Plan Review Details - Permit 04050661
Plan Review Stops For Permit 04050661
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 11:12 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 11:12 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-05-17 Time 11:13 Rev Time 0.20
Received By pkrauss Date 2004-05-27 Time 07:34 Sent To  
Notes
2004-05-27 00:00:00PROVISO:
 DUCT SMOKE DETECTORS REQUIRED IN THE
 SUPPLY DUCTS FOR UNITS WITH THE DESIGN
 CAPACITY GREATER THAN 2,000 CFM - 2001
 FBC(M) 606.2.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.