Plan Review Details - Permit 04050928
Plan Review Stops For Permit 04050928
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-10-29 Cont ID  
Sent By rmcdouga Date 2004-10-29 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2004-10-29 Time 10:09 Sent To  
Notes
2004-10-29 00:00:00DENIED
  
 1) ACCORDING TO THE PROPERTY APPRAISER,S
 RECORDS THIS PARCEL IS OWNED BY A
 CORPORATION. THEREFORE, A CONTRACTOR IS
 REQUIRED. NO OWNER BUILDER PERMIT CAN BE
 ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) CORRECT THE BUILDING TYPE SPECIFIED
 ON SHEET SP2. TYPE IV BUILDINGS ARE NOT
 ALLOWED TO HAVE WOOD TRUSSES. SEE FBC
 CHAPTER 6.
  
 5) SUBMIT (2) COMPLETE COPIES OF THE
 SOIL REPORT WITH BORING LOGS SIGNED AND
 SEALED BY THE SOIL ENGINEER.
  
 6) THE STRUCTURE IS LOCATED IN AN A5
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 7) CITY AMENDMENTS TO FBC TABLE 2306.1
 REQUIRES RING SHANK NAILS IN ZONE 3 FOR
 FASTENING ROOF SHEATHING. PLEASE REVISE
 THE NOTE ON S5.
  
 8) THE RED LINED CHANGES TO NOTE WT 3
 ARE REQUIRED TO BE INITAILED AND DATED
 BY THE P.E.
  
 9) REVISE THE TRUSS DESIGN CRITERIA ON
 S5 TO AGREE WITH INFO ON SHEET SN.
  
 10) UPDATE THE MASONRY STANDARDS ON SN1
 TO THE 2002 EDITIONS THAT ARE REFERENCED
 IN THE 2001 FBC CHAPTER 35(AMENDMENTS).
  
 11) THE CLEAR OPENING SIZES OF THE BED
 ROOM WINDOWS DO NOT APPEAR TO COMPLY
 WITH REQUIREMENTS OF FBC 1005.4 FOR
 EMERGENCY EGRESS. PLEASE CALL OUT THE
 WINDOW SIZES SEPARATELY FROM THE FIXED
 HALF CIRCLE WINDOWS THAT ARE ATTACHED
 ABOVE THEM WITH MULLIONS.
  
 12) PLANS SHOW A MASONRY FIREPLACE AND
 CHIMNEY. THE PLAN NOTES REFER TO A
 PREFABRICATED FIREPLACE AND CHIMNEY.
 PLEASE CLARIFY. IF IT IS PREFAB SUBMIT
 THE MANUFACTURER'S SPECIFICATIONS AND
 LISTING. IF IT IS A SITE CONSTRUCTED
 MASONRY FIREPLACE AND CHIMNEY SUBMIT
 DETAILED DRAWINGS WITH ALL DIMENSIONS
 FOR FIREBOX DEPTH, FIREPLACE OPENING,
 SMOKE CHAMBER, FLUE, ETC. SEE FBC 2804 &
 2806 FOR PREFAB AND FBC 2113 & 2114 FOR
 SITE CONSTRUCTED MASONRY.
  
 13) SPECIFY THE REINFORCING IN THE
 FIREPLACE FOUNDATION.
  
 14) PLEASE CORRECT NOTE 6 ON S3 THAT HAS
 TYPE OVER IT.
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT PRODUCT APPROVALS FOR WINDOWS,
 DOORS, ROOFING, OVERHEAD GARAGE DOORS,
 STORM PANELS, TRUSS CONNECTORS, ETC.
  
 16) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALCULATION FORMS.
  
