Plan Review Details - Permit 04050732
Plan Review Stops For Permit 04050732
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-03-02 Cont ID  
Sent By lsmith Date 2005-03-02 Time 11:24 Rev Time 0.75
Received By lsmith Date 2005-03-02 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-01-12 Cont ID  
Sent By lsmith Date 2005-01-12 Time 08:17 Rev Time 1.00
Received By lsmith Date 2005-01-12 Time 08:17 Sent To  
Notes
2005-01-12 00:00:00BUILDING PLAN REVIEW: FAILED
 BUTT GLASS ASSEMBLY:
  
 1. THE ENGINEER SHOULD SUBMIT HIS
 CALCULATIONS FOR THE DESIGN PRESSURE &
 MAX. SILCONE STRESS.
  
 2. NEED MFGRS. PRODUCT SPEC. SHEETS FOR
 THE SILICONE SEALANT.
  
 3.THE THIRD PARTY QUALITY ASSURANCE
 LISTED ON THE SITE SPECIFIC FORM HAS NOT
 SUBMITTED ANY TESTING THEY PERFORMED ON
 THIS SYSTEM.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLAN REVIEW
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-12-21 Cont ID  
Sent By lsmith Date 2004-12-21 Time 10:30 Rev Time 0.50
Received By lsmith Date 2004-12-21 Time 10:30 Sent To  
Notes
2004-12-21 00:00:00BUILDING PLAN REVIEW FAILED
  
 BUTT GLASS SITE SPECIFIC FORM:
  
 THE TWO COPIES HAVE DIFFERENT
 INFORMATION ON THEM: #7: NAME OF
 APPROVED THIRD PARTY QUALITY ASSURANCE
 ENTITY IS DIFFERENT.
  
 ONE COPY IS UNSIGNED BY APPLICANT.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-11-05 Cont ID  
Sent By lsmith Date 2004-11-05 Time 11:23 Rev Time 0.50
Received By lsmith Date 2004-11-05 Time 13:48 Sent To  
Notes
2004-11-05 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. THE SUBMITTALS FOR THE BUTT GLASS
 WINDOW ASSEMBLY IS INCOMPLETE. THE
 ENGINEER DRAWING SHOWING THE TOTAL BUTT
 GLASS ASSEMBLY IS MISSING. BE SURE THE
 TYPE OF GLASS BEING USED IS SHOWN ON
 THE
 DRAWING. (4500)
  
 2. THE SITE SPECIFIC FORM IS
 INCOMPLETE.
 SEE #1 FOR METHOD 1/METHOD 2 (CIRCLE
 ONE)
  
 3. THE SIZE OF THE BUTT GLASS ASSEMBLY
 SHOWN ON THE DRAWING BY THE ENGINEER
 MUST AGREE WITH THE ARCHITECT'S PLANS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-06 Cont ID  
Sent By lsmith Date 2004-07-06 Time 08:58 Rev Time 0.25
Received By lsmith Date 2004-07-06 Time 08:58 Sent To  
Notes
2004-07-06 00:00:00BUTT GLASS ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:19 Rev Time 1.50
Received By lsmith Date 2004-06-29 Time 09:24 Sent To  
Notes
2004-06-29 00:00:00PROVISO:
 BUTT GLASS ASSEMBLY:
 SUBMIT SIGNED & SEALED ENGINEERING WITH
 LETTER FROM ENGINEER STATING HE WILL
 PERFORM AN ONSITE INSPECTION OF THE
 BUTT GLASS WINDOWS WHEN THEY ARE
 INSTALLED AND VERIFY IT HAS BEEN
 INSTALLED PER HIS ENGINEERING.
  
 ANY QUESTSIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By jleech Date 2004-06-28 Time 19:37 Rev Time 3.00
Received By lsmith Date 2004-06-02 Time 10:13 Sent To  
Notes
2004-06-02 00:00:00BUILDING PLANS REVIEW FAILED:
  
  
 1. BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALMBEACH COUNTY.THE ACTUAL PERMIT
 PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.PLEASE CALL
 (561) 233-5025 FOR MORE INFORMATION.
  
 2. SUBMIT ENGINEERING ON THE 2 BUTT
 GLASS K & L.SUBMIT PRODUCT SPECS. FOR
 SILICONE TO BE USED. ENGINEER TO
 INSPECT INSTALLATION AND SUBMIT A SIGNED
 & SEALED LETTER VERIFYING INSTALLATION
 IS TO HIS SPECIFICATIONS.
  
