Plan Review Details - Permit 04050569
Plan Review Stops For Permit 04050569
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-30 Cont ID  
Sent By jwitmer Date 2004-07-30 Time 16:30 Rev Time 2.22
Received By jwitmer Date 2004-07-30 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-29 Time 16:29 Rev Time 0.75
Received By jwitmer Date 2004-07-16 Time 16:18 Sent To  
Notes
2004-07-16 00:00:002ND REVIEW NO CHANGE, ARCHITECT NEVER
 EVEN LISTED BUILDING COMMENTS ON HIS
 COMMENT SHEET!

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-09 Cont ID  
Sent By jwitmer Date 2004-06-09 Time 11:11 Rev Time 1.22
Received By jwitmer Date 2004-06-09 Time 10:53 Sent To PC
Notes
2004-06-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04050569
 ADD: 1041 45TH ST
 CONT: ANDERSON MOORE CONST CORP
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 WHAT TYPE OF CONSTRUCTION, MINIMUM BUILD
 ING TYPE?
  
 3) SHEET A2.0 SECTION# 3, INDICATES THE
 REMOVAL OF A RAMP TO STAIRS:
 1003.2.7.2 WHERE THE CHANGE IN ELEVATION
 OF 12 IN. OR LESS OCCURS IN EXIT ACCESS
 CORRIDORS, EXITS AND EXIT DISCHARGE,
 RAMPS COMPLYING WITH 1013 SHALL BE PRO-
 VIDED.
 1003.2.7.1. WHERE A CHANGE IN LEVEL
 MEANS OF EGRESS NOT EXCEEDING 21 IN. IS
 ACHIEVED BY A STAIR, THE MINIMUM TREAD
 DEPTH OF SUCH STAIR SHALL BE 13 IN.
 AND THE PRESENCE AND LOCATION OF EACH
 STEP SHALL BE READILY APPARENT.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT DOOR & TRANSOM
 B) WINDOWS
 C) STORM SHUTTERS IF GLAZING ISN'T
 TESTED FOR LARGE MISSLE IMPACT
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) SHEET A1.1 ADMINISTRATION OFFICE,
 DOOR 102 DOESN'T MEET THE MINIMUM CLEAR-
 ENCE AT DOORS.11-4.13.6. INTERIOR SIDE
 REQUIRES 12".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-08 Cont ID  
Sent By dpalmer Date 2004-07-08 Time 10:22 Rev Time 0.50
Received By dpalmer Date 2004-07-08 Time 10:22 Sent To  
Notes
2004-07-08 00:00:00********* PROVISO/ REVISION ********
  
 1)NOTE: PLEASE PROVIDE REVISED PANEL
 SCHEDULE AND CIRCUIT #'S ALONG WITH
 COMPLETED LOAD CALCULATIONS.
 ENGINEER HAS STATED COMPLETE ELECTRICAL
 SYSTEM W/ LOADS IS NOT KNOWN AT THIS
 TIME DUE TO EXISTING CONDITIONS.
 THIS INFORMATION IS TO BE SUBMITTED FOR
 REVIEW BEFORE ROUGH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By dpalmer Date 2004-05-14 Time 07:33 Rev Time 0.33
Received By dpalmer Date 2004-05-14 Time 07:32 Sent To  
Notes
2004-05-14 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULES SHOW
 LOAD CALCULATIONS/LOADS AS BLANK??
 PLEASE SHOW
  
 2)NOTE: PLEASE ALSO INDICATE IF PANELS
 ARE NEW OR EXISTING?
  
 3)NOTE: PLEASE SEE PLANS ARE NOT SIGNED
 AND SEALED BY THE ENGINEER OF RECORD.
 PLEASE SEE FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By nmccray Date 2004-07-12 Time 15:23 Rev Time 0.00
Received By nmccray Date 2004-07-12 Time 15:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By mcarsill Date 2004-05-14 Time 12:56 Rev Time 0.00
Received By mcarsill Date 2004-05-14 Time 12:56 Sent To  
Notes
2004-05-14 00:00:001) DEMOLTION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEMOLITION DEBRIS SHALL BE REMOVED
 DAILY FROM THE SITE.
  
 3) ALL EXITS SHALL REMAIN CLEAR.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 5) PLEASE INDICATE RISE AND RUN AND
 TREAD DEPTH FOR THE NEW STAIR.
  
 6) PLEASE ADVISE IF HANDRAILS ARE
 PRESENT ON BOTH SIDES OF THE NEW STAIRS.
  
 7) PLEASE INDICATE PRESCRIPTIVE
 CODE REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 08:44 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 08:44 Sent To  
Notes
2004-09-15 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-07-29 Time 16:29 Rev Time 0.00
Received By csiegber Date 2004-07-29 Time 16:29 Sent To B
Notes
2004-07-29 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 15:39 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 15:38 Sent To  
Notes
2004-07-01 00:00:00TO COMM BD#61

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-09 Cont ID  
Sent By jwitmer Date 2004-06-09 Time 13:13 Rev Time 0.00
Received By jwitmer Date 2004-05-13 Time 16:03 Sent To PC
Notes
2004-05-13 00:00:00TO COMM BD#4

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-07 Cont ID  
Sent By pkrauss Date 2004-07-07 Time 09:55 Rev Time 0.40
Received By pkrauss Date 2004-07-07 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-01 Cont ID  
Sent By pkrauss Date 2004-06-01 Time 07:47 Rev Time 0.40
Received By pkrauss Date 2004-06-01 Time 07:46 Sent To  
Notes
2004-06-01 00:00:00DENIED:
 1.PLANS ARE NOT SIGNED, SEALED & DATED
 BY THE ENGINEER INDICATED ON PLAN SHEET
 M-1.
  
 2.NO RETURN AIR IS INDICATED FROM THE
 DIRECTORS OFFICE #107.PLEASE CLARIFY,
 EXISTING OR NEW.
  
 3.PLEASE PROVIDE OUTSIDE AIR CALCS PER
 2001 FBC(M) TABLE 403.3.
  
 4.PLEASE INDICATE IF THE FOLLOWING
 EQUIPMENT IS NEW OR EXISTING; AHU 11 &
 12 ALSO FAN COILS 1 & 2.PROVIDE A
 SCHEDULE FOR ALL NEW EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-07-24 Cont ID  
Sent By kstevens Date 2004-07-24 Time 13:38 Rev Time 0.33
Received By kstevens Date 2004-07-24 Time 13:38 Sent To  
Notes
2004-07-24 00:00:00NO PLUMBING WORK SHOWN. PERMIT REQUIRED
 IF DEMO OF PLUMBING REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By kstevens Date 2004-06-02 Time 18:12 Rev Time 0.33
Received By kstevens Date 2004-06-02 Time 18:12 Sent To  
Notes
2004-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURE FACILITIES PER TABLES 1003.1 (BLDG)
 AND 403.1 (PLMBG). INDICATE SQUARE FEET
 OF SPACE. SHOW ALL EXISTING TOILET ROOMS
 AND INDICATE NUMBER OF FIXTURES. SHOW
 LOCATION OF DRINKING FOUNTAINS ECT.
 2) ALL DEMO'D/CAPPED PIPING SHALL BE IN-
 SPECTED PRIOR TO COVERING.
 3) NO DEAD ENDS SHALL BE ALLOWED IN THE
 SANITARY SYSTEM PER SECTION 704.5.
 4) PLANS SHALL BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD. FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]