 17) THE CONDITIONED AREA LISTED ON THE
 ENERGY CALCULATION FORM DOES NOT MATCH
 THE LIVING AREA SQUARE FOOTAGE LISTED ON
 THE PLAN. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-23 Cont ID  
Sent By jleech Date 2004-09-18 Time 09:53 Rev Time 4.00
Received By rmcdouga Date 2004-06-22 Time 14:19 Sent To  
Notes
2004-06-22 00:00:00DENIED
  
 ROBERT KNOTH IS NOT THE CURRENT OWNER OF
 RECORD. RECORDS INDICATE THAT PROPERTY
 WAS SOLD IN JANURARY 2004 TO AQUA VISTA
 LLC. OWNER BUILDER PERMIT CAN NOT BE
 ISSUED TO A CORPORATION. IF THIS INFORM-
 ATION IS INCORRECT, SUBMIT PROOF OF
 CURRENT OWNERSHIP.
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT AN ADDITIONAL COPY OF THE SOIL
 REPORT. SUBMIT (2) COPIES OF THE SOIL
 BORING LOGS.
  
 4) THE STRUCTURE IS LOCATED IN AN A5
 FLOOD ZONE AND IS REQUIRED TO HAVE THE
 FINISH FLOOR ELEVATION 6" ABOVE BASE
 FLOOD ELEVATION. SPECIFY ELEVATION ON
 THE PLANS. AN ELEVATION CERTIFICATE WILL
 BE REQUIRED PRIOR TO C.O.
  
 5) THE CITY OF WPB AMENDMENTS TO FBC
 TABLE 2306.1 REQIRE 8D RING SHANK NAILS
 IN ZONE 3 FOR STRUCTURES WITH MEAN ROOF
 HEIGHTS OF 25'-35'. PLEASE REVISE NOTE
 ON S5.
  
 6) REVISE ROOF ROOF TRUSS DESIGN CRITERA
 CRITERIA ON S5. BOTTOM CORD LIVE LOAD IS
 REQUIRED TO BE 10PSF FOR ATTICS WITHOUT
 STORAGE PER FBC TABLE 1604.1.
  
 7) SPECIFY THE POSITIVE AND NEGATIVE
 DESIGN PRESSURES FOR THE WINDOWS AND
 DOORS.
  
 8) THE MASONRY OPENING SIZES FOR WINDOWS
 IN THE SCHEDULE ON A14 DO NOT CORRESPOND
 TO STANDARD WINDOW SIZES. PLEASE REVIEW.
 SPECIFY THE CALL SIZES FOR THE WINDOWS
 SUCH AS SH25. WINDOWS MUST MEET EGRESS
 REQUIREMENTS OF FBC 1005.4.
  
 9) PROVIDE DETAILS FOR FIREPLACE AND
 CHIMNEY CONSTRUCTION. SPECIFY FRAMING
 MATERIALS, SPACING, CONNECTORS, ETC.
 SPECIFY THE HEIGHT OF THE CHIMNEY ABOVE
 THE ROOF. SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS AND UL OR OTHER LISTING
 INFORMATION FOR THE PREFAB FIREPLACE AND
 FLUE PIPE.
  
 10) REVISE SECTIONS ON A10 TO SHOW FIRE
 BLOCKING AT DROP CEILINGS PER FBC 2305.1
  
 11) CORRECT TYPO AT SCREEN VENT DETAILS.
 SHOULD BE OUTER MOST NOT CUTTER MOST.
  
 12) PROVIDE DETAILS OF THE INTERIOR
 GUARDRAIL/3'6" HIGH PARTITION WALL AT
 THE STAIRS, LANDING AND HALLWAY.
  
 13)FBC 1007.8.3 REQUIRES CIRCULAR STAIRS
 TO HAVE A MINIMUM TREAD DEPTH OF 9" WITH
 1" OF NOSING AT THE SMALLEST DIMENSION.
 CLARIFY THIS ON THE PLAN.
  
 14) REVISE STAIR DETAIL (2) ON A12.
 HUGHES IS NO LONGER IN BUSINESS AND DO
 NOT HAVE STATE PRODUCT APPROVAL. SPECIFY
 ANOTHER CONNECTOR.
  
 15) SPECIFY FIREBLOCKING AT THE TOP AND
 AND BOTTOM OF STAIR RUNS AS REQUIRED BY
 FBC 2305.1.3(3).
  
