Plan Review Details - Permit 04050402
Plan Review Stops For Permit 04050402
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-23 Cont ID  
Sent By lsmith Date 2004-07-23 Time 13:44 Rev Time 0.50
Received By lsmith Date 2004-07-23 Time 13:44 Sent To  
Notes
2004-07-23 00:00:00BUIDING PLAN REVIEW: PROVISO
  
 1. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERK OFFICE AND A
 COPY SUBMITTED TO THE CITY BEFORE A
 PERMIT CAN BE ISSUED.
 2. SEPARATE PERMITS WILL BE REQUIRED FOR
 ALL ELECTRIC, PLUMBING AND MECHANICAL
 WORK.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-05-20 Cont ID  
Sent By lsmith Date 2004-05-20 Time 10:31 Rev Time 0.50
Received By lsmith Date 2004-05-20 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-09 Cont ID  
Sent By dpalmer Date 2005-02-09 Time 11:52 Rev Time 0.25
Received By dpalmer Date 2005-02-09 Time 11:52 Sent To  
Notes
2005-02-09 00:00:00OWES REVISION FEE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-23 Cont ID  
Sent By dpalmer Date 2004-07-23 Time 09:12 Rev Time 0.33
Received By dpalmer Date 2004-07-23 Time 09:12 Sent To  
Notes
2004-07-23 00:00:00*********** PROVISO/REVISION ***********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPEC-
 -TION.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-05-12 Cont ID  
Sent By dpalmer Date 2004-05-12 Time 12:45 Rev Time 0.33
Received By dpalmer Date 2004-05-12 Time 09:49 Sent To  
Notes
2004-05-12 00:00:00***********PROVISO ******************
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL
 NEW CIRCUITING ON PLANS AND CORRELATE
 WITH A SUBMITTED PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW
 BEFORE FINAL. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-02-28 Cont ID  
Sent By nmccray Date 2005-02-28 Time 15:19 Rev Time 0.00
Received By nmccray Date 2005-02-28 Time 15:19 Sent To  
Notes
2005-02-28 00:00:00REVISION DATED 02-02-05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-29 Cont ID  
Sent By mcarsill Date 2004-07-29 Time 12:31 Rev Time 0.00
Received By mcarsill Date 2004-07-29 Time 12:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-05-14 Cont ID  
Sent By mcarsill Date 2004-05-14 Time 10:00 Rev Time 0.00
Received By mcarsill Date 2004-05-14 Time 09:59 Sent To  
Notes
2004-05-14 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-03 Cont ID  
Sent By adarroug Date 2005-02-03 Time 08:31 Rev Time 0.00
Received By adarroug Date 2005-02-03 Time 08:31 Sent To  
Notes
2005-02-03 00:00:00TO "COMM" BOARD #23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 10:03 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 10:03 Sent To  
Notes
2004-07-21 00:00:00TO COMM BD#49

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By kstevens Date 2004-06-02 Time 09:49 Rev Time 0.00
Received By kstevens Date 2004-05-11 Time 16:46 Sent To  
Notes
2004-05-11 00:00:00TO COMM BD#28

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-07 Cont ID  
Sent By hmoser Date 2004-08-07 Time 08:36 Rev Time 0.50
Received By hmoser Date 2004-08-07 Time 08:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-14 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 15:26 Rev Time 0.40
Received By pkrauss Date 2004-05-14 Time 15:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2005-03-02 Cont ID  
Sent By kstevens Date 2005-03-02 Time 11:45 Rev Time 0.50
Received By kstevens Date 2005-03-02 Time 11:45 Sent To  
Notes
2005-03-02 00:00:00NO PLUMBING REVISION SUBMITTED

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-31 Cont ID  
Sent By kstevens Date 2004-07-31 Time 14:33 Rev Time 0.75
Received By kstevens Date 2004-07-31 Time 14:33 Sent To  
Notes
2004-07-31 00:00:00 
  
  
 PASSED/PROVISO
  
 PUMP MANUF. SPECIFICATION SHEETS ARE RE-
 QUIRED AT TIME OF FINAL FOR FIELD INS-
 SPECTOR TO VERIFY LISTING FOR PUMP.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 N

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By kstevens Date 2004-06-02 Time 09:43 Rev Time 0.50
Received By kstevens Date 2004-06-02 Time 09:43 Sent To  
Notes
2004-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 2 SANT. RISER DIAGRAM. A GATE
 VALVE LOCATED ON THE DISCHARGE SIDE OF
 THE CHECK VALVE SHAL BE INSTALLED IN THE
 EJECTOR DISCHARGE PIPING BETWEEN THE
 PUMP OR EJECTOR AND THE GRAVITY DRAINAGE
 SYSTEM. - ACCESS REQUIRED TO VALVES -
 SECTION 712.2. (SHOWN ON INLET SIDE OF
 THE PUMP/EJECTOR).
 2) PUMP SHALL BE LISTED - SUBMIT MANUF.
 SPECIFICATION SHEETS. SECTION 303.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]