| Plan Review Stops For Permit 04051041 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-07-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-07-16 |
Time |
11:16 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2004-07-16 |
Time |
11:16 |
Sent To |
PC |
|
| Notes |
| 2004-07-16 00:00:00 | REVISION: STEM WALL, FOUNDATION, | | | SLAB & HANDRAIL. | | | BUILDING PROVISO: NEW DOOR REQUIRES | | | STATEWIDE PRODUCT TESTING REPORT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-15 |
Time |
15:26 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2004-06-25 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-06-16 |
Time |
11:45 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2004-06-16 |
Time |
11:45 |
Sent To |
PC |
|
| Notes |
| 2004-06-16 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04051041 | | | ADD: 2400 CENTREPARK WEST# 101 | | | CONT: CAPITAL CONSTRUCTION SERVICES | | | TEL: (954) 782-9222 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2)TABLE 704.1 OCCUPANCY SEPERATION | | | REQUIREMENTS; | | | S2: LOW HAZARD REQUIRES 2 HR WALLS | | | PROVIDE UL LISTING OR US GYPSOM | | | | | | 3) WAREHOUSE TO MERCANTILE, THIS WARE- | | | HOUSE OCUPANCY REQUIRES 2 HR WALL, 1 1/2 | | | HR OPOENING PROTECTIVES. | | | | | | 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-25 |
Time |
06:23 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-06-25 |
Time |
06:05 |
Sent To |
|
|
| Notes |
| 2004-06-25 00:00:00 | NOTED | | | | | | 250.30,250.24 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-02 |
Time |
12:54 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-06-02 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2004-06-02 00:00:00 | ************* UNSAT ************** | | | | | | 1 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS CORRELATE WITH THE SUBMITTED PANEL | | | SCHEDULE. PLEASE CIRCUIT EM/EXT LTS | | | PER 700.12E. | | | | | | 3)NOTE: PLEASE SEE PLANS SHOW TWO NEW | | | PANELS, YET RISER INDICATE ONLY ONE. | | | RISER INDICATES A NEW 200A DISC, IS THIS | | | THE 200A PANEL? | | | | | | 4)NOTE: PLEASE METHOD OF EQUIPMENT | | | GRONDING BETWEEN MAIN DISC AND PANEL. | | | 250.110/250.24 PER 250.122 | | | | | | 5)NOTE: PLEASE SEE RISER AND ELEC RM | | | LAYOUT. LAYOUT SHOWS MANY MORE PANELS | | | THAN ON RISER? | | | PLEASE SHOW SIZE OF EXISTING SERVICE | | | AND SERVICE ENT CONDUCTORS.215.5 | | | | | | 6)NOTE: PLEASE SEE FS 481.221 WHICH ALSO | | | REQ'S ARCH TO DATE PLANS WHEN SIGNED AND | | | SEALED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-06-29 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-06-29 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-06-29 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2004-05-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-26 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-26 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-08-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-20 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-20 |
Time |
14:39 |
Sent To |
P |
|
| Notes |
| 2004-08-20 00:00:00 | TO KS BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-07-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-15 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-15 |
Time |
15:26 |
Sent To |
B |
|
| Notes |
| 2004-07-15 00:00:00 | TO JW DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-06-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-24 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-24 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2004-06-24 00:00:00 | TO COMM BD#9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-24 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-26 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2004-05-26 00:00:00 | TO COMM BD. #42 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-07-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-20 |
Time |
14:39 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-07-03 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2004-07-06 00:00:00 | PER ARCHITECT - HIGH LOW DRINKING FOUNT- | | | AIN - OK TO REMOVE 2ND LAV FROM RISER | | | DIAGRAM TO REFLECT THE FLOOR PLAN. 7-6-4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-06-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-15 |
Time |
16:52 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-06-15 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2004-06-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT A-2 SHOW CLEAR FLOOR SPACE FOR | | | THE W/C 11-4.16.2, THE LAV 11-4.19.3, & | | | THE DRINKING FOUNTAIN WITH CLEARANCES | | | 11-4.15.5. | | | 2) SHT A2 HANDICAP BATHROOM REQUIREMENTS | | | SHOW THE FOLLOWING ON DETAILS: | | | - TOILET TO BE 17" TO 19" - SHOWS 20" | | | SECTION 11-4.16.3 | | | - LAVS TO BE 34" TO RIM SECTION 11-4.19 | | | .2 | | | - SHOW FLUSH CONTROLS FOR W/C SECTION | | | 11-4.16.5 | | | - SHOW EXPOSEC PIPES AND SURFACES SEC | | | 11-4.19.4 | | | - SHOW DRINKING FOUNTAIN SPOUT HEIGHT | | | SECTION 11-4.15.2 | | | - SHOW DRINKING FOUNTAIN CLEARANCES | | | SECTION 11-4.15.5 | | | - SHOW COMPLIANCE FOR THOSE WHO HAVE | | | DIFFICULTY BENDING OR STOOPING. SECTION | | | 11-4.1.3(10)(A) | | | 3) SHT A-2 SHOWS W/C AT 15" OFF WALL TO | | | CENTER OF FIXTURE. 18" REQUIRED SEE FIG. | | | 28. | | | 4) SUBMIT A WATER RISER DIAGRAM. SECTION | | | 104.3.1.1 | | | 5) SHT A-2 SANT. RISER DIAGRAM, DRINKING | | | FOUNTAIN IS NOT SHOWN ON RISER. RISER | | | DIAGRAM SHALL REFLECT THE FLOOR PLAN. | | | SECTION 104.2.1 | | | 6) THE DATE THAT THE SEAL AND SIGNATURE | | | ARE AFFIXED SHALL APPEAR BELOW THE SIG- | | | NATURE ON EACH SHEET. FAC 61G1-16.003 & | | | FS 481.2055 | | | 7) A SPACE FOR THE PRINTED NAME OF THE | | | PERSON SEALING THE DOCUMENT. FAC | | | 61G1-16.004(6) & FS 481.2055 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|