 3. HIGHLIGHT THE PRODUCT APPROVAL FOR
 THE TYPE OF CEMENT TILE TO BE INSTALLED.
  
 4. THE DESIGN PRESSURES SHOWN ON THE
 PLANS FOR THE 2 GARAGE DOORS DO NOT
 MATCH THE FLORIDA PRODUCT APPROVAL.
 PLEASE HIGHLIGHT THE FLORIDA PRODUCT
 APPROVAL FOR THE TYPE OF DOORS BEING
 INSTALLED.
  
 5. HIGHLIGHT THE MIAMI/DADE PRODUCT
 APPROVALS FOR THE FIXED WINDOW SHAPES &
 SIZES BEING INSTALLED.SPECIFY IMPACT
 GLASS.
  
 6. COULD NOT LOCATE THE B2 FIXED GLASS
 TRANSOM ON THE PLANS SHOWN ON WINDOW
 SCHEDULE.
  
 7. SEE NOTES FROM PLUMBING REVIEW
 REFERENCING THE SEAL & SIGNATURE OF THE
 ARCHITECT.ARCHITECT MUST SIGN FULL
 NAME AS SHOWN ON HIS LICENSE AND SEAL
 MUST LEAVE A READABLE IMPRESION ON THE
 PLANS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-20 Cont ID  
Sent By btrobaug Date 2005-04-20 Time 10:52 Rev Time 0.50
Received By btrobaug Date 2005-04-20 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-25 Cont ID  
Sent By btrobaug Date 2005-03-25 Time 10:17 Rev Time 0.50
Received By btrobaug Date 2005-03-25 Time 10:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-05-24 Cont ID  
Sent By btrobaug Date 2004-05-24 Time 13:24 Rev Time 0.50
Received By btrobaug Date 2004-05-24 Time 12:33 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-04-19 Cont ID  
Sent By adarroug Date 2005-04-19 Time 09:00 Rev Time 0.00
Received By adarroug Date 2005-04-19 Time 09:00 Sent To E
Notes
2005-04-19 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-03-18 Cont ID  
Sent By adarroug Date 2005-03-18 Time 07:55 Rev Time 0.00
Received By adarroug Date 2005-03-18 Time 07:55 Sent To E
Notes
2005-03-18 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 14:16 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 14:16 Sent To B
Notes
2005-02-18 00:00:00TO LSMITH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-05 Cont ID  
Sent By mjacobs Date 2005-01-05 Time 15:44 Rev Time 0.00
Received By mjacobs Date 2005-01-05 Time 15:44 Sent To B
Notes
2005-01-05 00:00:00TO "LS" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2004-12-20 Time 14:25 Sent To B
Notes
2004-12-20 00:00:00SENT TO "LS" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 10:56 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 10:56 Sent To B
Notes
2004-11-05 00:00:00TO LS DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:19 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 16:18 Sent To B
Notes
2004-07-01 00:00:00TO LS DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:52 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 14:52 Sent To P
Notes
2004-06-14 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By mmclean Date 2004-05-18 Time 17:42 Rev Time 0.00
Received By lsmith Date 2004-05-18 Time 15:53 Sent To  
Notes
2004-05-19 00:00:00TO SFD RACK/E
2004-05-18 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-28 Cont ID  
Sent By btrobaug Date 2004-05-24 Time 13:33 Rev Time 0.35
Received By pkrauss Date 2004-05-28 Time 11:45 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-28 Cont ID  
Sent By jleech Date 2004-06-28 Time 19:37 Rev Time 0.33
Received By jleech Date 2004-06-28 Time 19:37 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-29 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:52 Rev Time 0.33
Received By jleech Date 2004-05-29 Time 06:55 Sent To  
Notes
2004-05-29 00:00:00DENIED;
 RAISED SEAL NOT CLEAR.
 COMPLETE SIGNITURE IS REQUIRED. PLEASE
 ATTACH NEW RISER DIAGRAM TO PLANS AND
 VOID OUT OLD RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-18 Cont ID  
Sent By mmclean Date 2004-05-18 Time 17:42 Rev Time 0.00
Received By mmclean Date 2004-05-18 Time 17:42 Sent To I
Notes
***NONE***