Plan Review Details - Permit 04050610
Plan Review Stops For Permit 04050610
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-05-14 Time 11:41 Rev Time 0.00
Received By nmccray Date 2004-06-02 Time 08:41 Sent To M
Notes
2004-05-20 00:00:00*************DENIED*********************
 1) PLEASE PROVIDE CUT SHEET AND SPECS
 FOR ABOVEGROUND FUEL TANK.
  
 2) THE ABOVEGROUND FUEL TANK SHALL
 COMPLY WITH NFPA 30, 2000 EDITION.
  
 3) THE STORAGE ROOM FOR THE FUEL TANK
 MUST BE PROPERLY FIRE RATED.
  
 4) PER THE FIRE MARSHAL OF WEST PALM
 BEACH ABOVE GROUND TANKS ARE LIMITED TO
 500 GALS MAXIMUM. ( A LETTER IS REQUIRED
 FROM YOUR COMPANY REQUESTING,DUE TO THIS
 CONDO IS IN THE FIRE LIMIT)
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-14 Time 11:40 Rev Time 0.00
Received By csiegber Date 2004-05-14 Time 11:40 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By pkrauss Date 2004-06-02 Time 08:30 Rev Time 0.55
Received By pkrauss Date 2004-06-01 Time 12:04 Sent To  
Notes
2004-06-01 00:00:00DENIED:
 1. PERMIT APPLICATION INDICATES FUEL
 OIL PIPING & STORAGE.THE PLANS
 SUBMITTED WITH THE PERMIT APPLICATION
 ALSO INDICATES PLUMBING.PLEASE
 CLARIFY.
  
 2. PLANS INDICATE 1,000 GALLON FUEL
 TANK STORAGE.PER 2001 FBC 308.2.1,
 FUEL OIL H3 SHALL HAVE A 4 HOUR
 SEPARATION BETWEEN STORAGE ROOM AND
 OTHER OCCUPANCIES PER TABLE 704.1.4 OF
 THE 2001 FBC.
  
 3. PLEASE PROVIDE ADDTIONAL INFORMATION
 FORTHE VENTILATION FOR THE STORAGE ROOM.
 PLANS SHEET M2.43, INDICATES VEF-P.1-1
 IS THIS FOR EXHAUST OR AIR MAKE-UP?
 PLEASE INDICATE VENTILATION RATE.
 SHOW TERMIATION OF VEF-P.1-1.INDICATE
 LOCATION OF FRESH AIR INTAKE.
  
 4. PROVIDE MANUFACTURERS SUBMITTAL DATA
 FOR THE 1,000 GALLON FUEL TANK, DAY
 TANK & GENERATOR.
  
 5. PER 2001 FBC(M) 1305.6, FILL PIPE
 SHALL TERMINATE OUTSIDE AT A POINT AT
 LEAST 2 FEET FOR ANY BUILDING OPENING.
 FILL OPENING SHALL HAVE A TIGHT METAL
 COVER DESIGNED TO PREVENT TAMPERING.
  
 6. SHOP DRAWING #2 SHOWS A DETAIL FOR
 PIPING INSTALLED AT THE FLOOR OR WALL.
 PROVIDE DETAIL FOR THE PIPING INSTALLED
 AT THE CEILING.REFERENCE 2001 FBC(M)
 305.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.