Plan Review Details - Permit 04050770
Plan Review Stops For Permit 04050770
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-11-10 Cont ID  
Sent By mjacobs Date 2004-11-10 Time 11:58 Rev Time 2.00
Received By mjacobs Date 2004-11-10 Time 11:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-10-27 Cont ID  
Sent By mjacobs Date 2004-10-27 Time 15:47 Rev Time 2.50
Received By mjacobs Date 2004-10-27 Time 15:47 Sent To  
Notes
2004-10-27 00:00:00BUILDING PLAN REVIEW
 PERMIT:04050770
 ADD:2175 PALM BEACH LAKES BLVD
 CONT:TAYCON CONST. MANAGEMENT INC.
 TEL: (561)622-2699
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION:DENIED
  
  
 1) FL. BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PLEASE PROVIDE TWO COPIES
 (3COPIES IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PROCUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS.
 A) WINDOWS: PLEASE HAVE THE APPLICATION
 PROVIDED COMPLETE BY THE MANUFACTURE
 FOR THE WINDOWS SUBMITTED. IF NOT, YOU
 MAY SUBMIT A STATE APPROVE WINDOW
 PRODUCT.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
 YOU CAN ASK IF THERE IS ANY CREDIT FROM
 THE PREVIOUS BUILDING WHICH WAS DEMO.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEW
 TEL: (561) 805-6726
 FAX: (561) 659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-08-13 Cont ID  
Sent By mjacobs Date 2004-08-13 Time 09:49 Rev Time 1.00
Received By mjacobs Date 2004-08-13 Time 09:49 Sent To  
Notes
2004-08-13 00:00:008-13-04 SUBMITTALS MJACOBS
 FIREDOOR,LLC SWINGING (ILLEGIBLE PAGES)
 ROOFING TILES (INDICATE FASTEN SCHEDULE)
 SIMPSON STRONG TIE (OK)
 BUILT-UP ROOF SYSTEM FOR STEEL DECK
 SEE EXPIRATION DATE
 ROOFING INSULATION FL618 (OK)
 GLASS BLOCK WINDOW (OK)
 PLEASE SEE FIRST REVIEW NOTES FOR
 ADDITIONAL SUBMITTALS.
  
 SUBMITTALS REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-12 Cont ID  
Sent By mjacobs Date 2004-08-12 Time 15:30 Rev Time 4.00
Received By mjacobs Date 2004-08-12 Time 15:30 Sent To  
Notes
2004-08-12 00:00:00BUILDING PLAN REVIEW
 PERMIT:04050770
 ADD:2175 PALM BEACH LAKES BLVD
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 PLEASE SEE 1ST REVIEW #1
  
 2) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.REPORTS NEED ORIGINAL SIGNSTURE
 AND NEED TO SEALED.
 SEE IST REVIEW #2.
  
 3 ) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 ALSO SEE FLORIDA STATUES 481.221 AND
 F.A.C. 61G-16.003
  
 4) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 ON ROOFING DETAILS. PRESSURES ZONE 3
 SEE FBC TABLE 1606.2B. ROOF ANGLE 10-30
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS/STORE FRONT
 B)EXTERIOR DOORS METAL/GLASS SUBMITAL
 REPORT EXPEIRED. PROVIDE GLASS DOOR
 REPORTS.
 C)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
 D) FBC 1707.4.5.2 MULLIONS SHALL BE
 DESIGNED TO TRANSFER THE DESIGN PRESSURE
 LOAD APPLIED TO THE WINDOW OR DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBTRATE
 INFORMATION WAS NOT SUBMITTED. (13,14)
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE
 USED FOR ALL NON-IMPACT GLAZING.
 FBC. 1606.1.4.
  
 8)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 THE REFERENCE SECTION YOU GAVE ON
 SHEET A9 IS NOT IN OUR JURISDICTION.
 PLEASE SEE F.A.C. CH.4-13
  
 9) SHEET A-6A CANOPY PLAN. PLEASE
 SUBMIT ENGINEERING AND STRUCTUAL
 DRAWINGS FOR CONSTRUCTION CANOPY
 SEE NOTE #16 FIRST REVIEW.
  
