Plan Review Details - Permit 04051005
Plan Review Stops For Permit 04051005
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-10-13 Cont ID  
Sent By shill Date 2004-10-13 Time 14:19 Rev Time 0.50
Received By shill Date 2004-10-13 Time 14:19 Sent To  
Notes
2004-10-13 00:00:00REVISIONS 1&2 DATED 8/25/04
 A201, A211, A221, A222, A301

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-08-10 Cont ID  
Sent By shill Date 2004-08-10 Time 12:40 Rev Time 0.50
Received By shill Date 2004-08-10 Time 12:40 Sent To  
Notes
2004-08-10 00:00:00SEE PROVISO ON PLAN RE: STAIR DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-08-09 Cont ID  
Sent By shill Date 2004-08-09 Time 13:08 Rev Time 1.00
Received By shill Date 2004-08-09 Time 13:08 Sent To  
Notes
2004-08-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SEAL IS TO BE DATED.
  
 ****NO RESUB FEE****

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-15 Cont ID  
Sent By csiegber Date 2004-07-22 Time 15:35 Rev Time 2.00
Received By shill Date 2004-07-15 Time 09:17 Sent To  
Notes
2004-07-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)THE SEAL IS TO BE DATED, FS481.221.
  
 2.)SEE OTHER REVIEWER'S NOTES IN
 REGARDS TO PRINTED LICENSE REQUIREMENTS.
  
 3.)REGARDING PREVIOUS COMMENT #1, AND
 OUR TELEPHONE DISCUSSION THAT IT WOULD
 BE REDLINED IF NECESSARY, PLEASE NOTE
 THAT I WAS UNABLE TO FIND AN EXCEPTION
 TO THIS REQUIREMENT FBC412.8.1.AS THE
 OTHER REVIEWS HAVE FAILED, PLEASE MAKE
 THE CHANGE AT THIS TIME OR CONTACT ME
 IF YOU ARE ABLE TO FIND AN EXCEPTION TO
 THIS REQUIREMENT.
  
 4.)WHEN RESUBMITTING, REPLACE ONLY
 SHEETS WHICH HAVE CHANGED.SUBMIT OLD
 SHEETS SEPARATELY TO EXPEDITE PLAN
 REVIEW.
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 6.)THE ORIGINAL PERMIT APPLICATION
 IS NO LONGER IN THE PACKAGE.PLEASE
 ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-18 Cont ID  
Sent By shill Date 2004-06-18 Time 16:00 Rev Time 2.00
Received By shill Date 2004-06-18 Time 16:00 Sent To  
Notes
2004-06-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)FBC412.8.1, ALL STAIRWAY DOORS
 WHICH ARE TO BE LOCKED FROM THE STAIR-
 WAY SIDE SHALL HAVE THE CAPABILITY OF
 BEING UNLOCKED UPON ACTIVITION OF THE
 SPRINKLER SYSTEM OR UPON POWER FAILURE.
  
 2.)DOOR 902 IS TO COMPLY WITH
 FBC FIG 25, CHAPTER 11 (MANEUVERABILITY)
  
 3.)SEE OTHER REVIEWER'S COMMENTS IN
 REGARDS TO TITLE BLOCK ISSUES.
  
 4.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-10-14 Cont ID  
Sent By dpalmer Date 2004-10-14 Time 14:20 Rev Time 0.33
Received By dpalmer Date 2004-10-14 Time 13:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-10-07 Time 14:51 Rev Time 0.33
Received By dpalmer Date 2004-09-21 Time 20:23 Sent To  
Notes
2004-09-21 00:00:00********* UNSAT *******
  
 1)NOTE: PLEASE SEE J-BOX'S IN CONFERENCE
 ROOM WITH NEW CIRCUITS SHOWN TO PANEL
 "N". PLEASE SEE CIRCUITS SHOWN ARE
 ALREADY USED ON POWER PLAN?
 PLEASE CLARIFY ANY NEW CIRCUITS FOR
 REVISED AREAS.
 PLEASE ALSO CORRELATE CIRCUITS ON PLANS
 AND PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE ARCH FIRM MISSING
 CA # IN TITLE BLOCK FOR TRADE PLANS.
 SHOWN ON ARCH. O.K.
 FAC 61G1-16.004
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-03 Cont ID  
Sent By dpalmer Date 2004-08-03 Time 08:22 Rev Time 0.25
Received By dpalmer Date 2004-08-03 Time 08:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-02 Cont ID  
Sent By dpalmer Date 2004-07-02 Time 16:40 Rev Time 1.00
Received By dpalmer Date 2004-07-02 Time 16:38 Sent To  
Notes
2004-07-02 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE NOTE #2 FROM FIRST
 REVIEW. TITLE BLOCK NO CONTAINS INFOR-
 -MATION STATING FLORIDA CERTIFICATE OF
 AUTHORIZATION # AS AR0015003. THIS IS
 THE ARCH'S FL REGISTRATION #, NOT THE
 FIRM'S REQUIRED CERTIFICATE OF AUTHORIZ-
 -ATION NUMBER. PLEASE SEE FS 481.219
 WHICH REQUIRESTHIS LICENSE #.
 PLEASE ALSO SEE FAC 61G1-16.004 WHICH
 REQUIRES THIS TO BE INCLUDED ON TITLE
 BLOCK.
 PLEASE SEE THIS COMMENT IS FOR ALL SHEET
 -S , WHEATHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWERS.
 AT TIME OF REVIEW ONLY THE ARCH'S #
 AS REFERENCED ON PLANS AS BEING THE
 STATE CA # WAS FOUND ONLINE WITH DBPR.
  