 16) REVISE BALAUSTERS DETAIL ON A12. FBC
 1015.3 REQUIRES INTERMEDIATE RAILS OR
 ORNAMENTAL PATTERN SUCH THAT A 4"
 DIAMETER SPHERE CAN NOT PASS THROUGH ANY
 OPENING UP TO A HEIGHT OF 34". A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT PASSAGE OF A 2"DIAMETER SPHERE.
 SPECIFY THE HORIZONTAL REINFORCEMENT.
 SPECIFY THE SIZE OF THE VERTICAL
 REINFORCEMENT. SPECIFT THE EMBED DEPTH
 OF THE REINFORCING. SPECIFY HOW THE
 RAIN WATER WILL BE DRAINED FROM THE
 BALCONY. SHOP DRAWINGS WILL BE REQUIRED.
  
 17) SPECIFY THE DIAMETER OF THE TAP CON
 SCREWS ON THE SLIDING GLASS DOOR DETAIL
 (10) ON A13. DRAWING SHOULD SHOW
 FASTENERS FOR FRAME THROUGH THE 1X4 AND
 INTO THE SUBSTRATE AS REQUIRED BY FBC
 1707.4.4.2.
  
 18) REVISE EXTERIOR DOOR DETAIL (7) ON A
 13. FASTENERS FOR THE DOOR FRAME ARE
 REQUIRED TO GO THROUGH THE 1X BUCK AND
 INTO THE SUBSTRATE PER 1707.4.4.2. FRAME
 CAN ATTACH DIRECTLY TO 2X BUCKS.
  
 19) THE DOOR AND WINDOW BUCK NOTE 5
 UNDER DOORS AND WINDOWS ON A14 DOES NOT
 CORRESPOND TO BUCK DETAILS ON A13.
 PLEASE REVISE.
  
 20) SPECIFY ON THE PLANS THAT THE
 STRUCTURE IS DESIGNED AS ENCLOSED, OPEN
 OR PARTICALLY ENCLOSED. SPECIFY THE
 INTERNAL PRESSURE COEFFICENT.
  
 21) REVISE WOOD TRUSS NOTE WT3 ON SN.
 THE BOTTOM CORD LIVE LOAD IS REQUIRED TO
 BE 10 PSF FOR ATTICS WITHOUT STORAGE PER
 FBC TABLE 1604.1.
  
 22) THE I.D. MARK ON S3 FOR THE SECTION
 7/S4 IS IN THE WRONG LOCATION. PLEASE
 CORRECT. SEE MARKS ON PLAN.
  
 23) THE BALCONY PEIRS ARE LABELED AS MP1
 ON S3 AND MC1 ON S7. PLEASE CORRECT.
  
 24) ON THE TRUSS ANCHOR SCHEDULE ON S7 T
 HE UPLIFT CAPACITIES FOR THE META 16 (C)
 AND HETA 20 (E) ARE HIGHER THAN THE
 2004 CATALOG VALUES THAT DO NOT INCLUDE
 THE ONE-THIRD INCREASE ON THE STEEL
 CALCULATIONS. PLEASE REVISE.
  
 25) ON S1 THE TC3 COLUMN IS SPECIFIED ON
 THE SOUTH ELEVATION BETWEEN THE TWO
 WINDOWS WHICH ARE 10" APART. SHOULD THIS
 BE A TC1 COLUMN.
  
 26) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT STATE PRODUCT APPROVALS FOR
 WINDOWS, DOORS, ROOFING, OVERHEAD
 GARAGE DOORS, STORM PANELS, TRUSS
 CONNECTORS, ETC.
  
 27) THE OWNER AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORM.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-16 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 10:20 Rev Time 0.50
Received By dpalmer Date 2004-09-16 Time 10:10 Sent To P
Notes
2004-09-16 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SEE TITLE BLOCK FOR
 ARCH FIRM.
 FIRST SET OF PLANS HAS DANAN GROUP INC.
 AND SECOND/NEWER PLANS SHOWS SEHRES &
 DANAN ARCH & DESIGN.?
 PLEASE CORRELATE PLANS WITH CORRECT
 FIRM.
 PLEASE ALSO INCLUDE ALL REQUIRED LICENSE
 #'S IN TITLE BLOCK PER FAC 61G1-16.004
 AND FS 481.219
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE PLAN NOTES MENTIONS
 FOR ARC FAULT PROTECTION FOR RECEPTS AND
 LTS IN BEDRMS.
 PLEASE SEE 210.12 2002 NEC SD'S ALSO
 REQUIRED.
 IT IS NOTED ON PANEL SCHEDULE W/** THAT
 BATH LTS ARE TO BE ARC FAULT ALSO.
 CIRCUIT B-18.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-08-30 Time 11:10 Rev Time 1.00
Received By btrobaug Date 2004-06-02 Time 06:54 Sent To M
Notes
2004-06-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE TWO ROOMS LABELED "MASTER
 BEDROOM", PLEASE MAKE CLARIFICATION FOR
 CIRCUITING ON PANEL SCHEDULES.
  