 10)LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEW
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-21 Cont ID  
Sent By csiegber Date 2004-08-11 Time 15:48 Rev Time 8.00
Received By mjacobs Date 2004-06-18 Time 13:50 Sent To PC
Notes
2004-06-18 00:00:00BUILDING PLAN REVIEW
 PERMIT:04050770
 ADD: 2175 PALM BEACH LAKES BLVD
 CONT:FLORIDA GENERAL CONTRACTOR INC
 TEL: (561)364-4988
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITEY KNOWN, OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.SHEET A-2 INDICATES REPORT BY
 ARDAMEN 3/13/04
  
 3)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4) F102.1 WPB AMMENDMENTS, FIRE
 DISTRICTSHEET A-1 NO TYPE VI
 CONSTRUCTION ALLOW-ED. A) NO EXTERIOR
 WALLS CAN BE MADE OF COMBUSTIBLE
 MATERIALS,( PLYWOOD SHEATH- ING & WOOD
 FRAMING MEMBERS)
  
 5) FBC* F102.2.7ARCHITECTURAL TRIM,
 ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
 SEE A-5/ A-10 PECKY CYPRESS CORBOL
  
 6) FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 7) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 ON ROOFING DETAILS. PLEASE INDICATE
 WHICH DETAIL WILL BE USED AS PER SHEET
 A-8A DETAIL #2.(PLYWOOD DECK OR METAL
 DECK. ALSO INSULATION ATTATCHMENT)
  
 8) 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE
 ACCOMPLISHED BY DESIGN OR BY
 APPLICATION OF
 SECTION 301.13.1. (NO DIMENTIONS SHOWN)
 SHEET A-8A CONDENSING UNIT DETAIL.
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) GLASS BLOCK
 C)MULLIONS
 D) EXTERIOR DOORS
 E) STORM SHUTTERS/IF IMPACT GLAZING IS
 NOT USED,
 F) ROOF ASSEMBLIES/CEMENT TILE/INSUL
 MODIFIED ROOFING/90LB
 G) TRUSS ANCHOR
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE
 USEDFOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 12) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE
 INSTALLATIONSCHEDULE SUMMARIZING &
 IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL
 PRES-SURE ZONES, SLAT TYPES, ETC.,
 SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 13) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 14) 1707.4.5.2 MULLIONS SHALL BE
 DESIGN-ED TO TRANSFER THE DESIGN
 PRESSURE LOADSAPPLIED BY THE WINDOW OR
 DOOR ASSEMBLIESTO THE ROUGH OPENING
 SUBTRATE.
  
 15) A10 DETAIL#2 SHOW MORE DETAILS FOR
 CONNECTION TO BAR JOISTS. IF JOISTS ARE
 FIVE FEET O.C (5'O.C) PROVIDE DOCUMENTS
 OR REPORTS ON SPAN DISTANCE, FOR THE
 GAUGE OFTOP TRACKBEING USED AND
 HOW IT IS FASTENED TO THE BAR JOISTS.
  
 16) SHEET A-6A CANOPY PLAN.PLEASE
 SUBMITENGINEERING AND STRUCTUAL
 DRAWINGS FOR
 CONSTRUCTION OF CANOPY.
  
 17) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, AND EXTERIOR COMPONENT
 AND CLADDING DESIGN WIND PRESSURES.ALSO
 PLEASE SPECIFY THE TYPE OF BOLTS AND
 ANCHORS TO USED ON COSTRUCTION OF CANOPY
  
 18) F102.2.11 EXTERIOR PLASTIC VENEER IS
 NOT PERMITTED IN THE FIRE DISTRICT.
 PLEASE AMEND PLANS.
  
  
  
 NF

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-26 Cont ID  
Sent By dpalmer Date 2004-10-26 Time 10:36 Rev Time 0.50
Received By dpalmer Date 2004-10-26 Time 10:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-16 Cont ID  
Sent By dpalmer Date 2004-08-16 Time 15:34 Rev Time 0.75
Received By dpalmer Date 2004-08-16 Time 15:03 Sent To  
Notes
2004-08-16 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE PANEL "B" IS STILL
 SHOWN W/ 20A OCP AND #12 TO A PANEL
 SHOWN WITH A 71A LOAD??
 PLEASE SEE THIS WAS ON ORIGINAL NOTES.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM INDICAT
 -ES EQUIPMENT GROUNDING CONDUCTORS
 INSTALLED BEFORE AND AFTER FIRST MEANS
 OF DISCONNETC. EQUIPMENT GRNDS ARE ONLY
 PERMITTED AFTER THE FIRST MEANS OF DISC.
 250.6,250.24
 PLEASE ADJUST RISER.
  
