Plan Review Details - Permit 04050699
Plan Review Stops For Permit 04050699
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-19 Cont ID  
Sent By jwitmer Date 2004-07-19 Time 09:07 Rev Time 0.22
Received By jwitmer Date 2004-07-19 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By jwitmer Date 2004-06-15 Time 09:05 Rev Time 4.00
Received By jwitmer Date 2004-06-15 Time 09:05 Sent To  
Notes
2004-06-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04050699
 ADD: 600 NORTHPOINT PKWY (PHASE 7)
 CONT: AMERICAN BUILDING INTERIORS
 TEL: (239)542-5717
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 LOBBY, L102 NOTE 16-11N BACKING OR BLOCK
 ING FOR CHANDELIER, PROVIDE INFORMATION,
 HOW MUCH WEIGHT IS INVOLVED, WHAT TYPE
 OF STRUCTURAL COMPONENT WILL THE CHANDE-
 LIER BE HUNG FROM.
  
 3) FRONT ENTRY DOORS:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 PROVIDE 2 COPIES.
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) SHEET L305 DOESN'T INDICATE WALL FIN-
 ISHES, THERE ARE NUMBERS INDICATING A
 FINISH BUT NO FINISH SCHEDULE WAS FOUND.
 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 6) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-09 Cont ID  
Sent By dpalmer Date 2004-07-09 Time 15:19 Rev Time 0.25
Received By dpalmer Date 2004-07-09 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2204-05-19 Cont ID  
Sent By dpalmer Date 2004-05-19 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2004-05-19 Time 15:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-07-29 Cont ID  
Sent By mcarsill Date 2004-07-29 Time 10:30 Rev Time 0.00
Received By mcarsill Date 2004-07-29 Time 10:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-06-30 Time 16:27 Rev Time 0.00
Received By csiegber Date 2004-06-30 Time 16:27 Sent To  
Notes
2004-06-30 00:00:00TO COMM BD#56/7 OF 8 PERMITS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-06-30 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 15:21 Sent To  
Notes
2004-05-17 00:00:00TO COMM BD#6/7 OF 8 PERMITS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By pkrauss Date 2004-06-02 Time 09:40 Rev Time 0.10
Received By pkrauss Date 2004-06-02 Time 09:40 Sent To  
Notes
2004-06-02 00:00:00NO MECHANICAL PLANS SUBMITTED.PERMIT
 APPLICATION INDICATES NOT APPLICABLE.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-07-31 Cont ID  
Sent By kstevens Date 2004-07-31 Time 09:02 Rev Time 0.25
Received By kstevens Date 2004-07-31 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-20 Cont ID  
Sent By kstevens Date 2004-07-20 Time 13:48 Rev Time 0.25
Received By kstevens Date 2004-07-20 Time 13:48 Sent To  
Notes
2004-07-20 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 SEE REVIEW COMMENT PERMIT #04050693
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 09:46 Rev Time 0.25
Received By kstevens Date 2004-06-05 Time 09:46 Sent To  
Notes
2004-06-05 00:00:00SEE REVIEW COMMENTS FROM PERMIT NUMBER
 04050693. KSTEVENS