Plan Review Details - Permit 04050856
Plan Review Stops For Permit 04050856
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-16 Cont ID  
Sent By mjacobs Date 2004-07-16 Time 10:22 Rev Time 1.00
Received By mjacobs Date 2004-07-16 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-17 Cont ID  
Sent By mjacobs Date 2004-06-17 Time 14:49 Rev Time 2.00
Received By mjacobs Date 2004-06-17 Time 14:48 Sent To PC
Notes
2004-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT:04050856
 ADD:600 S. ROSEMARY AVE SUITE #140
 CONT:PEMBERTON BUILDERS,INC.
 TEL: (561)842-5137
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
  
  
 FIRST REVIEW
 ACTION: DENIED
  
 1)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (805)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-08 Cont ID  
Sent By dpalmer Date 2004-07-08 Time 13:47 Rev Time 0.33
Received By dpalmer Date 2004-07-08 Time 13:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-25 Cont ID  
Sent By dpalmer Date 2004-05-25 Time 12:16 Rev Time 0.75
Received By dpalmer Date 2004-05-25 Time 10:48 Sent To  
Notes
2004-05-25 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE TITLE BLOCK. THE
 CERTIFICATE OF AUTHORIZATION # SHOWN
 IS NOT LISTED WITH DBPR FOR KAMM CONSULT
 -ING INC. # 1689 SHOWN IS FOR ROY F JOHN
 S AND ASSOCIATES.
 PLEASE VERIFY LICENSE # AND CORRECT.
 FS 471.023, FAC 61G15-23.002
  
 2)NOTE: PLEASE SEE FS 471.025 AND FAC
 61G15-23.002 WHICH REQUIRES A SIGNATURE
 FOR THE ENGINEER OF RECORD. PLEASE
 SEE THIS REQUIRES A MIN OF FIRST AND
 LAST NAME. INITIALS ARE NOT PERMITTED.
  
 3)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWERS AS THEY MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 4)NOTE: PLEASE REMOVE ALL OLD VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 TWO SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-08 Cont ID  
Sent By nmccray Date 2004-07-08 Time 15:50 Rev Time 0.00
Received By nmccray Date 2004-07-08 Time 15:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-20 Cont ID  
Sent By mcarsill Date 2004-05-20 Time 14:34 Rev Time 0.00
Received By mcarsill Date 2004-05-20 Time 14:34 Sent To  
Notes
2004-05-20 00:00:001) PLEASE DISPLAY TENANT DEMISING WALLS.
  
 2) PLEASE INDICATE ALL REQUIRED EXIT
 SIGNS AND EMERGENCY LIGHTS.
  
 3) PLEASE DISPLAY ALL EXISTING OR
 NEW FIRE EQUIPMENT. THESE WOULD INCLUDE
 FIRE ALARM DEVICES AND PORTABLE FIRE
 EXTINGUISHERS.
  
 4) THE SCOPE OF WORK ON THE PLANS
 DO NOT CORRESPOND TO THE PERMIT
 APPLICATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-07-28 Time 11:21 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 11:21 Sent To M
Notes
2004-07-28 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 16:42 Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 16:42 Sent To  
Notes
2004-06-28 00:00:00TO COMM BD#33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-05-20 Time 09:00 Rev Time 0.00
Received By mjacobs Date 2004-05-20 Time 09:00 Sent To PC
Notes
2004-05-20 00:00:00TO COMM BD#36

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-08 Cont ID  
Sent By csiegber Date 2004-07-28 Time 11:21 Rev Time 0.40
Received By pkrauss Date 2004-07-06 Time 14:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-09 Cont ID  
Sent By pkrauss Date 2004-06-09 Time 06:48 Rev Time 0.45
Received By pkrauss Date 2004-06-09 Time 06:43 Sent To  
Notes
2004-06-09 00:00:00DENIED:
 1.CERTIFICATE OF AUTHORIZATION # ON
 THE TITLE BLOCK IS NOT CORRECT ACCORDING
 TO DBPR.PLEASE CORRECT.
  
 2.PLANS DO NOT INDICATE PIPING
 MATERIAL FOR THE CONDENSATE.NO
 COMBUSTIBLES ALLOWED ABOVE THE CEILING
 IN THE RETURN AIR PLENUM AS NOTED ON
 PLAN SHEET M1.0 OR M2.0.
  
 3.PLANS DO NOT INDICATE OUTSIDE AIR
 FOR THE NEW FCU-2.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-21 Cont ID  
Sent By kstevens Date 2004-07-17 Time 05:56 Rev Time 1.75
Received By kstevens Date 2004-07-17 Time 05:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By kstevens Date 2004-06-15 Time 12:06 Rev Time 1.50
Received By kstevens Date 2004-06-12 Time 17:27 Sent To  
Notes
2004-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FILTERS MUST MEET THE REQUIREMENTS OF
 NSF 42. SUBMIT MANUF. SPECIFICATIONS
 SHOWING COMPLIANCE. SECTION 611.1.
 2) SHTS P2.0 & P3.0 SUBMIT A SANITARY &
 A WATER RISER DIAGRAM IN ISOMETRIC FORM.
 SHOW ALL PIPE SIZES, WATER HAMMER ARRES-
 TORS REQUIRED BY SECTION 604.9 LOCATED
 IN ACCORDANCE WITH PDI-WH 201. RISER
 DIAGRAMS SHALL REFLECT THE FLOOR PLAN &
 ACTUAL INSTALLATION. SECTION 104.3.1.1.
 3) SHTS P2.0 & P3.0 PLUMBING SUPPLY PLAN
 NOTES #2 INDICATE THE WATER HEATER SHALL
 BE INSTALLED OVER THE MOP SINK. DETAIL
 #2 SHOWS THE SAME. FLOOR PLAN SHOW MOP
 SINK AND WATER HEATER IN DIFFERENT LOCA-
 TIONS. PLEASE CLARIFY, CORRELATE PLANS.
 SECTION 104.2.1.
 4) SHT P2.0 PLUMBING SCHEDULE: UNABLE TO
 LOCATE P047 FLOOR DRAIN, P360 FAUCET,
 P801 DRAIN GRAT, ADL 6 ICE BIN, ADL 7
 DIPPER WELL & ADL 8 WATER TOWER ON LAY-
 OUT FLOOR PLAN. PLEASE CLARIFY, CORRELA-
 TE PLANS. - INDICATE TYPE OF FIXTURE
 ADL 10 IS. NOT SHOWN ON SCHEDULE. SECT-
 ION 104.2.1/
 4) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]