 3)NOTE: PLEASE SEE A-17 WHICH CONTAINS
 A TITLE BLOCK FOR "COBURN & ASSC INC".
 PLEASE SEE THE ELECTRICAL PLANS DO NOT
 CONTAIN THIS SAME TITLE BLOCK FROM
 CONBURN & ASSC? FS 553.79 PE REQUIRED.
 PLEASE ALSO SEE FAC 61G15-23.002, WHICH
 ALSO REQUIRES TO HAVE THE PRINTED NAME
 AND LICENSE #(PE) INCLUDED IN TITLE
 BLOCK.
  
 4)NOTE: PLEASE SEE RISER INDICATES A
 PANEL CW AND NO PANEL SCHEDULE WAS
 SUBMITTED.?
  
 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 LOAD SHOWN APPEARS TO BE CONNECTED LOAD?
  
 PLEASE SEE POSSILE COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By jleahy Date 2004-06-02 Time 07:30 Rev Time 2.00
Received By jleahy Date 2004-06-02 Time 07:23 Sent To  
Notes
2004-06-02 00:00:001) NEED TO SHOW CLASS LOCATIONS ON A
 SITE PLAN, PER 500.4 OF THE NEC
  
 2) PUMPS NOT SHOWN ON DRAWINGS FOR
 LOCATION
  
 3) SHOW LOCATION OF EMERGENCY SWITCH
  
 4) RISER SHOWS #12 FEEDING PANEL "B"
 PANEL "B" HAS A LOAD OF 44 AMPERES?
  
 5) NEED EQUIPMENT SCHEDULE FOR FAST FOOD
 AREA, THIS LOOKS LIKE A KITCHEN IF SO
 SHOW GFCI PROTECTION FOR ALL 125V
 15,20ACIRCUITS.
  
 6) GAS PUMP PANEL WHICH ONE ON THE
 RISERIS IT?????
  
 7) CAR WASH IS A WET LOCATION NEED TO
 NOTE ABOUT 1/4" OF AIR SPACE BETWEEN
 WALLSAND EQUIPMENT.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-08-13 Cont ID  
Sent By mamini Date 2004-08-30 Time 09:11 Rev Time 1.00
Received By mamini Date 2004-08-13 Time 09:10 Sent To  
Notes
2004-08-30 00:00:00PASSED WITH PROVISOS:
 1. PLEASE SUBMIT CALCULATION FOR
 PERVIOUS, IMPERVIOUS AND BUILDING AREA.
 2. SHEET 2 OF 6 SHOWS 750 GAL. GREASE/
 WATER SEPARATOR IN SEWER LINE FROM THE
 PROPOSED CAR WASH, THIS SHOULD BE OIL/
 WATER SEPARATOR.
 3. POLLUTION/ EROSION PLANS MUST BE
 INSTALLED PRIOR TO BEGINNING ANY WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-05-21 Cont ID  
Sent By mamini Date 2004-05-21 Time 08:51 Rev Time 1.00
Received By mamini Date 2004-05-21 Time 08:50 Sent To  
Notes
2004-05-21 00:00:00FAILED:
 1. CIVIL PLANS MUST BE APPROVED BY THE
 PUBLIC UTILITIES & ENGINEERING FOR ALL
 THE CONNECTIONS FOR SERVICES AND FOR THE
 LOCATION OF METERS, BACKFLOWS, ETC.
 PROIR TO CONSTRUCTION SERVICES'S
 APPROVAL, 659-8040 ATT: MANNY GONZALEZ
 2. PLEASE SUBMIT CALCULATIONS FOR THE
 PROPOSED STORM WATER TO US OR TO STEVE
 SARLEY AT PUBLIC UTILITIES & ENGINNERING
 ,HOWEVER PERVIOUS , IMPERVIOUS, BUILDING
 AREA CALCULATION FOR THE ENTIRE SITE,
 SIGNED & SEALED MUST BE SUBMITED TO US.
 3. WORK WITHIN PUBLIC R.O.W REQUIRES
 APPROVAL AND SEPARATE PERMIT FROM PB
 COUNTY AND CITY ENGINEER'S OFFICE PROIR
 TO BEGIN WORK.
 4. PLEASE NOTE THAT SITE PLAN HAS NOT
 BEEN APPROVED BY THE PLANNING & ZONING.
 5. SHOW DIMENSIONS FOR THE DUMPSTER
 ENCLOSURE, IF TO BE PICKED UP BY THE
 CITY, 12'-6" OPENING BETWEEN GATE POSTS
 AND 12'-0" DEEP.DETAILS ON SHEET A-12
 ARCHITECTURAL MUST BE REVISED.
 6. PLEASE VERIFY, 150 GALLON OIL/WATER
 SEPARATOR AS SHOWN ON SEWER LINE FROM
 THE CONVENIENCE STORE, SHOULD THIS BE A
 GREASE/ WATER SEPARATOR?
 7. PLEASE CONTACT RODNEY COMPO AT
 837-4051 EXT. 4074 REGARDING THE SIZE,
 LOCATION INSTALLATION, INSPECTION AND
 SHOP DRAWING REQUIREMENTS FOR THE
 PROPOSED OIL,GREASE / WATER SEPARATORS,
 NOTE TO G.C.
 8. SIGNS AND MARKINGS SHOULD BE SHOWN ON
 CIVIL PLANS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-10-14 Cont ID  
Sent By nmccray Date 2004-10-14 Time 13:06 Rev Time 0.00
Received By nmccray Date 2004-10-14 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-08-13 Cont ID  
Sent By mcarsill Date 2004-08-13 Time 14:05 Rev Time 0.00
Received By mcarsill Date 2004-08-13 Time 14:01 Sent To  
Notes
2004-08-13 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR UNDERGROUND FUEL TANKS. PLANS
 ARE TO BE SUBMITTED TO PBC DERM FOR
 STAMPING PRIOR TO SUBMITTING TO
 CITY.
  
