Plan Review Details - Permit 04050693
Plan Review Stops For Permit 04050693
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-19 Cont ID  
Sent By jwitmer Date 2004-07-19 Time 09:01 Rev Time 0.55
Received By jwitmer Date 2004-07-19 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By jwitmer Date 2004-06-15 Time 10:09 Rev Time 1.11
Received By jwitmer Date 2004-06-15 Time 10:09 Sent To  
Notes
2004-06-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04050693
 ADD: 600 NORTHPOINT PKWY
 (PHASE 1) 3RD FL GUEST ROOMS
 CORRIDOR & VENDING
 CONT: AMERICAN BUILDING INTERIORS
 TEL: (239)542-5717
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 3) SHOW EXIT MEANS OF EGRESS WITHIN
 THE UNITS, DOUBLE/DOUBLE SUITE, KING
 SUITE. QUEEN/QUEEN CONNECTOR HAS ONLY
 30" BETWEEN THE DRESSER AND CORNER OF
 WALL. SEE TABLE 1004 36" MINIMUM CLEAR
 WIDTH.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-09 Cont ID  
Sent By dpalmer Date 2004-07-09 Time 15:09 Rev Time 1.50
Received By dpalmer Date 2004-07-09 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-19 Cont ID  
Sent By dpalmer Date 2004-05-19 Time 11:51 Rev Time 1.00
Received By dpalmer Date 2004-05-19 Time 11:51 Sent To  
Notes
2004-05-19 00:00:00******** UNSAT ****************
  
 1)NOTE: PLEASE SEEFAC 61G1-16.004,
 A TITLE BLOCK REQ'D FOR EACH SHEET AND
 ALL INFORMATION AS SETFORTH UNDER FAC
 AND FS 481.219.
  
 2)NOTE: PLEASE SEE ELECTRICAL SEEMS
 TO BE MIXED IN WITH ARCH PLANS.??
 PLEASE SHOW CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULE. ?
  
 PLEASE CLARIFY DEVICE HEIGHTS FOR
 FHAR 24 CFR 100.205
  
 PLEASE SEE 210.62/ 210.52 FOR RECEPT
 SPACING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-29 Cont ID  
Sent By mcarsill Date 2004-07-29 Time 10:27 Rev Time 0.00
Received By mcarsill Date 2004-07-29 Time 10:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-19 Cont ID  
Sent By mcarsill Date 2004-05-19 Time 13:34 Rev Time 0.00
Received By mcarsill Date 2004-05-19 Time 13:33 Sent To  
Notes
2004-05-19 00:00:001) DURING THE PHASING OPERATION, ALL
 EXIT DOORS SHALL REMAIN CLEAR AND
 ACCESSIBLE.
  
 2) NO BLOCKING OF ANY EXIT ACCESS, EXIT,
 OR EXIT DISCHARGE SHALL OCCUR.
  
 3) ANY DEBRIS SHALL BE REMOVED FROM
 THE SITE DAILY.
  
 4) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 5) NO UNAUTHORIZED CUTTING AND WELDING
 OPERATIONS SHALL BE PERFORMED.
  
 6) ALL REQUIRED FIRE AND LIFE SAFETY
 SYSTEMS SHALL REMAIN OPERATIONAL AT
 ALL TIMES.
  
 7) ANY USE OF FUEL POWERED EQUIPMENT
 MUST BE PROVIDED WITH PROPER
 VETILATION TO PREVENT THE ACCUMULATION
 OF CARBON MONOXIDE VAPORS.
  
 8) WHAT SAEFGUARDS WILL BE TAKEN TO
 SEPARATE CONSTRUCTION FROM NON
 CONSTRUCTION AREAS.
  
 9) NON FIRE RATED VISQUEEN SHALL NOT
 BE AFFIXED TO ANY WALLS OR CEILINGS.
  
 10) PLEASE REVIEW FURNITURE LOBBY PLAN.
 IT APPEARS THAT TO MUCH FURNITURE MAY
 BE PRESENT.
  
