Plan Review Details - Permit 04050936
Plan Review Stops For Permit 04050936
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-06-14 Cont ID  
Sent By kstevens Date 2004-06-12 Time 14:32 Rev Time 0.50
Received By alange Date 2004-06-14 Time 12:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-06-07 Time 09:20 Rev Time 0.33
Received By btrobaug Date 2004-06-07 Time 11:05 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-24 Cont ID  
Sent By csiegber Date 2004-06-24 Time 10:59 Rev Time 0.00
Received By csiegber Date 2004-06-24 Time 10:59 Sent To P
Notes
2004-06-24 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-06-07 Time 09:20 Rev Time 0.00
Received By csiegber Date 2004-06-07 Time 09:20 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-03 Cont ID  
Sent By mmclean Date 2004-06-04 Time 15:41 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 14:06 Sent To Z
Notes
2004-06-03 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:10 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 14:10 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-14 Cont ID  
Sent By kstevens Date 2004-07-14 Time 07:34 Rev Time 1.25
Received By kstevens Date 2004-07-14 Time 07:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-12 Cont ID  
Sent By csiegber Date 2004-06-24 Time 10:59 Rev Time 0.75
Received By kstevens Date 2004-06-12 Time 14:29 Sent To B
Notes
2004-06-12 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (DETAIL OR NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-06-04 Cont ID  
Sent By mmclean Date 2004-06-04 Time 15:41 Rev Time 0.00
Received By mmclean Date 2004-06-04 Time 15:41 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-05-24 Cont ID  
Sent By csiegber Date 2004-06-03 Time 14:06 Rev Time 0.00
Received By mmclean Date 2004-05-24 Time 10:45 Sent To  
Notes
2004-05-24 00:00:00DENIED, NEED TO PROVIDE 2 COPY OF SURVEY
 WITH SETBACK FOR POOL.CALLED CONT FILE
 FOR P/U A MM