 2) DOOR # 1 TO HAVE SIGNAGE 1" LETTERS
 "DOORS TO REMAIN UNLOCKED DURING
 BUSINESS HOURS".
  
 3) EMERGENCY SWITCHES NOTE ON PAGE
 A-17 NEEDS TO BE FINALIZED.
  
 4) PLEASE INDICATE LOCATIONS OF
 WARNING SIGNS AND WORDING FOR THESE
 SIGNS AT THE FUEL DISPENSERS.
  
 5) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATIONS AT FUELING AREA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-25 Cont ID  
Sent By mcarsill Date 2004-05-25 Time 10:01 Rev Time 0.00
Received By mcarsill Date 2004-05-25 Time 10:00 Sent To  
Notes
2004-05-25 00:00:001) ALL DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3) THE PLANS INDICATE TYPE VI
 CONSTRUCTION. TYPE VI CONSTRUCTION IS
 NOT ALLOWED IN THE CITY FIRE LIMITS.
 PLEASE SEE APPENDIX F, LOCAL AMENDMENTS
 TO THE FLORIDA BUILDING CODE. PLEASE
 AMEND THE PLANS.
  
 4) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWING. A MINIMUM OF 6"
 HIGH NUMBERS IS REQUIRED.
  
 5) WOOD SHOWN ON PLANS. FIRE RATED
 WOOD IS ALLOWED IN THE CITY FIRE LIMTS.
  
 6) PLEASE INDICATE INTERIOR FINISH
 FOR WALLS AND CEILINGS.
  
 7) EFIS NOTED ON CANOPY. ALL
 ARCHITECTURAL TRIM LOCATED IN THE
 FIRE LIMITS SHALL BE NONCOMBUSTIBLE.
  
 8) PLEASE INDICATE ALL WARNING SIGNS
 AND OTHER SAFETY EQUIPMENT PLANNED FOR
 THE FUEL DISPENSING PUMPS.
  
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FUEL TANK INSTALLATIONS.
  
 10) PLEASE INDICATE LOCATIONS OF ALL
 PORTABLE FIRE EXTINGUISHERS.
  
 11) FUEL TANKS TO COMPLY WITH NFPA 30A.
  
