| Plan Review Stops For Permit 04050601 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-06-25 |
Time |
09:39 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2004-06-24 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2004-06-25 00:00:00 | BUILDING PROVISO: | | | PERMIT: 04050601 | | | ADDRESS: 622 N FLAGLER# 1204 | | | | | | 1)FOAM PLASTIC TRIM 803.4 | | | FOAM PLASTICS SHALL NOT BE USED AS INTER | | | IOR FINISHES. | | | EXCEPTION: FOAM PLASTIC TRIM, DEFINED AS | | | PICTURE MOLDS, CHAIR RAIL, BASEBOARDS, | | | HANDRAILS CEILING BEAMS, DOOR TRIM AND | | | WINDOW TRIM, OR CROWN MOLDING SHALL BE | | | PERMITTED PROVIDED: | | | 1) THE MINIMUM DENSITY IS 20 LB/CU FT. | | | 2) THE MAXIMUM THICKNESS IS 1/2" AND | | | THE MAXIMUM WIDTH IS 4". | | | 3) THE TRIM CONSTITUTES NO MORE THAN | | | 10% OF THE AREA OF WALL OR CEILING. | | | 4) THE FLAMESPREAD RATING DOES NOT | | | EXCEED 75 WHEN TESTED PER ASTM E 84. THE | | | SMOKE DEVELOPMENT RATING IS NOT LIMITED. | | | | | | 2) SOFFITS: ARCHITECT TO SPECIFY THE | | | MINIMUM LENGTH OF FASTENRS TO STRUCTURE | | | ABOVE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-06-03 |
Time |
16:19 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2004-06-03 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2004-06-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04050601 | | | ADD: 622 N FLAGLER DR# 1204 | | | CONT: LIVINGSTON | | | TEL: (561)371-9685 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)412.6.2 ALL ROOMS AND ENCLOSURES SHALL | | | HAVE AT LEAST ONE EXIT ACCESSIBLE WITH- | | | OUT TRAVEL THROUGH THE ELEVATOR LOBBY. | | | | | | 2)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | PLANS DO NOT INDICATE HOW THE VARIOUS | | | SOFFITS ARE TO BE BUILT, MATERIALS, | | | SPACING OR ATTACHMENT TO STRUCTURE | | | ABOVE. | | | | | | 3) PLANS ALSO INDICATE A NEW PREMANUFACT | | | URED DOME. ADDITIONAL INFO REQUIRED. | | | FOAM PLASTIC TRIM 803.4 | | | FOAM PLASTICS SHALL NOT BE USED AS INTER | | | IOR FINISHES. | | | EXCEPTION: FOAM PLASTIC TRIM, DEFINED AS | | | PICTURE MOLDS, CHAIR RAIL, BASEBOARDS, | | | HANDRAILS CEILING BEAMS, DOOR TRIM AND | | | WINDOW TRIM, OR CROWN MOLDING SHALL BE | | | PERMITTED PROVIDED: | | | 1) THE MINIMUM DENSITY IS 20 LB/CU FT. | | | 2) THE MAXIMUM THICKNESS IS 1/2" AND | | | THE MAXIMUM WIDTH IS 4". | | | 3) THE TRIM CONSTITUTES NO MORE THAN | | | 10% OF THE AREA OF WALL OR CEILING. | | | 4) THE FLAMESPREAD RATING DOES NOT | | | EXCEED 75 WHEN TESTED PER ASTM E 84. THE | | | SMOKE DEVELOPMENT RATING IS NOT LIMITED. | | | | | | 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 5) 609.2.1 PARTITIONS OF TYPE I OR II | | | BUILDINGS SHALL BE CONSTRUCTED OF NON- | | | COMBUSTIBLE MATERIAL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-22 |
Time |
07:44 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-06-22 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2004-06-22 00:00:00 | NOTED *** | | | | | | EXISTING SD'S TO REMAIN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-05-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-17 |
Time |
07:26 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-05-17 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2004-05-17 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE HAVE ENGINEER SIGN W/ | | | SIGNATURE PER FS 471.025/ FAC 61G15-23. | | | 002. INITIALS ARE NOT PERMITTED PER FBPE | | | 'S. | | | | | | 2)NOTE: PLEASE NOTE/LIST ARC FAULT | | | PROTECTION PER 210.12/ 2002 NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-06-22 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-06-22 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2004-06-22 00:00:00 | 1) DEMOLITION, RENOPVATION AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) EXISTING SMOKE DETECTORS ARE | | | TO REMAIN. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2004-05-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-20 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-20 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2004-05-20 00:00:00 | 1) ALL DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3) ALL EXITS AND EXIT ACCESSES SHALL | | | REMAIN CLEAR AT ALL TIMES. | | | | | | 4) ANY NEW LIGHT FIXTURES SHALL NOT | | | INTERFERE WITH ANY EXISTING OR RELOCATED | | | FIRE SPRINKLER HEADS. | | | | | | 5) EXISTING ELECTRIC POWERED SMOKE | | | DETECTORS CONTAINED WITHIN THE UNITS | | | SHALL NOT BE DISTURBED. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE REMODEL OF THE FIRE SPRINKLER | | | SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-06-17 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-06-16 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-16 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2004-06-17 00:00:00 | TO COMM BD#36 | | 2004-06-16 00:00:00 | SENT TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-05-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-14 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-14 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2004-05-14 00:00:00 | TO COMM BD#12 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-07-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-07-01 |
Time |
15:24 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2004-07-01 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2004-07-01 00:00:00 | APPROVED 5-24-04/NO CHANGES ON THE | | | RE-SUBMITTAL. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-05-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-05-24 |
Time |
09:36 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2004-05-24 |
Time |
07:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2004-07-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-07-07 |
Time |
15:27 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2004-07-03 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2004-07-07 00:00:00 | NO SANT. RISER DIAGRAM OR WATER RISER | | | DIAGRAM SUBMITTED. SIGNED/SEALED ENGIN- | | | EERED RISER DIAGRAMS SHALL BE REQUIRED | | | AT TIME OF PLUMBING APPLICATION FOR | | | PERMIT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-06-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-05 |
Time |
05:22 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-06-04 |
Time |
18:30 |
Sent To |
|
|
| Notes |
| 2004-06-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) A WATER CLOSET SHALL BE SET NO CLOSER | | | THAN 15" FROM ITS CENTER TO ANY SIDE | | | WALL OR CLOSER THAN 30" CENTER TO CENTER | | | TO ADJACENT FIXTURES. NEW ROOM FOR W/C | | | AND LAV IS NOT WIDE ENOUGH. SECTION | | | 405.3.1 | | | 2) A SANITARY RISER DIAGRAM AND A WATER | | | RISER DIAGRAM ARE REQUIRED FOR NEW W/C | | | AND LAV. SECTION 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|