| Plan Review Stops For Permit 04050400 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-07-23 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-07-23 |
Time |
13:50 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
2004-07-23 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2004-07-23 00:00:00 | BUILDING PLANS REVIEW: PROVISO | | | | | | 1. SEPARATE PERMITS REQUIREDFOR ELEC, | | | PLUMB.& MECH. | | | | | | 2. A NOTICE OF COMMENCEMENT MUST BE | | | FILED AT THE COUNTY CLERK OFFICE AND A | | | COPY SUBMITTED TO THE CITY BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ANY QUESTIONS PLESE CALL: | | | LEA SMITH, BUILDINGPLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-06-02 |
Time |
10:07 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
2004-06-02 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2004-06-02 00:00:00 | SEE ELEC & PLUMBING NOTES. PLANS MUST | | | BE SIGNED & SEALED PER 481.221 | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-07-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-23 |
Time |
11:56 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-07-23 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-12 |
Time |
13:30 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-05-12 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2004-06-02 00:00:00 | ********** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE PLANS ARE NOT SEALED | | | BY THE ARCH PER FS 481.221 | | | | | | ELECTRICAL PLANS STAMPED IN ERROR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-08-02 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-08-02 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-08-02 00:00:00 | APPROVED BY MIKE CARSILLO 7/28/04LM |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-05-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-14 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-14 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2004-05-14 00:00:00 | 1) WHAT IS PLANNED TO BE STORED IN THE | | | WAREHOUSE. ARE ANY FLAMMABLE OR | | | COMBUSTIBLE LIQUIDS, SOLIDS, OR GASES | | | PLANNED. PLEASE PROVIDE INFORMATION. | | | | | | 2) WHY IS THERE NO FIRE SEPARATION | | | PLANNED BETWEEN THE WAREHOUSE AND THE | | | OFFICE AREA. NFPA 101, THE LIFE SAFETY | | | CODE, 2000 EDITION, SECTION 8-4.1.1 | | | REQUIES THAT "PROTECTION FROM ANY | | | AREA HAVING A DEGREE OF HAZARD GREATER | | | THAN THAT NORMAL TO THE GENERAL | | | OCCUPANCY OF THE BUILDING OR STRUCTURE | | | SHALL BE PROVIDED BY ONE OF THE | | | FOLLOWING MEANS: | | | A) ENCLOSE THE AREA WITH A FIRE BARRIER | | | WITHOUT WINDOWS THAT HAS A 1 HOUR | | | FIRE RESISTANCE RATING IN ACCORDANCE | | | WITH SECTION 8.2. | | | B) PROTECT THE AREA WITH AUTOMATIC | | | EXTINGUISHING SYSTEMS IN ACCORDANCE | | | WITH SECTION 9.7 | | | C) APPLY BOTH 8.4.1.1(1) AND (2) WHERE | | | THE HAZARD IS SEVERE OR WHERE OTHERWISE | | | SPECIFIED BY CHAPTERS 12-42". | | | THE APPENDIX FURTHER EXPLAINS "AREAS | | | REQUIRING SPECIAL HAZARD PROTECTION | | | INCLUDE, BUT ARE NOT LIMITED TO, AREAS | | | SUCH AS THOSE USED FOR STORAGE OF | | | COMBUSTIBLES OR FLAMMABLES, AREAS | | | HOUSING HEAT PRODUCING APPLIANCES, | | | OR AREAS USED FOR MAINTENANCE PURPOSES. | | | | | | 3) ANOTHER EXIT SIGN IS NEEDED TO | | | DIRECT PERSONS FROM THE WAREHOUSE | | | AREA INTO THE OFFICE AREA. | | | | | | 4) NO PORTABLE FIRE EXTINGUISHERS SHOWN | | | ON THE PLANS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-07-21 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-21 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-21 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2004-07-21 00:00:00 | TO COMM BD#57 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-05-14 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2004-05-11 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2004-05-11 00:00:00 | TO COMM BD#29 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2004-05-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-05-14 |
Time |
15:59 |
Rev Time |
0.15 |
| Received By |
pkrauss |
Date |
2004-05-14 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2004-05-14 00:00:00 | NO MECHANICAL PLANS OR INFORMATION INDIC | | | ATED WITH PERMIT APPLICATION |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-07-31 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2004-07-31 |
Time |
14:17 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-02 |
Time |
10:29 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-06-02 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2004-06-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT 2 RESTROOM REFERENCE NOTES "C" | | | STATES "PROVIDE HOT AND COLD WATER". NO | | | HOT WATER PIPING SHOWN. PLEASE CLARIFY. | | | 2) THE PERSONAL SEAL OF THE ARCHITECT | | | SHALL APPEAR ON ALL ARCHITECTRUAL DOC- | | | UMENTS TO BE FILED FOR PUBLIC RECORD. | | | FAC 61G1-16.003 - FS 481.2055 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|