| Plan Review Stops For Permit 04050976 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-06-22 |
Time |
11:42 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-06-22 |
Time |
11:42 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-06-17 |
Time |
16:29 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-06-17 |
Time |
16:29 |
Sent To |
PC |
|
| Notes |
| 2004-06-17 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)PROVIDE THE DESCRIPTION (RAISE | | | CEILING, PATCH DRYWALL) OF WORK ON THE | | | PLAN. | | | | | | 3.)PROVIDE A REASONABLE VALUE FOR THIS | | | JOB OR A MARSHALL & SWIFT ESTIMATED | | | VALUE WILL BE PROVIDED. | | | | | | 4.)WHAT IS THE BOX SHOWN IN THE | | | DINING AREA?PROVIDE A STRUCTURAL | | | DETAIL. | | | | | | 5.)PROVIDE INFORMATION IN REGARDS | | | TO BACKING FOR THE TUB. | | | | | | 6.) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-06-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-21 |
Time |
13:55 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-06-21 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2004-06-21 00:00:00 | NOTES REDLINED *** | | | | | | PLEASE SEE 210.52D/210.11C3, FOR BATH | | | RECEPTS. | | | | | | PLEASE SEE NFPA-72 8-1.4.1.6.2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-05-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-28 |
Time |
14:20 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-05-28 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2004-05-28 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE FBC 104.2.1 WHICH | | | REQUIRES PERSON RESPONSIBLE FOR PLANS | | | TO PRINT NAME AND SIGN PLANS. | | | | | | 2)NOTE: PLEASE SEE PERMIT APPLICATION | | | MENTIONS ELECTRICAL AS REQ'D?? | | | PLEASE SHOW SCOPE OF ELECTRICAL WORK, | | | MIN TO MEET NEC 2002. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2004-05-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-21 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-21 |
Time |
15:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-06-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-18 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-18 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2004-06-18 00:00:00 | TO COMM BD#61 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-21 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2004-05-21 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2004-05-21 00:00:00 | TO COMM BD#41 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-06-22 |
Time |
11:42 |
Rev Time |
0.25 |
| Received By |
shill |
Date |
2004-06-22 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2004-06-22 00:00:00 | OK PER PK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-06-09 |
Time |
06:34 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2004-06-09 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2004-06-09 00:00:00 | DENIED:MECHANICAL PERMIT 04050977 | | | PROVIDE PLANS INDICATE DUCT & GRILLE | | | SIZE, MATERIAL AND LAYOUT.INDICATE | | | EQUIPMENT EXISTING OR NEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2004-06-22 |
Time |
13:21 |
Rev Time |
0.60 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-06-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-15 |
Time |
16:00 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2004-06-15 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2004-06-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | | | | 1) ALL INFORMATION, DRAWING, SPECIFICAT- | | | IONS AND ACCOMPANYING DATA SHALL BEAR | | | THE NAME AND SIGNATURE OF THE PERSON RE- | | | SPONSIBLE FOR THE DESIGN. SEC. 104.2.1 | | | 2) PERMIT APPLICATION INDICATES THE ONLY | | | PLUMBING WORK TO BE DONE WILL BE IN THE | | | GUEST BATHROOM. IF THIS IS INCORRECT, | | | THE APPLICATION SHALL STATE ALL WORK TO | | | BE DONE ON THIS CONTRACT. | | | 3) SUPPLY A SANT. RISER DIAGRAM TO SHOW | | | HOW LAV WILL BE PIPED. SECTION 104.3.1.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|