 12) STATION TO COMPLY WITH NFPA 30A.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 10:01 Sent To B
Notes
2005-10-04 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 16:34 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 16:34 Sent To I
Notes
2005-09-21 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-01 Cont ID  
Sent By lmartine Date 2005-08-29 Time 09:23 Rev Time 0.00
Received By lmartine Date 2005-08-29 Time 09:22 Sent To P
Notes
2005-09-01 00:00:00REVISON/TCO
 SENT TO PLUMB.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-11 Cont ID  
Sent By adarroug Date 2005-05-11 Time 10:44 Rev Time 0.00
Received By adarroug Date 2005-05-11 Time 10:44 Sent To M
Notes
2005-05-11 00:00:00TO "PKRAUSS" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 16:34 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 16:34 Sent To B
Notes
2004-11-05 00:00:00TO MJ DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-27 Cont ID  
Sent By ptjomsto Date 2004-10-27 Time 11:54 Rev Time 0.00
Received By ptjomsto Date 2004-10-27 Time 11:54 Sent To  
Notes
2004-10-27 00:00:00SUBMITTAL GIVEN TO KEN STEVENS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-11 Time 15:48 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 15:48 Sent To B
Notes
2004-08-11 00:00:00TO MJ DESK/SUBMITTALS PA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 14:07 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 14:07 Sent To  
Notes
2004-08-03 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-21 Cont ID  
Sent By mmclean Date 2004-06-02 Time 16:21 Rev Time 0.00
Received By mjacobs Date 2004-05-18 Time 14:44 Sent To  
Notes
2004-05-18 00:00:00TO COMM BD#17

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-09-22 Cont ID  
Sent By tgordon Date 2005-09-22 Time 11:06 Rev Time 0.30
Received By tgordon Date 2005-09-22 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-06-01 Cont ID  
Sent By pkrauss Date 2005-06-01 Time 06:59 Rev Time 0.25
Received By pkrauss Date 2005-06-01 Time 06:59 Sent To  
Notes
2005-06-01 00:00:00DENIED:
 SEPARATE MECHANICAL PERMIT AND FEES
 REQUIRED FOR THE WALK-IN COOLER PERMIT.
 SEE COMMENTS DATED 10-14-04.
  
 IF YOU HAVE ANY QUESITSONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-10-14 Cont ID  
Sent By pkrauss Date 2004-10-14 Time 11:46 Rev Time 0.45
Received By pkrauss Date 2004-10-14 Time 11:46 Sent To  
Notes
2004-10-14 00:00:00ADDITIONAL PERMITS REQUIRED FOR THE
 FUEL TANKS/PIPING AND WALK-IN COOLERS.
 UNDERGROUND FUEL TANKS APPROVED BY
 DERM, CHIP GREENE.PLEASE PROVIDE
 MANUFACTURER CUT SHEETS FOR THE WALK-IN
 COOLERS WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-08-26 Cont ID  
Sent By pkrauss Date 2004-08-26 Time 06:54 Rev Time 0.40
Received By pkrauss Date 2004-08-26 Time 06:34 Sent To  
Notes
2004-08-26 00:00:00DENIED:
 1. PLEASE PROVIDE ORIGINAL PERMIT WITH
 RESUBMITTAL.
  
 2. PLANS FOR THE REMOVAL OR INSTALLATION
 OF FUEL TANKS SHALL HAVE PRIOR APPROVAL
 BY PBC DERM.SEE PREVIOUS COMMENTS FOR
 ADDRESS AND POINT OF CONTACT.
  
 3.ADDITIONAL PERMIT REQUIRED FOR FUEL
 TANKS & WALK IN COOLERS.CUT SHEETS ON
 THE COOLER PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-08 Cont ID  
Sent By pkrauss Date 2004-06-08 Time 09:55 Rev Time 1.25
Received By pkrauss Date 2004-06-08 Time 09:36 Sent To  
Notes
2004-06-08 00:00:00DENIED:
 1.ENERGY CALCULATIONS INDICATE MAXIMUM
 TONNAGE AS 6 TONS.PLAN SHEET A-15
 THE EQUIPMENT SCHEDULE INDICATES A TOTAL
 OF 11 TONS.
  
