Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-30 Cont ID  
Sent By jleahy Date 2004-06-30 Time 10:29 Rev Time 0.45
Received By jleahy Date 2004-06-30 Time 10:29 Sent To  
Notes
2004-06-30 00:00:00SEE ORIGINAL CHECK LIST #1,5,6,8JL

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-25 Time 15:13 Rev Time 0.66
Received By btrobaug Date 2004-06-16 Time 07:35 Sent To  
Notes
2004-06-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9.
  
 2} THE DRYER IS NOT INCLUDED IN THE
 LOADCALCULATION AS REQUIRED PER 220.18.
  
 3} THE AHU LISTED IN THE LOAD
 CALCULATION IS 6000VA, BUT ON THE PANEL
 SCHEDULE IT IS ON A 20 AMP BREAKER
 LISTED AS FAN. THE HEAT STRIPS MUST BE
 INCLUDED, SEE THE NAMEPLATE RATING AND
 CORRECT THE PLAN.
  
 4} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.11C3
  
 5} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6} THE RECEPTACLE PLACEMENT AND SPACING
 IN THE KITCHEN IS STILL INCORRECT,
 PLEASE READ 210.52 2002 NEC. IN ITS
 ENTIRETY
  
 7} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE, SEVERAL AREAS
 ARE STILL NOT IN COMPLIANCE AS
 INDICATED IN THE PREVIOUS REVIEW.
  
 8} SHOW THE LOCATION OF THE A/C
 EQUIPMENT AND THE RECEPTACLES REQUIRED
 BY 210.63.
  
 9} SUBMIT 2(TWO) SETS OF PLANS FOR
 REVIEW PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-26 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 15:05 Rev Time 1.00
Received By btrobaug Date 2004-05-26 Time 14:11 Sent To  
Notes
2004-05-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} PLEASE SUPPLY A LOAD CALCULATION PER
 220.30 NEC 2002.
  
 3} SUPPLY A PANEL SCHEDULE LISTING ALL
 REQUIRED CIRCUITS,RATING OF OVERCURRENT
 DEVICES AND CONDUCTOR SIZES.
  
 4} SHOW COMPLIANCE FOR GROUNDING ON THE
 RISER DIAGRAM PER 250.50 & 250.66.
  
 5} SHOW ALL LIGHTING IN COMPLIANCE WITH
 210.70 NEC.
  
 6} SHOW CABINET AND SINK LAYOUT IN THE
 KITCHEN AND BATH FOR COMPLIANCE WITH
 210.52(D) AND 210.52(C) &
 210.52(A)(1)&(2).
  
 7} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 8} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6',12'RULE, CHECK ENTIRE
 DRAWING FOR NON COMPLIANCE.
  
 9} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.SEE 8-1.4.1.6.2 NFPA-72 1999
 FOR REQUIREMENTS.
  
 10} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.210.52(E).
  
 11} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 THERE ARE SEVERAL DISCREPANCIES ON
 THESE PLANS. PLEASE READ NFPA-70 (NEC) &
 NFPA-72 BEFORE RESUBMITTING PLANS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 15:13 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 15:13 Sent To E
Notes
2004-06-25 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 15:05 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 15:05 Sent To E
Notes
2004-06-14 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 16:34 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 16:34 Sent To E
Notes
***NONE***