| 2004-06-07 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE BUILDING IS A TYPE II, FULLY |
| | SPRINKLED.THIS STRUCTURE IS |
| | CONSIDERED A PART OF THE PRIMARY |
| | BUILDING SO MUST ALSO BE TYPE II, |
| | FULLY SPRINKLED.SHOW COMPLIANCE. |
| | |
| | 2.)THE ELEVATIONS INDICATE "INFILL |
| | BY OTHERS".CALCULATIONS WERE |
| | PROVIDED USING A .18 COEFFICIENT FOR |
| | ENCLOSED BUILDINGS.EITHER PROVIDE |
| | INFORMATION ABOUT THE INFILL TO MAKE |
| | THIS AN ENCLOSED BUILDING OR PROVIDE |
| | NEW CALCULATIONS.TEST REPORTS REQUIRED |
| | FOR THE SLIDING GLASS DOORS, LOUVERS, |
| | IMPACT PROTECTION, SWING DOORS. |
| | |
| | 3.)PROVIDE THE INFORMATION REQUIRED |
| | TO BE ON PLANS FBC1606.1.7 2003 |
| | AMENDMENT.MOST OF THE INFORMATION HAS |
| | BEEN PROVIDED BUT THE ENCLOSURE |
| | CLASSIFICATION IS MISSING. |
| | |
| | 4.)PROVIDE THE ENGINEER'S INFORMATION |
| | ON THE PLANS (TITLE BLOCK) AS PER |
| | FAC61G15-23.002 (ADDRESS). |
| | |
| | 5.)PROVIDE PRODUCT APPROVALS FOR ALL |
| | STRUCTURAL COMPONENTS AS PER RULE 9B72. |
| | WWW.FLORIDABUILDING.ORG FOR MORE |
| | INFORMATION. |