Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 09:39 Rev Time 0.77
Received By jwitmer Date 2004-06-24 Time 10:09 Sent To  
Notes
2004-06-25 00:00:00BUILDING PROVISO:
 PERMIT: 04050601
 ADDRESS: 622 N FLAGLER# 1204
  
 1)FOAM PLASTIC TRIM 803.4
 FOAM PLASTICS SHALL NOT BE USED AS INTER
 IOR FINISHES.
 EXCEPTION: FOAM PLASTIC TRIM, DEFINED AS
 PICTURE MOLDS, CHAIR RAIL, BASEBOARDS,
 HANDRAILS CEILING BEAMS, DOOR TRIM AND
 WINDOW TRIM, OR CROWN MOLDING SHALL BE
 PERMITTED PROVIDED:
 1) THE MINIMUM DENSITY IS 20 LB/CU FT.
 2) THE MAXIMUM THICKNESS IS 1/2" AND
 THE MAXIMUM WIDTH IS 4".
 3) THE TRIM CONSTITUTES NO MORE THAN
 10% OF THE AREA OF WALL OR CEILING.
 4) THE FLAMESPREAD RATING DOES NOT
 EXCEED 75 WHEN TESTED PER ASTM E 84. THE
 SMOKE DEVELOPMENT RATING IS NOT LIMITED.
  
 2) SOFFITS: ARCHITECT TO SPECIFY THE
 MINIMUM LENGTH OF FASTENRS TO STRUCTURE
 ABOVE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-03 Cont ID  
Sent By jwitmer Date 2004-06-03 Time 16:19 Rev Time 1.22
Received By jwitmer Date 2004-06-03 Time 16:03 Sent To  
Notes
2004-06-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04050601
 ADD: 622 N FLAGLER DR# 1204
 CONT: LIVINGSTON
 TEL: (561)371-9685
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)412.6.2 ALL ROOMS AND ENCLOSURES SHALL
 HAVE AT LEAST ONE EXIT ACCESSIBLE WITH-
 OUT TRAVEL THROUGH THE ELEVATOR LOBBY.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS DO NOT INDICATE HOW THE VARIOUS
 SOFFITS ARE TO BE BUILT, MATERIALS,
 SPACING OR ATTACHMENT TO STRUCTURE
 ABOVE.
  
 3) PLANS ALSO INDICATE A NEW PREMANUFACT
 URED DOME. ADDITIONAL INFO REQUIRED.
 FOAM PLASTIC TRIM 803.4
 FOAM PLASTICS SHALL NOT BE USED AS INTER
 IOR FINISHES.
 EXCEPTION: FOAM PLASTIC TRIM, DEFINED AS
 PICTURE MOLDS, CHAIR RAIL, BASEBOARDS,
 HANDRAILS CEILING BEAMS, DOOR TRIM AND
 WINDOW TRIM, OR CROWN MOLDING SHALL BE
 PERMITTED PROVIDED:
 1) THE MINIMUM DENSITY IS 20 LB/CU FT.
 2) THE MAXIMUM THICKNESS IS 1/2" AND
 THE MAXIMUM WIDTH IS 4".
 3) THE TRIM CONSTITUTES NO MORE THAN
 10% OF THE AREA OF WALL OR CEILING.
 4) THE FLAMESPREAD RATING DOES NOT
 EXCEED 75 WHEN TESTED PER ASTM E 84. THE
 SMOKE DEVELOPMENT RATING IS NOT LIMITED.
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) 609.2.1 PARTITIONS OF TYPE I OR II
 BUILDINGS SHALL BE CONSTRUCTED OF NON-
 COMBUSTIBLE MATERIAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-22 Cont ID  
Sent By dpalmer Date 2004-06-22 Time 07:44 Rev Time 0.33
Received By dpalmer Date 2004-06-22 Time 07:41 Sent To  
Notes
2004-06-22 00:00:00NOTED ***
  
 EXISTING SD'S TO REMAIN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-06-17 Time 07:26 Rev Time 0.33
Received By dpalmer Date 2004-05-17 Time 16:17 Sent To  
Notes
2004-05-17 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE HAVE ENGINEER SIGN W/
 SIGNATURE PER FS 471.025/ FAC 61G15-23.
 002. INITIALS ARE NOT PERMITTED PER FBPE
 'S.
  
 2)NOTE: PLEASE NOTE/LIST ARC FAULT
 PROTECTION PER 210.12/ 2002 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-06-22 Cont ID  
Sent By mcarsill Date 2004-06-22 Time 09:25 Rev Time 0.00
Received By mcarsill Date 2004-06-22 Time 09:25 Sent To  
Notes
2004-06-22 00:00:001) DEMOLITION, RENOPVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) EXISTING SMOKE DETECTORS ARE
 TO REMAIN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-05-20 Cont ID  
Sent By mcarsill Date 2004-05-20 Time 13:46 Rev Time 0.00
Received By mcarsill Date 2004-05-20 Time 13:46 Sent To  
Notes
2004-05-20 00:00:001) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3) ALL EXITS AND EXIT ACCESSES SHALL
 REMAIN CLEAR AT ALL TIMES.
  
 4) ANY NEW LIGHT FIXTURES SHALL NOT
 INTERFERE WITH ANY EXISTING OR RELOCATED
 FIRE SPRINKLER HEADS.
  
 5) EXISTING ELECTRIC POWERED SMOKE
 DETECTORS CONTAINED WITHIN THE UNITS
 SHALL NOT BE DISTURBED.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE REMODEL OF THE FIRE SPRINKLER
 SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-17 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 15:13 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 15:13 Sent To  
Notes
2004-06-17 00:00:00TO COMM BD#36
2004-06-16 00:00:00SENT TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-14 Time 11:29 Rev Time 0.00
Received By csiegber Date 2004-05-14 Time 11:29 Sent To  
Notes
2004-05-14 00:00:00TO COMM BD#12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-01 Cont ID  
Sent By pkrauss Date 2004-07-01 Time 15:24 Rev Time 0.20
Received By pkrauss Date 2004-07-01 Time 15:24 Sent To  
Notes
2004-07-01 00:00:00APPROVED 5-24-04/NO CHANGES ON THE
 RE-SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-24 Cont ID  
Sent By pkrauss Date 2004-05-24 Time 09:36 Rev Time 0.50
Received By pkrauss Date 2004-05-24 Time 07:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-07-07 Cont ID  
Sent By kstevens Date 2004-07-07 Time 15:27 Rev Time 1.25
Received By kstevens Date 2004-07-03 Time 10:07 Sent To  
Notes
2004-07-07 00:00:00NO SANT. RISER DIAGRAM OR WATER RISER
 DIAGRAM SUBMITTED. SIGNED/SEALED ENGIN-
 EERED RISER DIAGRAMS SHALL BE REQUIRED
 AT TIME OF PLUMBING APPLICATION FOR
 PERMIT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 05:22 Rev Time 1.00
Received By kstevens Date 2004-06-04 Time 18:30 Sent To  
Notes
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) A WATER CLOSET SHALL BE SET NO CLOSER
 THAN 15" FROM ITS CENTER TO ANY SIDE
 WALL OR CLOSER THAN 30" CENTER TO CENTER
 TO ADJACENT FIXTURES. NEW ROOM FOR W/C
 AND LAV IS NOT WIDE ENOUGH. SECTION
 405.3.1
 2) A SANITARY RISER DIAGRAM AND A WATER
 RISER DIAGRAM ARE REQUIRED FOR NEW W/C
 AND LAV. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]