 2} THE DISCONNECTS FOR THE CONDENSERS
 DO NOT COMPLY WITH 110.26 FOR SPACING,
 PLEASE RELOCATE TO COMPLY WITH SAME AND
 440.14.
  
 3} ALTHOUGH NOTE #2 ON SHEET E1.01
 INDICATES INTERCONNECTED SMOKE
 DETECTORS REQUIRED BY NFPA-72 & FBC
 905.2, THE CIRCUIT DESIGNATIONS FOR
 A-18 & B-18 INDICATE TWO SEPARATE
 SOURCES OF POWER. PLEASE CLARIFY.
  
 4} ALSO NOTE THAT 210.12 STATES
 THAT ALL OUTLETS BE AFCI PROTECTED.
 THAT INCLUDES SMOKE DETECTORS LOCATED
 IN DWELLING UNIT BEDROOMS.
  
 5} THE RECEPTACLE LOCATED IN THE ATTIC
 ABOVE THE WALK IN CLOSET CANNOT BE ON
 THE BATH RECEPTACLE CIRCUIT PER
 210.11(C)(3). SHEET E1.02.
  
 6} THE SMOKE DETECTOR LOCATED IN THE
 HALLWAY OUTSIDE THE MASTER BEDROOM ON
 SHEET E1.02 MUST BE MOVED TO THE INSIDE
 OF THE ROOM (OTHER SIDE OF THE BUKHEAD)
 TO COMPLY WITH 8-1.4.1.6 NFPA-72.
  
 7} THERE IS A RECEPTACLE IN THE MASTER
 BEDROOM ON CIRCUIT B-26, THIS IS NOT AN
 ARC FAULT PROTECTED CIRCUIT PER THE
 PANEL SCHEDULE, AND THEREFORE DOES NOT
 COMPLY WITH 210.12.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-13 Time 11:06 Rev Time 0.00
Received By csiegber Date 2004-10-13 Time 11:06 Sent To M
Notes
2004-10-13 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-04 Cont ID  
Sent By mmclean Date 2004-10-12 Time 15:44 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 11:54 Sent To Z
Notes
2004-10-04 00:00:00TO Z/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 11:10 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 11:10 Sent To E
Notes
2004-08-30 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-26 Cont ID  
Sent By csiegber Date 2004-08-26 Time 10:28 Rev Time 0.00
Received By csiegber Date 2004-08-26 Time 10:28 Sent To Z
Notes
2004-08-26 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-22 Cont ID  
Sent By mmclean Date 2004-05-26 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2004-05-20 Time 14:19 Sent To  
Notes
2004-08-27 00:00:00RETUNED TO INCOMING - PLANNER JOSH WILL
 BE LAST TO REVIEW MM
2004-05-27 00:00:00TO SFD RACK/E
2004-05-20 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-10-21 Cont ID  
Sent By pkrauss Date 2004-10-21 Time 07:39 Rev Time 0.35
Received By pkrauss Date 2004-10-21 Time 07:27 Sent To  
Notes
2004-10-21 00:00:00DENIED:
 1.ONE SET OF PLANS MISSING PLAN SHEET
 M1.02 AND THE OTHER SET HAS 2 COPIES OF
 M1.02.PLEASE CORRELATE PLANS.
  
 2.SEE COMMENT #1 BY ELECTRICAL PLAN
 REVIEW, DEWEY PALMER.PROVIDE LICENSE
 NUMBERS AS REQUIRED PER FS 481.219 AND
 FAC 61G16.004.PLANS ARE OTHERWISE
 CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-14 Cont ID  
Sent By csiegber Date 2004-10-13 Time 11:06 Rev Time 0.45
Received By pkrauss Date 2004-06-14 Time 07:18 Sent To P
Notes
2004-06-14 00:00:00DENIED:
 1.RETURN AIR FROM THE MASTER BEDROOM
 INDICATED ON THE 1ST FLOOR IS NOT SIZED
 PROPERLY.ALL AIR INTO THE MASTER
 SUITE IS TO BE INCLUDED FOR A "TOTAL"
 OF SUPPLY AIR INTO THE SUITE.THE
 RETURN AIR JUMPER SHALL BE A MINIMUM OF
 1 1/2 TIMES THE TOTAL OF SUPPLY AIR.
 SEE THE ATTACHED SCHEDULE.
  
 2.PLAN SHEET M1.01, RETURN AIR INTO
 THE LIVING AREA - NO DUCT SIZE INDICATED
 IS THIS RETURN AIR FROM AHU 3, PLEASE
 CLARIFY.
  
 3.RETURN AIR REQUIRED FOM BEDROOM #2
 & 2ND FLOOR MASTER BEDROOM.
  
 4.PLAN SHEET M2.01 VENTILATION NOTE
 INDICATES PER TABLE 403.3.PLEASE
 INDICATE FRESH AIR INTAKE, DUCT SIZE
 AND MATERIAL.PLEASE NOTE, FRESH AIR
 SHALL NOT BE TAKEN FROM THE ROOF TOP IN
 A RESIDENTIAL APPLICATION PER 2001 FBC
 CHAPTER 13 SUB-CHAPTER 609.1.1BC.1 #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-09-18 Cont ID  
Sent By jleech Date 2004-09-18 Time 09:52 Rev Time 0.50
Received By jleech Date 2004-09-18 Time 09:52 Sent To B
Notes
2004-09-18 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTE #1.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 10:20 Rev Time 1.00
Received By jleech Date 2004-06-17 Time 17:08 Sent To B
Notes
2004-06-17 00:00:001.SHT. P1.01 2WAY CLEANOUTS REQUIRED
 WERE BUILDING DRAIN EXITS BUILDING.
 3" W/M DRAIN AND BAR SINK.
 2.HWR. IS SHOWN AS 3/4" AT PUMP IS SHOWN
 AS 1 1/2" HWR. PLEASE CLARIFY.
 3.SHT P1.02 NOTE # 6 PLEASE DELETE
 GAS RISER FROM NOTE. NO GAS RISER
 SHOWN ON PLANS.
 PLUMBING PLANREVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status F Date 2004-10-12 Cont ID  
Sent By mmclean Date 2004-10-12 Time 15:44 Rev Time 0.00
Received By mmclean Date 2004-10-12 Time 15:44 Sent To I
Notes
2004-10-12 00:00:00DENIED, APPLICANT NEED TO APPLY FOR A
 MINOR DSI AMENDMENT, SINCE ADOPTED SITE
 PLANS HAVE BEEN ALTERED.ALSO, FENCES &
 WALLS IN RESIDENTIAL DISTRICTS MAY NOT
 EXCEED 6FT IN HEIGHT. PLANNER, JOSH LONG
 822-1449. DSI AMENDMENT APPROVAL MUST
 BE SUBMITTED WITH PERMIT APPLICATION.
 CALLED OWNER ROBERT KNOTH NO ANSWER.
 2ND REQUEST.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-05-26 Cont ID  
Sent By csiegber Date 2004-10-04 Time 11:54 Rev Time 0.00
Received By mmclean Date 2004-05-26 Time 15:05 Sent To I
Notes
2004-05-26 00:00:00DENIED, APPLICANT NEED TO APPLY FOR A
 MINOR DSI AMENDMENT SINCE ADOPTED SITE
 PLANS HAVE BEEN ALTERED.ALSO, FENCES &
 WALLS IN RESIDENTIAL DISTRICTS MAY NOT
 EXCEED 5FT IN HEIGHT.APPLY FOR MINOR
 DSI AMENDMENT IS ENCLOSED WITH PERMIT
 APPLICATION.PLANNER, JOSH LONG
 REVIEWED 659-8031 MM