 2.ADDITIONAL PERMIT REQUIRED FOR THE
 WALK-IN COOLER/FREEZERS.PROVIDE
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 3.PLAN SHEET A-6 INDICATES THE TOP OF
 THE JOISTS AS 16' 4".PER 2001 FBC(M)
 306.5, EQUIPMENT LOCATED ON ROOFS AT A
 HEIGHT GREATER THAN 16' SHALL HAVE A
 PERMANENT MEANS OF ACCESS.SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBJECTS
 GREATER THAN 30".
  
 4.PLAN SHEET A-8A, DETAIL FOR THE
 CONDENSING UNIT.HEIGHT REQUIREMENT FOR
 THE C.U. STAND SHALL COMPLY WITH 2001
 FBC 1511.7 (SEE ATTACHED SCHEDULE).
  
 5.INDICATE TERMINATION OF THE
 CONDENSATE.
  
 6.ADDITIONAL PERMIT REQUIRED FOR THE
 UNDERGROUND FUEL TANKS, PLANS TO HAVE
 PRIOR APPROVAL FROM PALM BEACH COUNTY
 DERM AT 3323 BELVEDERE RD BUILD #502.
 ATTENTION CHIP GREEN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-10-12 Cont ID  
Sent By kstevens Date 2005-10-12 Time 09:07 Rev Time 0.55
Received By kstevens Date 2005-10-12 Time 09:06 Sent To  
Notes
2005-10-12 00:00:00REVISION OK ADDED AN OIL SEPARATOR TO
 PLANS, CHANGED 2 FLOOR SINKS TO FLOOR
 DRAINS. NO INDIRECT WASTE.

