Plan Review Details - Permit 04050604
Plan Review Stops For Permit 04050604
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-11 Cont ID  
Sent By rmcdouga Date 2005-03-11 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2005-03-11 Time 16:15 Sent To  
Notes
2005-03-11 00:00:00SUBMITTED CALCULATIONS FOR ROYALL WALL
 SYSTEM PER PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-29 Cont ID  
Sent By rmcdouga Date 2004-11-29 Time 12:24 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2004-11-29 00:00:00BUILDING PROVISO
  
 1) SUBMIT STRUCTURAL CALCULATIONS FOR
 THE AUGUSTA (GARAGE RIGHT) MODEL ROYALL
 WALL PANELS PRIOR TO INSTALLING THEM.
  
 2) STORM PANELS WILL BE APPLIED FOR
 UNDER A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-16 Cont ID  
Sent By jleech Date 2004-05-29 Time 07:55 Rev Time 4.00
Received By rmcdouga Date 2004-06-16 Time 13:29 Sent To  
Notes
2004-06-16 00:00:00DENIED
  
 1) THE NOTE ON SHEET 2 REFERS TO THE
 1997 STANDARD GAS CODE. PLEASE UPDATE
 TO THE 2001 FBC FUEL GAS CODE.
  
 2)A MEAN ROOF HEIGHT OF 25'-35' REQUIRES
 THE ROOF SHEATHING TO BE NAILED WITH 8D
 RING SHANK NAILS IN ZONE 3 PER CITY
 AMENDMENTS TO FBC TABLE 2306.1. REVISE
 ROOF SHEATHING NAILING NOTE ON SHEET 4.
  
 3) LIST THE ENGINEER'S FIRM LICENSE
 NUMBER IN THE TITLE BLOCK OF EVERY SHEET
 THAT IS SIGNED AND SEALED BY HIM AS
 REQUIRED BY FS 471.
  
 4) REVISE WOOD CONSTRUCTION NOTE 4 ON
 SHEET 6. THERE IS NO FBC 3218.17.
  
 5) SUBMIT THE UL LISTING INFORMATION FOR
 THE PREFAB FIREPLACE.
  
 6)THE TWO TRUSS ANCHOR UPLIFT SCHEDULES
 ON RF-1 AND SD-2 CONTAIN CONFLICTING
 INFORMATION. PLEASE REMOVE ONE OF THEM.
  
 7) THE USP TA16 CONNECTOR SPECIFIED ON
 SHEET RF-1, REQUIRES (9) 10D NAILS FOR
 AN UPLIFT OF 1205#. PLEASE CORRECT.
  
 8) THE ROYAL WALL ATTACHMENT PLAN IS FOR
 THE AUGUSTA GARAGE RIGHT AND THE SHOP
 DRAWINGS ARE FOR THE AUGUSTA GARAGE LEFT
 THE PANEL NUMBERS DO NOT CORRESPOND.
 THIS IS A SITE SPECIFIC ITEM. PLEASE
 SUBMIT THE APPROPRIATE INFORMATION.
  
 9) THE TRUSS LAYOUT PLAN DIFFERS QUITE A
 BIT FROM THE ROOF FRAMING PLAN ON RF-1.
 REVISE THE ROOF FRAMING PLAN TO MATCH
 THE LAYOUT PLAN FROM THE TRUSS COMPANY.
  
 10) THE TRUSS LAYOUT AND DRAWINGS DO NOT
 INCLUDE THE FLORIDA ROOM. PLEASE CORRECT
  
 11) THE TRUSS DRAWINGS ARE REQUIRED TO
 LIST A BOTTOM CORD LIVE LOAD OF AT LEAST
 10 PSF. SEE FBC TABLE 1604.1.
  
 12) SUBMIT DRAWINGS FOR THE F600 FIXED
 WINDOWS WITH THE CURRENT NOA 02-0701.08
 STAMPED ON THEM.
  
 13) WEATHERGUARD BUILDING PRODUCTS DOES
 NOT HAVE STATE PRODUCT APPROVAL FOR THE
 STORM PANELS. THE KEY PLAN AND SCHEDULE
 DO NOT SHOW THE IMPACT RATED EMERGENCY
 EGRESS WINDOW IN THE DEN. PLEASE CORRECT
 AND SUBMIT PRODUCT WITH STATE OR LOCAL
 PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-17 Cont ID  
Sent By dpalmer Date 2004-11-17 Time 14:14 Rev Time 0.33
Received By dpalmer Date 2004-11-17 Time 14:14 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-18 Cont ID  
Sent By dpalmer Date 2004-05-18 Time 11:13 Rev Time 0.25
Received By dpalmer Date 2004-05-18 Time 11:13 Sent To M
Notes
2004-05-18 00:00:00**UNSAT **
  
 1)NOTE: PLEASE HAVE ARCH SIGN FIRST
 NAME ALSO. FS 481.221
  
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE NOTE, THIS CAN BE A PROVISO DUE
 TO THE FACT OF THE UNKNOWN AMOUNT OF FIX
 -TURES AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 10:48 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 10:48 Sent To B
Notes
2005-03-09 00:00:00TO RMCDOUGAL DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 10:20 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 10:20 Sent To E
Notes
2005-02-28 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 15:06 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 15:06 Sent To E
Notes
2004-11-12 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-16 Cont ID  
Sent By mmclean Date 2004-05-17 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2004-05-14 Time 11:39 Sent To  
Notes
2004-05-18 00:00:00TO SFD RACK/E
2004-05-14 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-28 Cont ID  
Sent By dpalmer Date 2004-05-18 Time 11:13 Rev Time 0.35
Received By pkrauss Date 2004-05-28 Time 07:20 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-29 Cont ID  
Sent By pkrauss Date 2004-05-28 Time 07:39 Rev Time 0.33
Received By jleech Date 2004-05-29 Time 07:55 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-17 Cont ID  
Sent By mmclean Date 2004-05-17 Time 15:39 Rev Time 0.00
Received By mmclean Date 2004-05-17 Time 15:39 Sent To I
Notes
***NONE***