| Plan Review Stops For Permit 04050820 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-10-21 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-26 |
Time |
10:19 |
Rev Time |
1.50 |
| Received By |
lsmith |
Date |
2004-10-21 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2004-10-21 00:00:00 | BUILDING PLAN REVIEW: | | | | | | 1. SUBMIT ENERGY CODE FORM SIGNED BY | | | OWNER/AGENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-14 |
Time |
07:43 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2004-06-08 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2004-06-08 00:00:00 | BUILDING PLANS REVIEW FAILED: | | | | | | 1.PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATIONPLEASE SEE THE STATE WEBSITE | | | AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | A. ROOF MATERIALS | | | B. STRUCTURAL COMPONENTS (TRUSS STRAPS, | | | ETC. | | | C. WINDOWS & DOORS BY MARVIN | | | | | | 2. SHOW ATTIC ACCESS | | | | | | 3. SHOW DESIGN PRESSURES ON ALL DOORS & | | | WINDOWS. | | | | | | 4. NOTES: TIMBER AND WOOD REFERENCES | | | STANDARD BUILDING CODE.CHANGE TO | | | FLORIDA BUILDING CODE. | | | | | | 5. S1-01.1 SPECIFY SIZE OF STEEL REBAR | | | IN FOOTINGS. | | | | | | SEE SAMPLE FLORIDA BUILDING PRODUCT | | | APPROVALS ATTACHED. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-09-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-09-21 |
Time |
12:49 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-09-21 |
Time |
12:30 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-05-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-15 |
Time |
14:53 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-05-24 |
Time |
07:17 |
Sent To |
P |
|
| Notes |
| 2004-05-24 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | | | | 2} PLEASE ADD A RECEPTACLE AT THE REAR | | | OF THE HOUSE TO COMPLY WITH 210.52(E). | | | | | | 3} PLEASE NOTE THAT THE ARCHITECTS | | | SIGNATURE IS REQUIRED ON HIS/HER SEAL | | | PER 61G1-16.003. INITIALS ARE NOT | | | ACCEPTABLE. ALSO NOTE THE FIRMS LICENSE | | | NUMBER IS REQIRED IN THE TITLE BLOCK IN | | | THE TITLE BLOCK PER 61G1-16.004. | | | | | | 4} RECEPTALES ARE MISSING IN THE KITCHEN | | | ON THE COUNTERTOP AND THE PENINSULAR PER | | | 215.52(C)(1) & (4). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2004-05-19 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2004-05-19 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-05-19 00:00:00 | APPROVED PER E BOWERS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-10-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-26 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-26 |
Time |
10:19 |
Sent To |
B |
|
| Notes |
| 2004-10-26 00:00:00 | TO LS DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-09-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-15 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-15 |
Time |
14:53 |
Sent To |
E |
|
| Notes |
| 2004-09-15 00:00:00 | TO BT DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-05-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-20 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-20 |
Time |
14:16 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-05-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-05-20 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-19 |
Time |
13:49 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-10-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-10-08 |
Time |
15:25 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-10-05 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2004-10-05 00:00:00 | PROVISO: | | | PROVIDE AS-BUILT INDICATING NEW DUCT & | | | GRILLE SIZE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-09-21 |
Time |
12:49 |
Rev Time |
0.15 |
| Received By |
pkrauss |
Date |
2004-06-02 |
Time |
11:08 |
Sent To |
B |
|
| Notes |
| 2004-06-02 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE A COMPLETED FORM 600C | | | PER 2001 FBC CHAPTER 13 SUB-CHAPTER 6, | | | SECTION 600.1 METHOD C & 600.1.C. | | | | | | 2.INDICATE ON THE PLAN IF THE ADDITION | | | WILL HAVE SUPPLY AIR FROM THE EXISTING | | | A/C SYSTEM.INDICATE ANY NEW DUCTWORK | | | AND GRILLES.SHOW SIZE, MATERIAL AND | | | LAYOUT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-10-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-14 |
Time |
07:42 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-10-13 |
Time |
18:51 |
Sent To |
B |
|
| Notes |
| 2004-10-14 00:00:00 | PASSED/PROVISO | | | | | | VENTS ARE REQUIRED AT THE KITCHEN SINKS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-05-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-05-24 |
Time |
09:01 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2004-05-29 |
Time |
10:42 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-10-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-10-08 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-10-08 |
Time |
15:25 |
Sent To |
M |
|
| Notes |
| 2004-10-08 00:00:00 | RE-STAMP PLANS FOR ADDITION & PORCH ONLY |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-05-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-19 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-05-20 |
Time |
13:29 |
Sent To |
I |
|
| Notes |
| 2004-05-20 00:00:00 | APPROVING ADDITION & PORCH ONLY |
|
|