| 2004-05-26 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 2} PLEASE SUPPLY A LOAD CALCULATION PER |
| | 220.30 NEC 2002. |
| | |
| | 3} SUPPLY A PANEL SCHEDULE LISTING ALL |
| | REQUIRED CIRCUITS,RATING OF OVERCURRENT |
| | DEVICES AND CONDUCTOR SIZES. |
| | |
| | 4} SHOW COMPLIANCE FOR GROUNDING ON THE |
| | RISER DIAGRAM PER 250.50 & 250.66. |
| | |
| | 5} SHOW ALL LIGHTING IN COMPLIANCE WITH |
| | 210.70 NEC. |
| | |
| | 6} SHOW CABINET AND SINK LAYOUT IN THE |
| | KITCHEN AND BATH FOR COMPLIANCE WITH |
| | 210.52(D) AND 210.52(C) & |
| | 210.52(A)(1)&(2). |
| | |
| | 7} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 8} PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6',12'RULE, CHECK ENTIRE |
| | DRAWING FOR NON COMPLIANCE. |
| | |
| | 9} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS.SEE 8-1.4.1.6.2 NFPA-72 1999 |
| | FOR REQUIREMENTS. |
| | |
| | 10} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING.210.52(E). |
| | |
| | 11} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | THERE ARE SEVERAL DISCREPANCIES ON |
| | THESE PLANS. PLEASE READ NFPA-70 (NEC) & |
| | NFPA-72 BEFORE RESUBMITTING PLANS. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |