| 2004-06-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04050765 |
| | ADD: 1822 UPLAND RD |
| | CONT: BANES BUILDING CO |
| | TEL: (561)635-6935 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) UNITY OF TITLE, FOR |
| | 74-43-43-29-004-0050 |
| | 74-43-43-29-004-0051 |
| | REMOVAL OF BLOCK WALL AT PROPERTY LINE |
| | WILL REQUIRE THE UNITY OF TITLE. |
| | |
| | 3) TO INCORPORATE THE NEW DOORS AND SIDE |
| | LIGHTS AT 2400 FLORIDA MANGO UNDER THIS |
| | PERMIT THE UNITITY OF TITLE WOULD ALSO |
| | NEED TO INCLUDE THIS LOT, OTHERWISE A |
| | SEPERATE PERMIT WOULD BE REQUIRED. |
| | |
| | 4) 705.1.1.2 OPENINGS WITHIN 15'-0" OF |
| | THE PROPERTY LINE REQUIRE OPENING PROTEC |
| | TIVES, (45 MIN), THE NEW WEST DOORS, |
| | THE OPENINGS ON THE SOUTH, NEW AND EXIST |
| | ING. |
| | |
| | 5) THE OCCUPANCY IS NOT CLEAR AS TO WHAT |
| | THIS BUILDING WILL BE USED FOR? |
| | IF THE USEAGE WILL BE AUTO REPAIR GARAGE |
| | SECTION411.5 (1-6) MUST BE TO BE IMPLE- |
| | MENTED. NOTE THAT (3) OTHER OCCUPANCIES |
| | ARE LOCATED IN OR ATTECHED ARE TO BE SEP |
| | ERATED AS 704. (2 HR). THIS APPLIES TO |
| | DOORS AND WINDOWS REQUIRING 1 1/2 HR |
| | PROTECTION. NOTE (4) VENTILATION REQIURE |
| | MENTS.PROVIDE THE 2HR RATING TO THE |
| | UNDER SIDE OF THE ROOF. |
| | |
| | 6)705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | |
| | 7)11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 8) NOTE RESTROOM DOOR BLOCKS EGRESS, |
| | 1012.1.4 DURING ITS SWING ANY DOOR IN A |
| | MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED |
| | AT LEAST ONE HALF OF THE REQUIRED WIDTH |
| | OF AN CORRIDOR, PASSAGEWAY OR LANDING. |
| | THE CLEAR MINIMUM WIDTH REQUIRED IS 18". |
| | |
| | 9) THE KITCHEN SINK HEIGHT NOT GIVEN, |
| | 11-4.24.2 SINK SHALL BE MOUNTED WITH THE |
| | COUNTER OR RIM NO HIGHER THAN 34". |
| | |
| | 10)11-4.16.4 MISSING THE GRAB BARS |
| | BEHIND THE WATER CLOSET. THE GRAB BAR BE |
| | HIND THE WATER CLOSET SHALL BE 36" MIN- |
| | IMUM. SEE FIGURE 29. |
| | |
| | 11) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 12) SUBMIT THE CORRECT PRODUCT APPROVALS |
| | THE BEST ROLLING DOOR NOA DOESN'T MATCH |
| | THE STATE LISTING, SEE ATTACHED LISTING |
| | 2ND PAGE LIST COVERED NOA'S. |
| | |
| | 13) CERTIFIED TESTING REPORT SUBMITTED |
| | FOR SINGLE HUNG WINDOWS, PLANS DO NOT IN |
| | DICATE WHERE THEY ARE TO BE USED. |
| | |
| | 14) MISSING NOA AND STATE LISTING FOR |
| | THE NEW 6068 STOREFRONT DOORS AND SIDE- |
| | LIGHTS. |
| | |
| | 15) PLANS DO NOT INDICATE IF THE GLASS |
| | BLOCK ARE EXISTING OR NEW? IF NEW PRO- |
| | VIDE THE STATE LISTING AND NOA PLUS PRO- |
| | VIDE INFO. FOR THE 45 MIN FIRE RATING |
| | THAT IS REQUIRED. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |