 3308 45TH ST |
| | CONT: STEVE THOMSON |
| | TEL: (561)248-9594 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ALL SUBMITTALS, GEOTECH REPORT, PRO- |
| | DUCT APPROVALS REQUIRE (2) TWO COPIES |
| | FOR EACH PERMIT. PHASE I AND PHASEII ARE |
| | STAND ALONE PERMITS! |
| | |
| | 2) THIS WAS COMMENT # 8 FROM 1ST REVIEW |
| | DISCREPANCY FLOOR PLAN AND ELEVATIONS |
| | THE FLOOR PLAN DOES NOT MATCH THE ELE- |
| | VATIONS. ELEVATIONS FOR EAST AND WEST |
| | ARE REVERSED. |
| | |
| | 3) PART "B" OF COMMENT 8 1ST REVIEW, |
| | THE LOUVERS ARE ON THE WEST ELEVATION |
| | LESS THAN 15'-0" FROM THE PROIPERTY LINE |
| | REQUIRING A 45 MIN RATING, THE MANUFAC- |
| | TURES SPEC SHEET SUBMITTED ARE FOR (2) |
| | SEPERATE SYSTEMS, NOT A TESTED ASSEMBLY. |
| | THE RUSKIN IS NOT LISTED ON THE FLORIDA |
| | STATEWIDE PRODUCT APPROVAL SYSTEM. |
| | |
| | 4)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) COMMENT # 16 FROM 1ST REVIEW, |
| | PROVIDE INFORMATION AS WHAT WILL BE |
| | FABRICATED, SINCE FACTORY OCC, WHAT TYPE |
| | OF FUTURE EQUIPMENT WILL BE USED? |
| | |
| | 6)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |