Plan Review Details - Permit 04050734
Plan Review Stops For Permit 04050734
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-06 Cont ID  
Sent By lsmith Date 2004-07-06 Time 08:57 Rev Time 0.25
Received By lsmith Date 2004-07-06 Time 08:57 Sent To  
Notes
2004-07-06 00:00:00BUTT GLASS ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:21 Rev Time 1.50
Received By lsmith Date 2004-06-29 Time 09:54 Sent To  
Notes
2004-06-29 00:00:00PROVISO:
  
 BUTT GLASS ASSEMBLY:
 SUBMIT ENGINEERING (SIGNED & SEALED) ON
 THE BUTT GLASS ASSEMBLY.INCLUDE A
 LETTER FROM THE ENGINEER STATING HE
 WILL PERFORM AN ONSITE INSPECTION OF
 THE WINDOWS WHEN IT HAS BEEN INSTALLED
 TO VERIFY IT HAS BEEN INSTALLED PER HIS
 ENGINEERING.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By jleech Date 2004-06-28 Time 19:38 Rev Time 2.00
Received By lsmith Date 2004-06-02 Time 11:48 Sent To  
Notes
2004-06-02 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALMBEACH COUNTY.THE ACTUAL PERMIT
 PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.PLEASE CALL
 (561) 233-5025 FOR MORE INFORMATION.
  
 2. SUBMIT THE ENGINEERING FOR THE BUTT
 GLASS ASSEMBLY INCLUDING MFGRS. SPECS
 ON SILICONE GEL BEING USED.THE
 ENGINEER MUST INSPECT THE UNIT WHEN
 INSTALLED AND PROVIDE A SIGNED & SEALED
 LETTER STATING IT IS INSTALLED PER HIS
 SPECIFICATIONS. PRODUCT APPROVALS ARE
 ALSO REQUIRED.
  
 3. HIGHLIGHT THE MIAMI/DADE PRODUCT
 APPROVALS FOR THE FIXED WINDOWS SHOWING
 SIZE AND SHAPE BEING INSTALLED.
  
 4. THE DESIGN PRESSURES OF THE GARAGE
 DOORS AS STATED ON THE PLANS DO NOT
 MATCH THE PRODUCT APPROVALS.PLEASE
 CORRECT.
  
 5. SEE NOTES FROM ELECTRIC REGARDING
 THE ARCHITECT TITLE BLOCK AND SIGNATURE
 REQUIREMENTS PER FS 481.221
  
 6. HIGHLIGHT THE TYPE OF CEMENT TILE
 BEING INSTALLED ON THE PRODUCT
 APPROVALS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 06:00 Rev Time 0.25
Received By dpalmer Date 2005-02-23 Time 06:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-02-01 Cont ID  
Sent By dpalmer Date 2005-02-01 Time 08:32 Rev Time 0.50
Received By dpalmer Date 2005-02-01 Time 08:29 Sent To  
Notes
2005-02-01 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS SHOWN FROM METER
 TO MAIN/PANEL "B". PLEASE SEE
 250.6,250.24. EQP GRND IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISC.
  
 2)NOTE: PLEASE SEE
 210.11C1,210.52B,220.16, SMALL APPL IS
 1.5 KW MIN, PLEASE ALSO SEE DINING RM
 RQ'D RECEPTS.
  
 3)NOTE: PLEASE SEE 5KW SHOWN ON 1P20A
 BRKR FOR GOLF CART CHARGER.
 PLEASE SEE 3KW ON 1P20A BATH GFI
 CIRCUIT.
 PLEASE ADJUST.
 LOADS EXCEED RATINGS OF CIRCUITS.
 240.4 ETC.
  
 4)NOTE:PLEASE SEE MAIN BRKR PANEL "B",
 IS SHOWN AS 8-16 CIRCUIT PANEL YET,
 PANEL "B" IS SHOWN ASA 42 CIRCUIT
 PANEL ON PANEL SCHEDULE.
  
 5)NOTE: PLEASE SHOW PANEL "C" ON PLANS.
 COULD NOT LOCATE THIS ON PLANS.
  
  
 6 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 07:36 Rev Time 0.33
Received By dpalmer Date 2004-06-17 Time 07:36 Sent To P
Notes
2004-06-17 00:00:00PLANS ARE REQUIRED TO HAVE ALL OLD/
 VOIDED SHEETS REMOVED AND NEW SHEETS TO
 BE INSERTED.
  
 ELEC STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-19 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:56 Rev Time 0.33
Received By dpalmer Date 2004-05-19 Time 18:46 Sent To M
Notes
2004-05-19 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEAS INDICATE GFI/GFI PROTECT-
 -ION JACUZZI TUB. 680
  
 2)NOTE: PLEASE SEE AN EQUIPMENT GROUND-
 -ING CONDUCTOR IS SHOWN FROM METER TO
 DISC "B". PLEASE SEE 250.6/250.24
  
 3)NOTE: PLEASE SEE 210.52C1 FOR MISSING
 RECEPTS ON KITCHEN COUNTERSPACE.
  
 4)NOTE: PLEASE SEE 210.63 FOR MISSING
 GFI RECEPT FOR A/C COND UNITS.
  
 5)NOTE: PLEASE SEE SEE RAISED SEAL MUST
 BE CLEAR AND VISABLE WITH ALL INFORMAT-
 -ION. PLEASE ALSO SEE FS 481.221, WHICH
 REQ'S A COMPLETE SIGNATURE. FIRST NAME
 IS SHOWN AS AN INITIAL. PLEASE ALSO
 SIGN FIRST NAME. PER DBPR.
 THIS IS REQ'D ON ALL PLANS WEATHER OR
 NOT COMMENT IS MADE BY OTHER REVIEWERS.
  
 6 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 7)NOTE: PLEASE SEE ONE PANEL IS SHOWN
 IN GARAGE, PLEASE INDICATE LOCATION OF
 OTHER PANEL.
  
 8)NOTE: PLEASE SEE SD IS REQ'D TO BE
 MOVED INTO MASTER BEDRM. NFPA-72
 8-1
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 14:13 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 14:13 Sent To E
Notes
2005-02-18 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 07:49 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 14:13 Sent To E
Notes
2005-01-31 00:00:00TO "DP" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:21 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 16:21 Sent To B
Notes
2004-07-01 00:00:00TO LS DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:55 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 14:55 Sent To E
Notes
2004-06-14 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By mmclean Date 2004-05-18 Time 17:45 Rev Time 0.00
Received By lsmith Date 2004-05-18 Time 15:52 Sent To  
Notes
2004-05-19 00:00:00TO SFD RACK/E
2004-05-18 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-28 Cont ID  
Sent By dpalmer Date 2004-05-19 Time 18:46 Rev Time 0.35
Received By pkrauss Date 2004-05-28 Time 11:13 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-28 Cont ID  
Sent By jleech Date 2004-06-28 Time 19:38 Rev Time 0.33
Received By jleech Date 2004-06-28 Time 19:38 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-29 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 07:37 Rev Time 0.50
Received By jleech Date 2004-05-29 Time 06:39 Sent To B
Notes
2004-05-29 00:00:00DENIED;
 RAISED SEAL IS NOT CLEAR.
 COMPLETE SIGNITURE IS REQUIRED.
 ONLY ONE COPY OF RISER DIAGRAM FOUND.
 PLEASE ATTACH TO PLANS AND VOID OUT
 OLD RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-18 Cont ID  
Sent By mmclean Date 2004-05-18 Time 17:45 Rev Time 0.00
Received By mmclean Date 2004-05-18 Time 17:45 Sent To I
Notes
***NONE***