 PLEASE SEE THAT NO PERMIT APPLICATION
 WAS SUBMITTED BACK WITH RESUB. THIS
 MUST BE BROUGHT BACK IN FOR PROCESSING
 AND FOR REVIEWS TO BE COMPLETED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By dpalmer Date 2004-06-02 Time 12:21 Rev Time 0.75
Received By dpalmer Date 2004-06-02 Time 12:21 Sent To  
Notes
2004-06-02 00:00:00******* UNSAT ******
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42,210.19A,210.20A ETC
  
 2)NOTE: PLEASE SEE FS 481.219, FAC
 61G1-16.004. PLEASE INCLUDE ALL LICENSE
 INFORMATION ON TITLE BLOCK(S). THIS
 NOTE IS FOR ARCH FIRM. THIS IS REQ'D ON
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE FROM OTHER REVIEWER(S).
  
 3)NOTE: PLEASE SEE IMPRESSION TYPE SEAL
 IS REQ'D TO BE CLEAR AND VISABLE WITH
 ALL INFORMATION ON SAID SEAL.
 PLEASE SEE SOME SHEETS ARE FAINT AND
 UNCLEAR.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE ALSO REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 14:48 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-07-28 Cont ID  
Sent By mcarsill Date 2004-07-28 Time 15:10 Rev Time 0.00
Received By mcarsill Date 2004-07-28 Time 15:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-07-08 Cont ID  
Sent By nmccray Date 2004-07-08 Time 11:35 Rev Time 0.00
Received By nmccray Date 2004-07-08 Time 11:41 Sent To  
Notes
2004-07-08 00:00:00PLANS HAS MET CODE COMPLIANCES PLEASE
 SEE ELECTRICAL AND MECHANICAL REVIEWS.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By mcarsill Date 2004-05-25 Time 12:34 Rev Time 0.00
Received By mcarsill Date 2004-05-25 Time 12:33 Sent To  
Notes
2004-05-25 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 BUILDING DAILY.
  
 3) ALL EXITWAYS SHALL REMAIN CLEAR
 AND ACCESSIBLE.
  
 4) DOOR SWING APPEARS TO BE INCORRECT
 ON ONE OF THE EXISTING STAIRTOWERS.
  
 5) PLEASE CLARIFY # 8 ON PAGE A211.
 ANY LOCKING DEVICES INSTALLED ON
 EXIT DOORS SHALL COMPLY WITH
 SPECIAL LOCKING ARRANGEMENTS AS PER
 THE 2000 EDITION OF THE LIFE SAFETY
 CODE. PLEASE PROVIDE MORE DETAILS.
  
 6) WHAT FIRE RATING IS PRESENT FOR
 THE HERCULITE DOORS PLANNED FOR THE
 ELEVATOR LOBBY.
  
 7) HOW IS FIRE RESCUE EXPECTED TO
 ENTER THE SPACE SHOULD THE FIRE ALARM
 SYSTEM OR SPRINKLER SYSTEM NOT BE
 OPERATING WITH THE PROPOSED INSTALLATION
 OF SECURITY DEVICES.
  
 8) PLEASE SHOW ALL REQUIRED DIMENSIONS
 BETWEEN WORK STATIONS THAT WILL BE
 USED FOR EXITING.
  
 9) FIRE ALARM NOTES # 16 AND # 18
 ARE INCORRECT. FIRE ALARM CIRCUITS
 SHALL BE CLASS A, STYLE D AND DUCT
 SMOKE DETECTORS WHEN ACTIVATED SHALL
 INITIATE AN ALARM CONDITION NOT A
 TROUBLE CONDITION. PLEASE REVISE
 PLANS.
  
 10) NO MANUAL PULL STATION NOTED AT
 EXIT STAIR NEAR COPY AREA. SEPARATE
 PLANS AND PERMITS REQUIRED FOR
 FIRE ALARM SYSTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 14:51 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 14:51 Sent To E
Notes
2004-10-07 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 08:42 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 08:42 Sent To  
Notes
2004-09-15 00:00:00TO COMM BD#29

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 15:35 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 15:35 Sent To  
Notes
2004-07-22 00:00:00TO COMM BD#35

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 16:24 Sent To  
Notes
2004-06-25 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-24 Cont ID  
Sent By alange Date 2004-05-24 Time 13:09 Rev Time 0.00
Received By alange Date 2004-05-24 Time 13:09 Sent To  
Notes
2004-05-24 00:00:00TO COMM BD #10

