Plan Review Details - Permit 04050400
Plan Review Stops For Permit 04050400
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-23 Cont ID  
Sent By lsmith Date 2004-07-23 Time 13:50 Rev Time 0.50
Received By lsmith Date 2004-07-23 Time 13:50 Sent To  
Notes
2004-07-23 00:00:00BUILDING PLANS REVIEW: PROVISO
  
 1. SEPARATE PERMITS REQUIREDFOR ELEC,
 PLUMB.& MECH.
  
 2. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERK OFFICE AND A
 COPY SUBMITTED TO THE CITY BEFORE A
 PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS PLESE CALL:
 LEA SMITH, BUILDINGPLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By lsmith Date 2004-06-02 Time 10:07 Rev Time 0.50
Received By lsmith Date 2004-06-02 Time 10:07 Sent To  
Notes
2004-06-02 00:00:00SEE ELEC & PLUMBING NOTES. PLANS MUST
 BE SIGNED & SEALED PER 481.221
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-23 Cont ID  
Sent By dpalmer Date 2004-07-23 Time 11:56 Rev Time 0.25
Received By dpalmer Date 2004-07-23 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By dpalmer Date 2004-05-12 Time 13:30 Rev Time 0.33
Received By dpalmer Date 2004-05-12 Time 13:30 Sent To  
Notes
2004-06-02 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS ARE NOT SEALED
 BY THE ARCH PER FS 481.221
  
 ELECTRICAL PLANS STAMPED IN ERROR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-08-02 Cont ID  
Sent By lmartine Date 2004-08-02 Time 17:01 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2004-08-02 00:00:00APPROVED BY MIKE CARSILLO 7/28/04LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By mcarsill Date 2004-05-14 Time 10:09 Rev Time 0.00
Received By mcarsill Date 2004-05-14 Time 10:09 Sent To  
Notes
2004-05-14 00:00:001) WHAT IS PLANNED TO BE STORED IN THE
 WAREHOUSE. ARE ANY FLAMMABLE OR
 COMBUSTIBLE LIQUIDS, SOLIDS, OR GASES
 PLANNED. PLEASE PROVIDE INFORMATION.
  
 2) WHY IS THERE NO FIRE SEPARATION
 PLANNED BETWEEN THE WAREHOUSE AND THE
 OFFICE AREA. NFPA 101, THE LIFE SAFETY
 CODE, 2000 EDITION, SECTION 8-4.1.1
 REQUIES THAT "PROTECTION FROM ANY
 AREA HAVING A DEGREE OF HAZARD GREATER
 THAN THAT NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING OR STRUCTURE
 SHALL BE PROVIDED BY ONE OF THE
 FOLLOWING MEANS:
 A) ENCLOSE THE AREA WITH A FIRE BARRIER
 WITHOUT WINDOWS THAT HAS A 1 HOUR
 FIRE RESISTANCE RATING IN ACCORDANCE
 WITH SECTION 8.2.
 B) PROTECT THE AREA WITH AUTOMATIC
 EXTINGUISHING SYSTEMS IN ACCORDANCE
 WITH SECTION 9.7
 C) APPLY BOTH 8.4.1.1(1) AND (2) WHERE
 THE HAZARD IS SEVERE OR WHERE OTHERWISE
 SPECIFIED BY CHAPTERS 12-42".
 THE APPENDIX FURTHER EXPLAINS "AREAS
 REQUIRING SPECIAL HAZARD PROTECTION
 INCLUDE, BUT ARE NOT LIMITED TO, AREAS
 SUCH AS THOSE USED FOR STORAGE OF
 COMBUSTIBLES OR FLAMMABLES, AREAS
 HOUSING HEAT PRODUCING APPLIANCES,
 OR AREAS USED FOR MAINTENANCE PURPOSES.
  
 3) ANOTHER EXIT SIGN IS NEEDED TO
 DIRECT PERSONS FROM THE WAREHOUSE
 AREA INTO THE OFFICE AREA.
  
 4) NO PORTABLE FIRE EXTINGUISHERS SHOWN
 ON THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 14:35 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 14:35 Sent To  
Notes
2004-07-21 00:00:00TO COMM BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-02 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 15:57 Rev Time 0.00
Received By kstevens Date 2004-05-11 Time 16:48 Sent To  
Notes
2004-05-11 00:00:00TO COMM BD#29

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-05-14 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 15:59 Rev Time 0.15
Received By pkrauss Date 2004-05-14 Time 15:59 Sent To  
Notes
2004-05-14 00:00:00NO MECHANICAL PLANS OR INFORMATION INDIC
 ATED WITH PERMIT APPLICATION

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-31 Cont ID  
Sent By pschmitz Date 2004-07-31 Time 14:17 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By kstevens Date 2004-06-02 Time 10:29 Rev Time 0.50
Received By kstevens Date 2004-06-02 Time 10:04 Sent To  
Notes
2004-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT 2 RESTROOM REFERENCE NOTES "C"
 STATES "PROVIDE HOT AND COLD WATER". NO
 HOT WATER PIPING SHOWN. PLEASE CLARIFY.
 2) THE PERSONAL SEAL OF THE ARCHITECT
 SHALL APPEAR ON ALL ARCHITECTRUAL DOC-
 UMENTS TO BE FILED FOR PUBLIC RECORD.
 FAC 61G1-16.003 - FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]