Plan Review Details - Permit 04050773
Plan Review Stops For Permit 04050773
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-22 Cont ID  
Sent By shill Date 2004-06-22 Time 13:07 Rev Time 1.00
Received By shill Date 2004-06-22 Time 12:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-17 Cont ID  
Sent By shill Date 2004-06-17 Time 13:52 Rev Time 1.50
Received By shill Date 2004-06-17 Time 13:13 Sent To  
Notes
2004-06-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THE DOCTOR'S TOILET SHALL BE
 ADAPTABLE FBC11-4.1.3(11) (GRAB BAR
 BACKING, SINK), PROVIDE A DETAIL. CLEAR
 FLOOR SPACE REQUIRED FBC11-4.23.3.
  
 3.)SHOW CLEAR FLOOR SPACE FOR
 FIXTURES.
  
 4.)DOORS SHALL NOT SWING INTO THE
 FLOOR SPACE REQUIRED FOR ANY FIXTURE
 FBC11-4.23.2 (HANDICAP TOILET).
  
 5.)RE: THE NEW CASED OPENINGS, PROVIDE
 INFORMATION ABOUT THE WALL, IS A HEADER
 REQUIRED?
  
 6.)THE GRAB BAR AT THE WATER CLOSET IS
 TO BE 36" MIN, FBC 11-FIGURE 29.
  
 7.) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-06 Cont ID  
Sent By btrobaug Date 2005-04-06 Time 12:52 Rev Time 0.50
Received By btrobaug Date 2005-04-06 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-22 Cont ID  
Sent By dpalmer Date 2004-06-22 Time 19:30 Rev Time 0.33
Received By dpalmer Date 2004-06-22 Time 19:30 Sent To  
Notes
2004-06-22 00:00:00********** PROVISO/ REVISIONS ********
  
 1)NOTE: PLEASE SEE 600.5 FOR MISSING
 REQUIRED SIGN CIRCUIT.
  
 2)NOTE: PLEASE PROVIDE ALL CIRCUITING
 ON PLANS AND SUBMIT W/ PANEL SCHEDULE
 BEFORE FINAL ELECTRICAL INSPECTION.
 THIS MUST BE SUBMITTED TO CITY FOR
 REVIEW AND STAMPING TO BE BACK ON
 JOBSITE FOR INSPECTION.
  
 ** PLEASE NOTE, ALL OTHER REVSIONS TO
 PLANS/JOBSITE MUST BE SUBMITTED FOR
 REVIEW AND STAMPING BEFORE ROUGH ELECTR-
 -ICAL INSPECTION IS CALLED IN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-20 Cont ID  
Sent By mjacobs Date 2004-06-21 Time 16:31 Rev Time 0.33
Received By dpalmer Date 2004-05-20 Time 14:47 Sent To  
Notes
2004-05-20 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE(
 S) TO BE SUBMITTED.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/LTS.
  
 2)NOTE: PLEASE SHOW NEW OR EXSITNG
 SIGN CIRCUIT PER 600.5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-05-20 Cont ID  
Sent By mcarsill Date 2004-05-19 Time 13:10 Rev Time 0.00
Received By mcarsill Date 2004-05-19 Time 13:10 Sent To  
Notes
2004-05-19 00:00:001) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS IS TO BE REMOVED DAILY FROM
 THE SITE.
  
 3) ENSURE THAT PORTABLE FIRE
 EXTINGUISHERS ARE PRESENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 13:49 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 13:49 Sent To E
Notes
2005-03-31 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-21 Cont ID  
Sent By mjacobs Date 2004-06-21 Time 16:30 Rev Time 0.00
Received By mjacobs Date 2004-06-21 Time 16:30 Sent To  
Notes
2004-06-21 00:00:00SENT TO COMM BD#21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-17 Cont ID  
Sent By shill Date 2004-06-17 Time 15:17 Rev Time 0.00
Received By shill Date 2004-05-19 Time 07:56 Sent To  
Notes
2004-05-19 00:00:00TO COMM BD#2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-08 Cont ID  
Sent By pkrauss Date 2004-06-08 Time 07:27 Rev Time 0.25
Received By pkrauss Date 2004-06-08 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-08 Cont ID  
Sent By kstevens Date 2004-07-08 Time 12:28 Rev Time 1.00
Received By kstevens Date 2004-07-08 Time 12:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 10:20 Rev Time 0.50
Received By kstevens Date 2004-06-05 Time 10:20 Sent To  
Notes
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT 1 DEMO NOTES #4 & #5 - NO DEAD
 ENDS ALLOWED IN THE REMOVAL OF ANY PART
 OF THE DRAINAGE SYSTEM. SECTION 704.5
 2) SHT 3 GENERAL PLUMBING NOTES #17, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE NOTE. SECTION 604.9
 3) SHT 3 WATER HEATER SHALL BE ACCESSIB-
 LE. SUBMIT A DETAIL. - SUBMIT A DETAIL
 FOR THE PIPING OF THE T/P RELEIF VALVE
 DISCHARGE AND THE EMERGENCY HEATER PAN
 DRAINAGE PIPING. SECTIONS 501.4 AND
 104.2.1
 4) SHT 3 THERMAL EXPANSION CONTROL IS
 REQUIRED FOR THE WATER HEATER. SECTION
 607.3.2.
 5) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. (ALSO SEE SECTION 410.1)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]