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-10-07 Cont ID  
Sent By pkrauss Date 2004-10-07 Time 07:25 Rev Time 0.45
Received By pkrauss Date 2004-10-07 Time 06:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-08-05 Cont ID  
Sent By pkrauss Date 2004-08-05 Time 14:50 Rev Time 0.35
Received By pkrauss Date 2004-08-05 Time 14:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-07-06 Cont ID  
Sent By pkrauss Date 2004-07-06 Time 11:30 Rev Time 0.40
Received By pkrauss Date 2004-07-06 Time 11:00 Sent To  
Notes
2004-07-06 00:00:00DENIED:
 PLANS ARE CODE COMPLIANT WITH THE
 EXCEPTION FOR THE TITLE BLOCK.PLEASE
 PROVIDE CERTIFICATE OF AUTHORIZATION #
 AS REQUIRED BY THE FLORIDA STATUTE AND
 THE FLORIDIA ADMISTRATIVE CODE.
  
 PROVIDE ORIGINAL PERMIT APPLICATION
 WITH RE-SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-10 Cont ID  
Sent By pkrauss Date 2004-06-10 Time 06:49 Rev Time 0.50
Received By pkrauss Date 2004-06-09 Time 16:34 Sent To  
Notes
2004-06-10 00:00:00DENIED:
 1.PLEASE CLARIFY LOCATION & ACCESS TO
 THE CONDENSING UNIT FOR THE NEW 3 TON
 LIEBERT SYSTEM.
  
 2.THE CONDENSING UNIT STAND SHALL HAVE
 A MINIMUM CLEARANCE BETWEEN THE ROOF
 SURFACE & THE BOTTOM OF THE SUPPORT RAIL
 IN ACCORDANCE WITH 2001 FBC 1511.7
 (SEE ATTACHED).
  
 3.PLEASE CLARIFY NEW OR EXISTING FIRE
 DAMPERS.
  
 SEE ALSO COMMENT #2 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-10-06 Cont ID  
Sent By kstevens Date 2004-10-06 Time 17:39 Rev Time 0.50
Received By kstevens Date 2004-10-06 Time 17:39 Sent To  
Notes
2004-10-06 00:00:00REVISION OK - SHTS P1, P2, & P3

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-08-07 Cont ID  
Sent By kstevens Date 2004-08-07 Time 14:40 Rev Time 0.50
Received By kstevens Date 2004-08-07 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-10 Cont ID  
Sent By kstevens Date 2004-07-10 Time 16:30 Rev Time 0.75
Received By kstevens Date 2004-07-10 Time 16:30 Sent To  
Notes
2004-07-10 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: TITLE BLOCK
 REQUIRES FIRM LICENSE, (CERTIFICATE OF
 AUTHORIZATION). LICENSE FOR ARCHITECT IS
 SHOWN AS CERTIFICATE OF AUTHORIZATION.
 2) SHT A231 ROOMS 931, 937, & 961 SHOW
 CLEAR FLOOR SPACE FOR SINKS AND TURNING
 AREA ON FURNITURE PLAN TO SHOW HOW THE
 FURNITURE IMPACTS THE TURNING AREA AND
 THE CLEAR FLOOR SPACE, - RESPONSE NOTED,
 BUT THE CLEAR FLOOR SPACE AND THE TURN-
 ING AREA ARE REQUIRED TO BE ON THE FLOOR
 PLAN, NOT JUST THE TURNING AREA.
 3) THE PERMIT APPLICATION WAS NOT SUB-
 MITTED WITH PLANS. THIS WILL BE REQUIRED
 FOR PERMIT TO BE ISSUED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By kstevens Date 2004-06-15 Time 15:29 Rev Time 1.50
Received By kstevens Date 2004-06-15 Time 15:29 Sent To  
Notes
2004-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ARCHITECTURAL SHEETS, TITLE BLOCK RE-
 QUIRES FIRM LICENSE NUMBER, DATE PREPAR-
 ED, PRINTED NAME OF PERSON SEALING DOCU-
 MENT, AND CERTIFICATE OF AUTHORIZATION
 NUMBER. FAC 61G1-16.004 & FS 481.219
 2) SINKS SHALL COMPLY WITH SECTION 11-4.
 24 AND ALL SUBSECTIONS. SUBMIT A DETAIL
 KNEE CLEARANCE 11-4.24.3, DEPTH 11-4.24.
 4, EXPOSED PIPES AND SURFACES 11-4.24.6,
 3) SHT A231 ROOMS 931, 937, AND 961,
 SHOW CLEAR FLOOR SPACE 11-4.24.4 AND A
 TURNING AREA 11-4.2.3 ON FURNITURE PLAN
 TO SHOW HOW FURNITURE IMPACTS THE CLEAR
 FLOOR SPACE AND THE TURNING AREA.
 4) SHT P3 PLUMBING SPECIFICATIONS: 7 & 8
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCES.
 5) SHT P3 WATER RISER DIAGRAMS. SHOW THE
 LOCATION FOR THE WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. (AT ICE
 MAKERS). SHOW LOCATION AT FIXTURE NOT IN
 THE CEILING. PDI-WH 201 & MANUF. INSTALL
 INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]