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-09-21 Cont ID  
Sent By kstevens Date 2005-09-21 Time 09:19 Rev Time 0.75
Received By kstevens Date 2005-09-21 Time 09:19 Sent To  
Notes
2005-09-21 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTPER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS A-13 & A-14 FLOOR DRAINS ARE NOT
 AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTIONS 802.3 & 802.3.2. A FLOOR SINK
 OR A HUB DRAIN IS REQUIRED FOR INDIRECT
 WASTE.
 2. SHTS A-13 & A-14 THE PERSONAL
 SIGNATURE IS REQUIRED ON THE SEAL PER
 FAC 61G1-16.003 & FAC 61G1-16.004(5).
 INITIALS ARE NOT APPROVED. FS 481.2055.
 3. SHT A-13 FLOOR DRAIN IN TOILET ROOM
 IS NOT VENTED AS SHOWN. SEE RED LINE
 CORRECTION ON PLANS FOR THE CORRECT
 CONNECTION OF W/C TO BUILDING DRAIN.
 THIS WAS RED LINED ON ISSUED SET OF
 PLANS AND SHALL BE CORRECTED ON
 REVISION. SECTIONS 901.2.1 & 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-08 Cont ID  
Sent By kstevens Date 2004-11-08 Time 10:11 Rev Time 0.75
Received By kstevens Date 2004-11-08 Time 10:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-08-21 Cont ID  
Sent By kstevens Date 2004-08-21 Time 06:57 Rev Time 1.50
Received By kstevens Date 2004-08-20 Time 18:55 Sent To  
Notes
2004-08-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHTS A-1 & A-2, SHT A-1 SHOWS A PRO-
 POSED 750 GAL SAND/OIL INTERCEPTOR,
 WHEREAS SHT A-2 SHOWS A 158 GAL INTECEP-
 TOR. PLEASE CORRELATE PLANS/DETAILS.
 SECTION 104.2.1
 2) FROM PREVIOUS REVIEW: ROUTE PLANS TO
 DBPR HOTEL AND RESTURANT DIVISION. RES-
 PONSE NOTED BUT UNABLE TO FIND INFORMAT-
 ION FROM RESPONSE. PLEASE CLARIFY. SECT-
 ION 104.2.1
 3) FROM PREVIOUS REVIEW: SHT A-3 WATER
 FILTERS SHALL COMPLY WITH NSF-42. MANUF.
 INFORMATION IS NOT CLEAR AND HARD TO
 READ, AND DOES NOT INDICATE COMPLIANCE
 WITH NSF-42. PLEASE SUBMIT MANUF. INFOR-
 MATION SHOWING THAT FILTERS COMPLY WITH
 NSF-42. SECTION 611.1
 4) FROM PREVIOUS REVIEW: SUBMIT PLANS
 FOR CAR WASH. NO RESPONSE NOTED. SECTION
 1-4.2.1 & 104.3.1.1
 5) SHT A-1 REFERS TO CIVIL PLANS. CIVIL
 PLANS ARE NOT SUBMITTED. PLEASE SUBMIT
 A SET OF CIVIL PLANS TO CORRELATE INFOR-
 MATION REQUIRED TO APPROVE PLANS. SECT-
 ION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 13:51 Rev Time 2.50
Received By kstevens Date 2004-06-05 Time 13:50 Sent To  
Notes
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) CONTACT RODNEY COMPO, ENVIRONMENTAL
 MANAGER FOR SIZING OF GREASE INTERCEPTOR
 AND OIL/SAND INTERCEPTOR. WASET ORDINAN-
 CE 2938-96. (561) 837-4074.
 2) ROUTE PLANS TO DBPR HOTEL AND RESTUR-
 AND DIVISION FOR REVIEW PRIOR TO RESUB-
 MITTING FOR REVIEW AT CITY WPB. PLANS
 SHALL BE STAMPED AND WORKSHEETS ATTACHED
 TO EACH SET OF PLANS FOR REVIEW. SECTION
 101.4.7
 3) SHT A-3 SHOW CLEAR FLOOR SPACE FOR
 FIXTURES IN WOMENS TOILET ROOM. SECTIONS
 11-4.16.2 AND 11-4.19.3.
 4) SHT A-3 WATER FILTERS SHALL COMPLY
 WITH NSF-42. SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 611.1
 5) SEPARATE PERMITS ARE REQUIRED FOR:
 - GREASE INTERCEPTORS
 - OIL/SAND INTERCEPTORS
 - IRRIGATION
 - CAR WASH SYSTEM - SUBMIT PLANS.
 6) SHT A-13 THE CODE IN EFFECT IS FBC-
 2001 PLUMBING. PLUMBING NOTES REFERES
 TO STANDARD CODE. PLEASE CHANGE REFEREN-
 CE. SECTION 104.2.1
 7) RPZ BACKFLOW IS REQUIRED FOR WATER
 SERVICE TO THE CAR WASH. SEC 608.13.2
 8) SHT A-14 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN (FLAT LAYOUT
 ON SHT A-13) NOR DOES IT MEET CODE REQ-
 UIREMENTS.
 A) A-13 SHOWS ALL FLOOR SINKS ON THE
 GREASE LINE. - RISER SHOWS SOME F.S. ON
 THE SANT. LINE.
 B) A FLOOR DRAIN AND A FLOOR SINK ARE
 MISSING ON THE RISER DIAGRAM.
 C) THERE IS A HORIZONTAL DRY VENT AFTER
 THE LAST FLOOR SINK ON THE GREASE LINE.
 THIS FLOOR SINK SHOULD BE CONNECTED ON
 THE VERTICAL RISE OF THE VENT. SECTION
 905.3
 D) FLOOR DRAIN IN MENS TOILET ROOM IS
 LABLED AS A FLOOR SINK ON THE RISER DIA-
 GRAM.
 E) LAV ARMS AND TRAP ARE NOT SHOWN ON
 THE RISER DIAGRAM.
 F) HAND SINK VENT IS SHOWN AS A 3" ON
 A-13 AND 2" ON THE RISER DIAGRAM.
 PLEASE CORRELATE PLANS. SECTION 104.2.1
 9) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 DOCUMENTS SHALL BE SIGNED PERSONALLY AND
 SEALED/DATED BY THE RESPONSIBLE ARCHITE-
 CT. INITIALS ARE NOT APPROVED. IF THISIS
 YOUR LEGAL SIGNATURE, A COPY OF DRIVERS
 LICENSE, VOTERS REGISTRATION, OR ARCHIT-
 ECTS LICENSE SHOWING LEGAL SIGNATURE
 WITH A NOTARIZED LETTER STATING THAT IS
 YOUR LEGAL SIGNATURE FOR OUR FILE WILL
 SUFFICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-02 Cont ID  
Sent By mmclean Date 2004-06-02 Time 16:21 Rev Time 0.00
Received By mmclean Date 2004-06-02 Time 16:21 Sent To I
Notes
2004-06-02 00:00:00APPROVED BY JOSH LONG, PLANNER 659-8031