 11) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL NEW
 HANDRAILS.
  
 12) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW FIRE ALARM EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-06-30 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-06-30 Time 14:33 Sent To  
Notes
2004-06-30 00:00:00TO COMM BD#56/1 OF 8 PERMITS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-15 Cont ID  
Sent By jwitmer Date 2004-06-15 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2004-05-17 Time 15:19 Sent To PC
Notes
2004-05-17 00:00:00TO COMM BD#6/1 0F 8 PERMITS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By pkrauss Date 2004-06-02 Time 09:34 Rev Time 0.30
Received By pkrauss Date 2004-06-02 Time 09:02 Sent To  
Notes
2004-06-02 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PERMIT APPLICATION INDICATES NOT
 APPLICABLE.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-07-31 Cont ID  
Sent By kstevens Date 2004-07-31 Time 08:53 Rev Time 1.33
Received By kstevens Date 2004-07-31 Time 08:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-20 Cont ID  
Sent By kstevens Date 2004-07-20 Time 13:22 Rev Time 0.75
Received By kstevens Date 2004-07-20 Time 13:19 Sent To  
Notes
2004-07-20 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: PER SECTION
 11-9.2.3 (CHAPTER 509 FS) 1 UNIT REQUIR-
 ED TO COMPLY WITH ITEMS (1)(2)(3) - PRO-
 VIDE DETAILS/ROOM NUMBER. - RESPONSE
 NOTED, BUT ANY FRACTION ABOVE A WHOLE
 NUMBER SHALL BE ROUNDED UP TO A WHOLE
 NUMBER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 06:12 Rev Time 2.00
Received By kstevens Date 2004-06-05 Time 06:12 Sent To  
Notes
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PER SECTION 11-9.2.3 (CHAPTER 509 FS)
 1 UNIT REQUIRED TO COMPLY WITH ITEMS
 (1)(2)(3) - PROVIDE DETAILS AND ROOM
 NUMBER.
 2) PER SECTION 11-9.1.3, 5 ROOMS IN ADD-
 ITION TO THOSE REQUIRED TO BE ACCESSIBLE
 SHALL BE PROVIDED WITH VISUAL ALARMS,
 NOTIFICATION DEFICES, AND TELEPHONE FOR
 PERSONS WITH HEARING IMPAIRMENTS. PLEASE
 PROVIDE INFORMATION, DETAILS, AND ROOM
 NUMBERS TO SHOW COMPLIANCE.
 3) PER SECTION 11-9.1.4, SLEEPING ROOMS
 AND SUITES REQUIRED TO BE ACCESSIBLE BY
 11-9.1.2 SHALL BE DISPERSED AMONG THE
 VARIOUS CLASSES OF SLEEPING ACCOMODAT-
 IONS AVAILABLE TO PATRONS OF THE PLACE
 OF TRANSIENT LODGING. PLANS INDICATE
 THAT NO ACCESSIBLE ROOMS OR SUITES ARE
 AVAILABLE FOR THE KING CONNECTOR, QUEEN/
 QUEEN OR THE QUEEN/QUEEN CONNECTOR.
 PLEASE CLARIFY.
 4) SHTS L101 & L305 DETAIL 11-10D - RE-
 MOVAL OF DRINKING FOUNTAIN, MINIMUM FAC-
 ILITIES REQUIRES A DRINKING FOUNTAIN PER
 TABLE 403.1. WILL THE DRINKING FOUNTAIN
 BE REPLACED/RELOCATED? IS THERE ANOTHER
 DRINKING FOUNTAIN AVAILABLE? PLEASE
 CLARIFY.
 5) SHT L101 ITEM 11-17D - IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED. (OVER 2 FEET)
 SECTION 704.5.
 6) MORE INFORMATION REQUIRED ON TITLE
 BLOCK FOR ARCHITECT. SEE FAC 61G1-16.004
 AND FS 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]