Plan Review Details - Permit 04050765
Plan Review Stops For Permit 04050765
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-04 Cont ID  
Sent By jwitmer Date 2004-06-04 Time 08:19 Rev Time 1.22
Received By jwitmer Date 2004-06-04 Time 08:19 Sent To  
Notes
2004-06-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04050765
 ADD: 1822 UPLAND RD
 CONT: BANES BUILDING CO
 TEL: (561)635-6935
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) UNITY OF TITLE, FOR
 74-43-43-29-004-0050
 74-43-43-29-004-0051
 REMOVAL OF BLOCK WALL AT PROPERTY LINE
 WILL REQUIRE THE UNITY OF TITLE.
  
 3) TO INCORPORATE THE NEW DOORS AND SIDE
 LIGHTS AT 2400 FLORIDA MANGO UNDER THIS
 PERMIT THE UNITITY OF TITLE WOULD ALSO
 NEED TO INCLUDE THIS LOT, OTHERWISE A
 SEPERATE PERMIT WOULD BE REQUIRED.
  
 4) 705.1.1.2 OPENINGS WITHIN 15'-0" OF
 THE PROPERTY LINE REQUIRE OPENING PROTEC
 TIVES, (45 MIN), THE NEW WEST DOORS,
 THE OPENINGS ON THE SOUTH, NEW AND EXIST
 ING.
  
 5) THE OCCUPANCY IS NOT CLEAR AS TO WHAT
 THIS BUILDING WILL BE USED FOR?
 IF THE USEAGE WILL BE AUTO REPAIR GARAGE
 SECTION411.5 (1-6) MUST BE TO BE IMPLE-
 MENTED. NOTE THAT (3) OTHER OCCUPANCIES
 ARE LOCATED IN OR ATTECHED ARE TO BE SEP
 ERATED AS 704. (2 HR). THIS APPLIES TO
 DOORS AND WINDOWS REQUIRING 1 1/2 HR
 PROTECTION. NOTE (4) VENTILATION REQIURE
 MENTS.PROVIDE THE 2HR RATING TO THE
 UNDER SIDE OF THE ROOF.
  
 6)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
  
 7)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 8) NOTE RESTROOM DOOR BLOCKS EGRESS,
 1012.1.4 DURING ITS SWING ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED
 AT LEAST ONE HALF OF THE REQUIRED WIDTH
 OF AN CORRIDOR, PASSAGEWAY OR LANDING.
 THE CLEAR MINIMUM WIDTH REQUIRED IS 18".
  
 9) THE KITCHEN SINK HEIGHT NOT GIVEN,
 11-4.24.2 SINK SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34".
  
 10)11-4.16.4 MISSING THE GRAB BARS
 BEHIND THE WATER CLOSET. THE GRAB BAR BE
 HIND THE WATER CLOSET SHALL BE 36" MIN-
 IMUM. SEE FIGURE 29.
  
 11) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 12) SUBMIT THE CORRECT PRODUCT APPROVALS
 THE BEST ROLLING DOOR NOA DOESN'T MATCH
 THE STATE LISTING, SEE ATTACHED LISTING
 2ND PAGE LIST COVERED NOA'S.
  
 13) CERTIFIED TESTING REPORT SUBMITTED
 FOR SINGLE HUNG WINDOWS, PLANS DO NOT IN
 DICATE WHERE THEY ARE TO BE USED.
  
 14) MISSING NOA AND STATE LISTING FOR
 THE NEW 6068 STOREFRONT DOORS AND SIDE-
 LIGHTS.
  
 15) PLANS DO NOT INDICATE IF THE GLASS
 BLOCK ARE EXISTING OR NEW? IF NEW PRO-
 VIDE THE STATE LISTING AND NOA PLUS PRO-
 VIDE INFO. FOR THE 45 MIN FIRE RATING
 THAT IS REQUIRED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-21 Cont ID  
Sent By dpalmer Date 2004-05-21 Time 09:33 Rev Time 0.50
Received By dpalmer Date 2004-05-21 Time 08:47 Sent To  
Notes
2004-05-21 00:00:00**************UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE(S).
 PLEASE SEE SOME CIRCUITS ARE MISSING AND
 SOME DO NOT MATCH W/ PANEL.
 PLEASE SEE 700.12E FOR EM/EXT LTS
  
 2)NOTE: SERVICE IS BEING SHOWN AS NEW?
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE INCLUDE COLD WATER PIPE
 FOR GROUNDING ELECTRODE SYSTEM. 250.50
  
 4)NOTE: PLEASE SEE 210.8B3 FOR KITCHEN
 CIRCUITS.ALL.
  
 5)NOTE: PLEASE SEE E-PLAN IS NOT SEALED,
 BY ENGINEER.ONE SET SEEMS TO BE MISSING
 SEAL. PLEASE SEAL SETS NEEDED.
 FAC 61G15-23.002 IF ALL SETS ARE NEEDED
 TO BE STAMPED, THEN ALL AREQ'D TO BE
 SIGNED, DATED AND SEALED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-19 Cont ID  
Sent By mcarsill Date 2004-05-19 Time 12:53 Rev Time 0.00
Received By mcarsill Date 2004-05-19 Time 12:53 Sent To  
Notes
2004-05-19 00:00:001) ON PAGE E-1 IS APPEARS THAT ALL
 EMERGENCY LIGHTS AND EXIT SIGNS ARE
 LOCATED ON ONE SIDE OF THE BUILDING
 ONLY. THIS APPEARS TO BE INCORRECT AND
 MAKES THE BUILDING LOPSIDED. ALSO WITH
 THE EXIT SIGNS SHOWN HOW ARE YOU
 MEETING THE 1/3 WITH SPRINKLERS OR
 1/2 WITHOUT SPRINKLERS SEPARATION
 BETWEEN EXITS.
  
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. A MINIMUM OF
 6" HIGH NUMBERS ARE REQUIRED.
  
 3) DEMOLITION, CONSTRUCTION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 4) DEBRIS IS TO BE REMOVED FROM THE
 BUILDING DAILY.
  
 5) NO PORTABLE FIRE EXTINGUISHERS
 SHOWN.
  
 6) IS THE BUILDING SPRINKLER OR NON
 FIRE SPRINKLERED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-08 Cont ID  
Sent By pkrauss Date 2004-06-08 Time 06:58 Rev Time 0.00
Received By pkrauss Date 2004-05-18 Time 15:05 Sent To  
Notes
2004-05-18 00:00:00TO COMM BD#15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-08 Cont ID  
Sent By pkrauss Date 2004-06-08 Time 06:43 Rev Time 0.40
Received By pkrauss Date 2004-06-08 Time 06:39 Sent To  
Notes
2004-06-08 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.INDICATE OUTSIDE AIR DUCT, MATERIAL,
 SIZE, LAYOUT AND INTAKE.FRESH AIR
 INTAKE SHALL BE A MINIMUM OF 10 FT FROM
 STREETS, ALLEYS, PARKING LOT, LOADING
 DOCK, OR ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT OR FUMES.2001 FBC(M)
 401.5.1.
  
 3.INDICATE LOCATION FOR THE CONDENSING
 UNIT.ROOF INSTALLATIONS SHALL COMPLY
 WITH HEIGHT REQUIREMENTS OF THE 2001 FBC
 1511.7.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL FOR THE ROOF STAND.PLEASE
 NOTE, SHOULD ROOF HEIGHT EXCEED 16 FT,
 PERMANENT MEANS OF ACCESS IS REQUIRED
 PER 2001 FBC(M) 306.5.PLEASE CLARIFY.
  
 4.PLANS DO NOT INDICATE LINE SET FOR
 THE LIQUID & SUCTION LINES OR THE
 CONDENSATE.PLEASE INDICATE LINE SIZE,
 MATERIAL & LAYOUT.PROVIDE INFORMATION
 FOR THE TERMINATION OF THE CONDENSATE.
  
 5.PLEASE INDICATE IF ANY WORK IS TO
 BE DONE IN THE GARAGE AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 11:02 Rev Time 1.00
Received By kstevens Date 2004-06-05 Time 11:02 Sent To  
Notes
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) INDICATE OCCUPANCY/USAGE OF GARAGE
 BLDG. IF SERVICE GARAGE MORE COMMENTS
 SHALL BE FORTHCOMING.
 2) SHT A-2 A DRINKING FOUNTAIN IS REQUI-
 RED PER TABLE 403.1. - ALSO SEE SECTION
 410.1.
 3) SHT A-2 FLOOR PLAN, SHOW CLEAR FLOOR
 SPACE FOR THE TOILETS 11-4.16.2 AND THE
 LAVS 11-4.19.3.
 4) SJT A2 KITCHEN, SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. SUBMIT
 A DETAIL SHOWING COMPLIANCE.
 5) SHT A3 DETAILS # 1 & 2 H.C. ELEVAT-
 IONS, SHOW HEIGHT OF W/C'S 11-4.16.3 AND
 FOR LAVS EXPOSED PIPES AND SURFACES PER
 SECTION 11-4.19.4.
 6) SHT M-1 SHOW WATER HEATER LOCATION ON
 THE FLOOR PLAN. SUBMIT INFORMATION ON
 THE EMERGENCY PAN DRAIN LINE AND THE P/T
 RELIEF VALVE DISCHARGE LINE. WATER HEAT-
 ER SHALL BE ACCESSIBLE. SUBMIT A DETAIL.
 SECTIONS. 104.2.1 AND 501.4.
 7) SHT M-1 THERMAL EXPANSION CONTROL IS
 REQUIRED. SECTION 607.3.2
 8) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE LINE TO THE BLDG. SECTION
 608.13.2
 9) SHT M-1 WATER RISER DIAGRAM, PLEASE
 EXPLAIN WHICH FIXTURE IS BEING SUPPLIED
 WITH THE LINES PAST THE LAVS. - NO WATER
 SUPPLY IS SHOWN TO THE KITCHEN SINK.
 PLEASE CLARIFY. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]