Plan Review Details - Permit 04050920
Plan Review Stops For Permit 04050920
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-23 Cont ID  
Sent By lsmith Date 2004-06-23 Time 13:30 Rev Time 1.00
Received By lsmith Date 2004-06-23 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-03 Cont ID  
Sent By vmahle Date 2004-06-23 Time 11:05 Rev Time 1.00
Received By lsmith Date 2004-06-03 Time 15:00 Sent To  
Notes
2004-06-03 00:00:00BUILDING PLAN REVIEW: FAILED:
  
 1.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
 1. ROOF MATERIALS
 2. GLASS BLOCK
 3. STRUCTURAL COMPONENTS (TRUSS
 BUCKETS, ETC.)
  
 2. SURVEY NEEDS TO SHOW NEW ADDITION
 WITH SETBACKS.
  
 3. NEED SEPARATE ROOFING PERMIT. ROOFER
 NEEDS TO SUBMIT STATE PRODUCT APPROVALS
 FOR METAL ROOF & COMPONENTS.
  
 4. NEED SEPARATE PERMITS FOR IRRIGATION.
  
 5. NEED SEPARATE PERMIT FOR DRIVEWAY
 APPROACH.
  
 6. NEED TO APPLY FOR AN EASEMENT
 RELEASE FORM FOR THE NEW FENCE.NEED
 FENCE PERMIT.
  
 7. SHOW A SEPARATE SECTION OF THE TIE-IN
 OF THE ROOF TRUSSES (SEE SECTION 4/2)
 WITH MORE DETAIL.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUIDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-23 Cont ID  
Sent By vmahle Date 2004-06-23 Time 11:04 Rev Time 0.00
Received By vmahle Date 2004-06-23 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-26 Cont ID  
Sent By csiegber Date 2004-06-18 Time 10:36 Rev Time 0.75
Received By btrobaug Date 2004-05-26 Time 11:07 Sent To P
Notes
2004-05-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW THE GROUNDING ELECTRODE SYSTEM
 ON THE RISER DIAGRAM FOR COMPLIANCE
 WITH 250.50 & 250.66.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 3} INDICATE CONDUCTOR AND CONDUIT SIZE
 AND TYPE FOR THE SERVICE PER 230.41 &
 42.
  
 4} INDICATE THE MEANS OF DISCONNECT FOR
 THE SERVICE PER 230.70.
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 6} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED.
  
 7} THE SMALL APPLIANCE CIRCUITS MUST BE
 CALCULATED @ 1500VA EACH PER 220.16(A).
  
 8} THERE MUST BEA DISCONNECTING MEANS AT
 THE A/C CONDENSER PER 440.14, AND A
 RECEPTACLE PER 210.63.
  
 9} A SMOKE DETECTOR MUST BE LOCATED IN
 THE SLEEPING ROOM PER 8-1.4.1.6.2
 NFPA-72.
  
 10} A RECEPTACLE MUST BE ADDED IN THE
 BEDROOM TO COMPLY WITH 210.52(A)(1)
 SPACING.
  
 11} THE DINING ROOM MUST BE ON A SMALL
 APPLIANCE CIRCUIT PER 210.52(B)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-18 Time 10:36 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 10:36 Sent To E
Notes
2004-06-18 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-17 Cont ID  
Sent By mmclean Date 2004-06-17 Time 16:01 Rev Time 0.00
Received By csiegber Date 2004-06-17 Time 10:20 Sent To Z
Notes
2004-06-17 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-25 Cont ID  
Sent By alange Date 2004-05-25 Time 13:15 Rev Time 0.00
Received By alange Date 2004-05-25 Time 13:15 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By mmclean Date 2004-05-24 Time 13:05 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 14:12 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By jleech Date 2004-05-29 Time 11:21 Rev Time 0.30
Received By pkrauss Date 2004-06-02 Time 14:22 Sent To B
Notes
2004-06-02 00:00:00NO MECHANICAL PLANS SUBMITTED.NOTE ON
 FLOOR PLAN 1 INDICATES A/C CONTRACTOR TO
 PROVIDE PLANS AND SPECIFICATIONS.
 ENERGY CALCULATIONS PROVIDED WITH
 BUILDING PERMIT

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-29 Cont ID  
Sent By btrobaug Date 2004-05-26 Time 13:14 Rev Time 0.25
Received By jleech Date 2004-05-29 Time 11:21 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-06-17 Cont ID  
Sent By mmclean Date 2004-06-17 Time 16:01 Rev Time 0.00
Received By mmclean Date 2004-06-17 Time 16:01 Sent To I
Notes
2004-06-17 00:00:00NOTE: MUST PULL A SEPARATE PERMIT FOR
 FENCE WITH UTILITY APPROVAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-05-24 Cont ID  
Sent By csiegber Date 2004-06-17 Time 10:20 Rev Time 0.00
Received By mmclean Date 2004-05-24 Time 13:05 Sent To I
Notes
2004-05-24 00:00:00DENIED, NEED TO PROVIDE ADDITION ON
 SURVEY WITH SETBACKS AND PROVIDE
 DIMENSION FOR NEW DRIVEWAY (MUST MEET
 1000SQ FT OR 75% OF LANDSCAPE IN THE
 FIRST 25FR FRONT SETBACK).CALLED CONTR